TIB 080-124 EX
AC/DC DIN Rail Power Supply (PSU), ITE, 1 Output, 80 W, 24 VDC, 3.4 A
- Manufacturer: TRACO POWER
- Product type:
- SVHC: No SVHC (16-Jul-2019)
- Product Range: TIB 080-EX Series
- No. of Outputs: 1 Output
- Output Power Max: 80W
- Current, Output 4: -
- Input Voltage VAC: 85V to 264V
- Power Supply Output Type: Fixed
- Output Current - Output 1: 3.4A
- Output Current - Output 2: -
- Output Current - Output 3: -
- Output Voltage - Output 1: 24VDC
- Output Voltage - Output 2: -
- Output Voltage - Output 3: -
- Output Voltage - Output 4: -
- Power Supply Applications: ITE
| Delivery and price | |
|---|---|
| Units per pack | 50 |
| Price | 64.9 € |
| Current stock | 10+ |
| Lead time | 30 days |
**AC/DC Industrial Power Supply** **TIB 080-EX Series, 80 Watt** - **UL Hazloc Class I, division 2 approval and ATEX certification** - **SEMI F47 compliant for voltage sag immunity** - **Rugged metal case with optional side-mounting** - **Back power immunity** - **150% peak current for 4 s** - **Operating Temp –40°C to +70°C (full load up to 60°C)** - **Adjustable output voltage** - **High Reliability: MTBF 1 mill hrs per IEC 61709** UL 508 UL 60950-1 IEC 62368-1 - **Short circuit and overload protection** - **5-year product warranty** The TIB 080-EX family of next generation of 80 Watt din rail power supplies feature high efficiency operation of up to 90% enabling a slim design with alternative side-mounting for flat panels (DC OK Indicator on both front and side panel). These products certified to UL Hazloc Class 1 / Div 2, and ATEX (EN 60079-0, EN 60079-7. EN 600079-15) for operation in hazardous locations. These convection cooled power supplies have a -40°C to +60°C full load operating temperature range. 150% peak power for up to 4 seconds which is ideal for stepper motors, solenoids or actuators. The TIB 080-EX series has an important Back Power Immunity feature that helps protect against shut-down or malfunction with loads such as inductors and decelerating motors that can feed voltage back to the power supply. Outputs are radio-interference-suppressed to impede radiation at long output lines which reduces the common mode current to within limits of telecommunication ports. The series operate with a high power factor of up to 99% which also minimizes inrush current. Additional qualifications include IEC/EN/UL 60950-1, UL 508 and CB Report with EMC compliance to IEC/EN 61000-6-2 and IEC/EN 61000-6-3. ## **Models** |**Order Code**|**Output Power**<br>**max.**|**Output Voltage**<br>**nom.**(adjustable)|**Output Current**<br>**max.**|**Output Current**<br>**peak**|**Efficiency**<br>**typ.**| |---|---|---|---|---|---| |**TIB 080-112EX**<br>**TIB 080-124EX**<br>**TIB 080-148EX**|80 W|12 VDC(11.8 - 15.0 VDC)<br>24 VDC(23.5 - 28.0 VDC)<br>48 VDC(47.0 - 56.0 VDC)|6'700 mA<br>3'400 mA<br>1'700 mA|10'050 mA<br>5'100 mA<br>2'550 mA|88 %<br>90 %<br>90 %| ## **Options** **on demand** (backorder with MOQ - Optional models with certified DC input non stocking item) **Page 1 / 7** **November 30, 2022** **www.tracopower.com** **TIB 080-EX Series, 80 Watt** ## **Input Specifications** Input Voltage Input Frequency Power Consumption - No load & Vin = 230 VAC - No load & Vin = 115 VAC Input Inrush Current - At 230 VAC - At 115 VAC Power Factor - At 230 VAC - At 115 VAC Recommended Input Fuse Operational Range: 85 - 264 VAC (Full Range) Rated Range: 100 - 240 VAC (Full Range) (Optional models with certified DC input available on demand. Please see PCN no. 038-22.) Operational Range: 45 - 65 Hz Certified: 50/60 Hz 2'000 mW max. 2'000 mW max. 30 A max. 15 A max. 0.48 min. 0.48 min. (The need of an external fuse has to be assessed in the final application.) ## **Output Specifications** Output Voltage Adjustment 12 VDC model: 11.8 - 15.0 VDC 24 VDC model: 23.5 - 28.0 VDC 48 VDC model: 47.0 - 56.0 VDC |Output Voltage Adjustment||12 VDC model: 11.8 - 15.0 VDC<br>24 VDC model: 23.5 - 28.0 VDC<br>48 VDC model: 47.0 - 56.0 VDC| |---|---|---| |||(By trim potentiometer)| |||Outputpower must not exceed ratedpower!| |Voltage Set Accuracy||±0.25% max.| |Regulation|- Input Variation (Vmin - Vmax)|0.1% max.| ||- Load Variation(10 - 90%)|0.5% max.| |Boost Power||Output Current peak: See model table| |||Peak power time: 4 s max.(auto switch off)| |||Off Time: 10 s typ.| |||(During peak operation, the unit continuously| |||switches off the output voltage after 4 s and| |||restarts after approx. 10 s.)| |Ripple and Noise||12 VDC model: 100 mVp-p max.| |(20 MHz Bandwidth)||24 VDC model: 100 mVp-p max.| |||48 VDC model: 200 mVp-pmax.| |Capacitive Load||Infinite| |Minimum Load||Not required| |Temperature Coefficient||±0.02 %/K max.| |Hold-up Time|- At 230 VAC|160 ms min.| ||- At 115 VAC|20 ms min.| |Start-up Time|- At 230 VAC|2'000 ms max.| ||- At 115 VAC|2'000 ms max.| |Short Circuit Protection||Continuous,Automatic recovery| |Overload Protection||Constant Current Mode| |||Switch off after 4 s delay,automatic restart| |Output Current Limitation||155% min. of Iout max.| |Overvoltage Protection||117 - 158% of Vout nom.| |||(depending on model)| |||16 - 19 VDC(12 VDC model)| |||32 - 35 VDC(24 VDC model)| |||56 - 60 VDC(48 VDC model)| |||(In case of an internal error a second voltage| |||regulation loop keeps the output voltage at a save| |||level, the power supply turnes off and tries to| |||restart after 6 s.)| All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated. **Page 2 / 7** **November 30, 2022** **www.tracopower.com** **TIB 080-EX Series, 80 Watt** |Transient Response|- Peak Variation|600 mV max.(10% to 90% Load Step)| |---|---|---| ||- Response Time|2'500 µs typ.(10% to 90% Load Step)| |||| |**Safety Specifications**||| |Safety Standards|- IT / Multimedia Equipment|CSA-C22.2, No. 60950-1| |||EN 60950-1| |||EN 62368-1| |||IEC 60950-1| |||IEC 62368-1| |||UL 60950-1| ||- Industrial Control Equipment|UL 508| ||- ATEX|EN 60079-0| |||EN 60079-15| |||EN 60079-7| |||EX II3G Ex nA nC IIC T4 GC| ||- HazLoc|UL 121201| |||Class I; Div 2; Groups A,B,C,D; T4| ||- Measurement, Control & Lab.|EN 61010-1| |||EN 61010-2-201| |||IEC 61010-1| |||IEC 61010-2-201| |||UL 61010-1| |||UL 61010-2-201| ||- Certification Documents|www.tracopower.com/overview/tib080-ex| |Protection Class||Class I(Prepared): Connection to PE| |Pollution Degree||PD 2| |Over Voltage Category||OVC II| |**EMC Specifications**||| |EMI Emissions||EN 61000-6-3(Generic Residential)| |||EN 61204-3(Low Voltage Power Supplies)| |||EN 50121-3-2(EMC for Rolling Stock)| |||EN 50121-4(Railway Application Signalling)| ||- Conducted Emissions|EN 55011 class B(internal filter)| |||EN 55032 class B(internal filter)| ||- Radiated Emissions|EN 55011 class B(internal filter)| |||EN 55032 class B(internal filter)| ||- Harmonic Current Emissions|EN 61000-3-2,class A| All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated. **Page 3 / 7** **November 30, 2022** **www.tracopower.com** **TIB 080-EX Series, 80 Watt** EMS Immunity - Electrostatic Discharge - RF Electromagnetic Field - EFT (Burst) / Surge - Conducted RF Disturbances - PF Magnetic Field - Voltage Dips & Interruptions EN 50121-3-2 (EMC for Rolling Stock) EN 50121-4 (Railway Application Signalling) EN 61000-6-2 (Generic Industrial) EN 61204-3 (Low Voltage Power Supplies) Air: EN 61000-4-2, ±8 kV, perf. criteria A Contact: EN 61000-4-2, ±4 kV, perf. criteria A EN 61000-4-3, 10 V/m, perf. criteria A EN 61000-4-4, ±2 kV, perf. criteria B L to L: EN 61000-4-5, ±1 kV, perf. criteria B L to PE: EN 61000-4-5, ±2 kV, perf. criteria B EN 61000-4-6, 10 Vrms, perf. criteria A Continuous: EN 61000-4-8, 30 A/m, perf. criteria A 230 VAC / 50 Hz: EN 61000-4-11 20%, 250 periods, perf. criteria C 30%, 25 periods, perf. criteria C 60%, 10 periods, perf. criteria C >95%, 1 period, perf. criteria B >95%, 5 periods, perf. criteria C 115 VAC / 60 Hz: EN 61000-4-11 - Voltage Sag Immunity 20%, 250 periods, perf. criteria C 30%, 25 periods, perf. criteria C 60%, 10 periods, perf. criteria C >95%, 1 period, perf. criteria B >95%, 5 periods, perf. criteria C SEMI F47, criteria A ## **General Specifications** |Relative Humidity||95% max. (non condensing)| |---|---|---| |Temperature Ranges|- OperatingTemperature|–40°C to +70°C| |Power Derating|- High Temperature|2 %/K above 60°C(at standard operation)| |||3 %/K above 60°C(at peak power mode)| ||- Low Input Voltage|3 %/V below 90 VAC(at standard operation)| |||1.5 %/V below 100 VAC(atpeakpower mode)| |Over Temperature|- Protection Mode|Latch off| |Protection Switch Off||| |CoolingSystem||Natural convection(20 LFM)| |Altitude DuringOperation||2'000 m max.| |SwitchingFrequency||60 - 75 kHz (PWM)| |Insulation System||Reinforced Insulation| |Isolation Test Voltage|- Input to Output, 60 s|3'000 VAC| ||- Input to Case or PE, 60 s|1'500 VAC| ||- Output to Case or PE, 60 s|750 VDC| |Creepage|- Input to Output|8 mm min.| ||- Input to Case or PE|4 mm min.| ||- Output to Case or PE|1.5 mm min.| |Clearance|- Input to Output|8 mm min.| ||- Input to Case or PE|4 mm min.| ||- Output to Case or PE|1.5 mm min.| |Leakage Current|- Earth Leakage Current|3500 µA max.| ||- Touch Current|310 µA max.| |Reliability|- Calculated MTBF|1'950'000 h(IEC 61709)| |Environment|- Vibration|EN 61373| |||IEC 60068-2-6| |||2 g, 3 axis, sine sweep, 10-55 Hz, 11 oct/min| ||- Mechanical Shock|EN 61373| |||IEC 60068-2-27| |||25g,3 axis,half sine,11 ms| All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated. **Page 4 / 7** **November 30, 2022** **www.tracopower.com** **TIB 080-EX Series, 80 Watt** |Housing Material|||Aluminum(Chassis)| |---|---|---|---| ||||Stainless Steel(Cover)| |HousingType|||Metal Case| |Mounting Type|||DIN-Rail Mount| ||||(EN 60715 - 35x7.5mm/35x15mm)| |Connection Type|||Screw Terminal| |Weight|||367 g| |Thermal Impedance|- Case to Ambient||1.81 K/W typ.| |Power Back Immunity||12 VDC model:|19 V max.| |||24 VDC model:|35 V max.| |||48 VDC model:|60 V max.| ||||(When external voltage is supplied above set| ||||output voltage and below OVP threshold, the| ||||power supply will function normally without switch| ||||off or destruction, even if external voltage is| ||||applied continuously.)| |Power OK Signal|||Relay Output| ||- Trigger Threshold|12 VDC model:|10.5 - 11.1 VDC| |||24 VDC model:|21 - 23 VDC| |||48 VDC model:|42 - 46 VDC| ||- Power OK||Relay contact closed| ||- Power Off||Relay contact open| ||- Pin Specifications||30 VDC / 1 A max.| |Status Indicator|||Also indicated by green LEDs: front and side| |Environmental Compliance|- REACH Declaration||www.tracopower.com/info/reach-declaration.pdf| ||||REACH SVHC list compliant| ||||REACH Annex XVII compliant| ||- RoHS Declaration||www.tracopower.com/info/rohs-declaration.pdf| ||||Exemptions: 7a, 7c-I| ||||(RoHS exemptions refer to the component| ||||concentration only, not to the overall| ||||concentration in the product (O5A rule).| ||||The SCIP number isprovided on request.)| |**Supporting Documents**|||| |Overview Link(for additional|Documents)||www.tracopower.com/overview/tib080-ex| All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated. **Page 5 / 7** **November 30, 2022** **www.tracopower.com** **TIB 080-EX Series, 80 Watt** ## **Blockdiagram** ## **Outline Dimensions** **==> picture [306 x 173] intentionally omitted <==** **----- Start of picture text -----**<br> * Measurement from front panel to DIN-Rail<br>98,6 ±1 * 32 ±1<br>94,2 ± 1 Combi HeadM3 | 6,35 — —<br>— + Ms<br>U | 24 VDC/3.4 A DC OK<br>DCON<br>| (0) L] ée V adj.<br>©<br>Industrial Power Supply<br>80 W<br>fo} ° hIN ll Model vse<br>TIB 080-124<br>t<br>100-240 VAC,50-60 Hz<br>® ( | 2.00-0.90 AL N a<br>6,35<br>M3<br>DIN-Rail Combi Head<br>Hook<br>114,2 ±1<br>**----- End of picture text -----**<br> All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated. **Page 6 / 7** **November 30, 2022** **www.tracopower.com** **TIB 080-EX Series, 80 Watt** ## **Alternative side mounting** **==> picture [41 x 122] intentionally omitted <==** **----- Start of picture text -----**<br> 24 VDC/ DC OK<br>3.4 A<br>DC<br>ON<br>V adj.<br>Industrial Power Supply<br>80 W<br>Model<br>TIB 080-124<br>100-240 VAC,50-60 Hz<br>2.00-0.90 A<br>L N<br>**----- End of picture text -----**<br> © Copyright 2022 Traco Electronic AG Specifications can be changed without notice. Rev. November 30, 2022 **Page 7 / 7** www.tracopower.com
Updated at June 4, 2026
TRACO Electronic AG, operating globally under the Traco Power brand, is a premier Swiss power supply specialist with over 35 years of industry expertise. Renowned for engineering high-quality power conversion products, the company delivers reliable, cost-effective solutions tailored to the exacting standards of industrial, medical, railway, and automation applications. The cornerstone of our Traco Power portfolio is an extensive selection of power conversion systems. Our offering is heavily focused on a vast array of high-performance AC/DC converters engineered to provide exceptional efficiency and safety for sensitive electronics. This is complemented by a robust lineup of DC/DC converters built to ensure stable, isolated power delivery in challenging environments. Beyond flagship power supplies, the Traco Power range includes specialized passive components and thermal management solutions essential for complete system integration. We supply power inductors, common mode chokes, and power line filters designed for rigorous EMC and RFI suppression, alongside natural convection heat sinks that guarantee optimal thermal performance and prolonged component lifespan.
About Novapart
Novapart is a B2B electronic component broker specialising in stock shortages and cost reduction. We source hard-to-find parts and identify compliant alternatives across a catalogue of 410,000+ components from 500+ manufacturers.
Learn more →Stock Shortage Specialist
When a component is unavailable, discontinued or has an unacceptable lead time, we tap into our network of vetted European and Asian distributors to source what you need — without compromising on quality or traceability.
Request a quote →Compliant Alternatives
We identify pin-to-pin, electrically equivalent substitutes that meet the same certifications (RoHS, AEC-Q100, REACH) as your original specification — validated against datasheets, not just part numbers. Often at a lower cost.
BOM Analysis service →