Image not available
Illustrative purposes only
PEL 112
DATA LOGGER, ENERGY & POWER, 6 CHANNEL
⚠️ Reference pricing provided. In case of supply shortages, we will connect you with our trusted procurement partners to ensure your project's continuity.
- Manufacturer: AEMC INSTRUMENTS
- Product type:
- Data Logger Type:Energy, Power; No. of Channels / Inputs:6 Channel; Sensor / Measurement Type:-; Maximum Samples:-; Data Interface:Ethernet/Wi-Fi LAN & Direct, USB, DataViewSync, S
- SVHC: No SVHC (16-Jul-2019)
- Display Type: -
- Product Range: PEL 110 Series
- Data Interface: Ethernet/Wi-Fi LAN & Direct, USB, DataViewSync, SD Card
- Maximum Samples: -
- Data Logger Type: Energy, Power
- No. of Channels / Inputs: 6 Channel
- Sensor / Measurement Type: -
| Delivery and price | |
|---|---|
| Units per pack | 1 |
| Price | 2595.21 € |
| Current stock | 10+ |
| Lead time | 30 days |
## **POWER QUALITY / ENERGY ANALYZERS, METERS & LOGGERS PEL 110 SERIES** IP **1000 V 600 V** ® 54 **CAT III CAT IV** C US **ETHERNET** ~~a *~~ m= ~~= =—=_ ce|O7~~ **MODEL PEL 112 PRODUCT INCLUDES** _**Supports Negative Temps!**_ **PEL 112** _**(WITHOUT SENSORS) Great for use in Cold Rooms (Down to -4**_ ° _**F)**_ **CAT. #2137.63 T**
Small classic tool bag, (4) 10 ft black test leads in reeling box, (4) black alligator clips, set of (12) color-coded input ID markers, 8 GB SD-card _(installed)_ , USB SD-card reader, USB type A to type B cable, 115 V power cord, NiMH AAA 8.4 V battery _(installed)_ , quick start guide, and USB drive with DataView® software and user manual.
**==> picture [90 x 200] intentionally omitted <==**
**----- Start of picture text -----**<br>
Recordings Covering<br>Several Months!<br>5x Faster!<br>(Than the PEL 102)<br>Dataview’<br>DataViewSync<br>SCAN TO<br>:aue ©pee LEARN<br>MORE<br>**----- End of picture text -----**<br>
## **PEL 112** _**(WITH SENSORS)**_
## **CAT. #2137.53** _**(SHOWN)**_
Small classic tool bag, (3) MiniFlex® MA193-10-BK Sensors, (4) 10 ft black test leads in reeling box, (4) black alligator clips, set of (12) color-coded input ID markers, 8 GB SD-card _(installed)_ , USB SD-card reader, USB type A to type B cable, 115 V power cord, NiMH AAA 8.4 V battery _(installed)_ , quick start guide, and USB drive with DataView® software and user manual.
## **FEATURES**
- Simple-to-use, single-, dual- _(split-phase)_ and three-phase (Y, ∆) power & energy loggers
- 3 voltage and 3 current channels with auto recognition of connected current sensors and probes
- 32 alarms can be configured to receive alerts and reports through email
- Multiple connectivity options supports USB, Ethernet, Wi-Fi, and remote access with DataViewSync™
- • Secure SMTP e-mail transmission via DataViewSync™
- Remote access and real-time monitoring to view and analyze power consumption from anywhere
- Wide range of applications: predictive & preventive maintenance, energy audits, cost optimization and IT infrastructure maintenance
- Supports SD cards up to 32 GB
- Can be powered directly from the phases with PEL Adapter _(sold separately)_
- Compact and magnetized for mounting inside power panels
- Includes FREE DataView® software for configuring, data retrieval, real-time measurement display, data analysis and report generation
## **ACCESSORIES**
## **CAT. #2137.90**
Adapter – 600 V CAT III Power to Phase Adapter for use with Models PEL 112 & PEL 113 ***ADAPTER SOLD SEPARATELY**
## **SEE PAGE 130-131 FOR MORE OPTIONAL ACCESSORIES**
## **ANDROID™ APP AVAILABLE**
## **FOR PEL 112, 113 & 115**
- Configure measurements and recordings
- Display data in real-time
- For use on devices with an Android™ platform
- Software sensors providing all comprehensive and instantaneous motors electrical parameters such as rotation speed, efficiency and torque
**==> picture [44 x 18] intentionally omitted <==**
**----- Start of picture text -----**<br>
Phase<br>Powered<br>**----- End of picture text -----**<br>
**CAT. # DESCRIPTION**
2137.63 Power & Energy Logger Model PEL 112 (No LCD, No Sensors) 2137.53 Power & Energy Logger Model PEL 112 (No LCD, w/3 MA193-10-BK)
**126 www.aemc.com Technical Assistance (800) 343-1391 © 2024 Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All Rights Reserved.**
**Vol. 24 Rev.00 0** 63 **/202** 45
**POWER QUALITY / ENERGY ANALYZERS, METERS & LOGGERS**
|**MODEL**<br>~~SS~~|**PEL 112 & PEL 113**<br>~~SS~~|**PEL 112 & PEL 113**<br>~~SS~~|**PEL 115**<br>~~SS~~|**PEL 115**<br>~~SS~~|
|---|---|---|---|---|
|**Description**|**Meter Only**|**Meter with**<br>**MA193-10-BK Sensors**|**Meter Only**|**Meter with**<br>**196A-24-BK Sensors**|
|**GENERAL**|||||
|**Number of Voltage Channels**|3-(V1,V2,V3)||4-(V1,V2,V3,Earth/Ground)||
|**Number of Current Channels**|3 -(L1,L2,L3)||4 -(L1,L2,L3,Earth/Ground)||
|**Distribution Systems**|Single-/-Split-/3-Phase,DC,etc._(17 choices)_||||
|**MEASUREMENTS**|||||
|**Voltage Range - Phase-Neutral(V)**<br>**2**|(10 to 1000)Vac/dc<br>2||||
|**Voltage Range - Phase-Phase(U)**<br>**2**|(10 to 1000)Vac||(17 to 1000)Vac||
|**Typical Accuracy - Voltage**|±0.2 % R ±0.2 V||||
|**Current Range AC**|5 mA to 12 kAac<br>3|200 mA to 12 kAac|5 mA to 12 kAac<br>3|200 mA to 12 kAac|
|**Current Range DC**|50 mA to 1300 Adc<br>3||||
|**Typical Accuracy - Current**<br>**(Meter Only)**<br>**4**|±0.4 % R ± 0.04 % Inom|–|±0.4 % R ± 0.04 % Inom|–|
|**Network Frequencies**|DC/50/60/400 Hz_(VFD/PWM not available)_||||
|**CALCULATED MEASUREMENTS**|||||
|**Voltage Ratios**|upto 650 kV||||
|**Current Ratios**|Up to 25 kA<br>_(MN193probe, 5 A range)_|Not available with AmpFlex<br>®/<br>MiniFlex<br>®sensors|Up to 25 kA<br>_(MN193probe, 5 A range)_|Not available with AmpFlex<br>®/<br>MiniFlex<br>®sensors|
|**Power(P, P+, Punb, Qf, N, D, S)**|upto 10 GW/Gvar/GVA<br>5||||
|**Energy**|upto 4 EWh/EVAh/Evarh<br>5||||
|**Phase**|cosф,tan<br>PF||||
|**Phase Order / Phasor Diagram**|Yes/Yes_(with DataView_<br>_® or App for Android_<br>_™)_||||
|**Harmonics**|THD for V,A and Harmonics to 50<br>thorder for V,A||||
|**RECORDING**|||||
|**Aggregations(Fixed)**|200 ms/1 s trends||||
|**Aggregations(Selectable)**|(1 to 60)min_(12 choices)_||||
|**Min/Max Values**|Yes||||
|**Alarms**|upto 32 separate alarms||||
|**Emailed Reports**|Yes,alarms andperiodical Min/Max data through DataViewSync<br>®||||
|**Storage Media**|SD Card_(32 GB Max)_||||
|**Recording Length**|Several weeks toyears_(Configuration dependent)_||||
|**OTHER FEATURES**|||||
|**Communication**|USB,Ethernet/Wi-Fi LAN,Ethernet/Wi-Fi Direct,DataViewSync<br>®||||
|**Software**|DataView<br>®included,free Appfor Android<br>™||||
|**NEC Article 220.87**<br>**Load Study Compliant**|Yes, DataView<br>®configuration button and report templates||||
|**Mounting**|Embedded Magnets in Case||Pole MountingKit_(Cat. #2137.82)_||
|**Powered from Phase**|Phase Power Adapter_(Cat. #2137.90)_||Yes||
|**External Power Supply**|120 / 240 V Line Power Cord||Power Adapter||
|**SAFETY AND MECHANICAL**|||||
|**Electrical Safety (IEC 61010)**|600 V CAT IV / 1000 V CAT III||1000 V CAT IV||
|**Ingress Protection**<br>**6**|IP 54 / IP 20||IP 67||
|**Weight**|<2.2 lb(1 kg)||7.5 lb(3.4 kg)||
- 1 Please see user manual for complete technical specifications.
- 2 400 Hz - Phase-Neutral-V (5 to 600) V ; Phase-Phase-U (10 to 600) V.
- 3 Probe dependent.
- 4 Accuracy of connected current probe must be added to this value
5 (G = Giga =109), (E = Exa= 1018)
- 6 (PEL 115) IP 67 with included waterproof accessories;
(PEL 112/113) IP 54 instrument disconnected (de-energized) / IP 20 instrument connected (energized and operating)
**Vol. 24 Rev.00 0** 63 **/202** 4 5 **Technical Assistance (800) 343-1391 www.aemc.com © 2024 Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All Rights Reserved.**
**129**
**POWER QUALITY / ENERGY ANALYZERS, METERS & LOGGERS OPTIONAL ACCESSORIES** ee
|MODEL<br>~~a~~|MAX<br>CONDUCTOR<br>SIZE<br>~~a~~|ACCURACY<br>_(TYPICAL)_<br>~~a~~|TYPICAL<br>ERROR ONAT<br>(50 / 60) HZ<br>~~a~~|CURRENT RANGE<br>~~a~~|USED WITH<br>MODEL<br>~~a~~|CAT. #<br>~~a~~|
|---|---|---|---|---|---|---|
|**MiniFlex**<br>**® Model MA193-10-BK* &**<br>**MiniFlex**<br>**® Model MA193-14-BK* &**<br>**MiniFlex**<br>**® Model MA194-24-BK***<br>**10, 14 & 24 in Sensor**<br>OO<br>oS|2.75 in<br>(70 mm)<br>(10 in sensor)|± 1 %|0.5°|100 mA to 12,000 Aac(1)|PEL 52<br>PEL 112<br>PEL 113<br>PEL 115<br>8333<br>8336<br>8436<br>8345|2140.48<br>(10 in sensor)|
||3.94 in<br>(100 mm)<br>(14 in sensor)|||||2140.50<br>(14 in sensor)|
||7.64 in<br>(194 mm)<br>(24 in sensor)|||||2140.80<br>(24 in sensor)|
|**AC/DC Current Probe Model MR193-BK**<br>©“>|1.6 in<br>(41 mm)|± 2.5 %|-0.80 °|(1 to 1000) Aac<br>(1 to 1300) Adc|PEL 112<br>PEL 113<br>PEL 115<br>8333<br>8336<br>8436<br>8345|2140.28|
|**AC Current Probe Model MN93-BK**<br>Oo|0.78 in<br>(20 mm)|± 1 %|0.8°|(0.5 to 240) Aac|PEL 52<br>PEL 112<br>PEL 113<br>PEL 115<br>8333<br>8336<br>8436<br>8345|2140.32|
|**AC Current Probe Model SR193-BK**<br>OQ“|2.05 in<br>(52 mm)|± 0.3 %|0.2°|(1 to 1200) Aac|PEL 52<br>PEL 112<br>PEL 113<br>PEL 115<br>8333<br>8336<br>8436<br>8345|2140.33|
|**AmpFlex**<br>**® Sensor 24 in**<br>**Model 193-24-BK***<br>O|7.64 in<br>(194 mm)<br>(24 in sensor)|± 1 %|0.5°|100 mA to 12,000 Aac(1)|PEL 52<br>PEL 112<br>PEL 113<br>PEL 115<br>8333<br>8336<br>8436<br>8345|2140.34|
|**AmpFlex**<br>**® Sensor 36 in**<br>**Model 193-36-BK***<br>oc>|11.64 in<br>(291 mm)<br>(36 in sensor)|± 1 %|0.5°|100 mA to 12,000 Aac(1)|PEL 52<br>PEL 112<br>PEL 113<br>PEL 115<br>8333<br>8336<br>8436<br>8345|2140.35|
**130 www.aemc.com Technical Assistance (800) 343-1391 Vol. 24 Rev.0** 20 **0** 63 **/202** 45 **© 2024 Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All Rights Reserved.**
**POWER QUALITY / ENERGY ANALYZERS, METERS & LOGGERS OPTIONAL ACCESSORIES**
|MODEL|MAX<br>CONDUCTOR<br>SIZE|ACCURACY<br>_(TYPICAL)_|TYPICAL<br>ERROR ONAT<br>(50 / 60) HZ|CURRENT RANGE|CURRENT RANGE|CURRENT RANGE|USED WITH<br>MODEL|CAT. #|
|---|---|---|---|---|---|---|---|---|
|**AC Current Probe Model MN193-BK**|0.78 in<br>(20 mm)|± 1 %|0.75°|100 A|200 mA to<br>120 Aac||PEL 52<br>PEL 112<br>PEL 113<br>PEL 115<br>8333<br>8336<br>8436<br>8345|2140.36|
||||1.7°|5 A|5 mA to<br>6 Aac||||
|**AmpFlex**<br>**® Sensor 24 in**<br>**Model 196A-24-BK*****_(Waterproof IP67)_**|7.64 in<br>(194 mm)<br>(24 in sensor)|± 1 %|0°|100 mA to 12,000 Aac(1)|||PEL 115<br>8436|2140.75|
|**MiniFlex**<br>**® Sensor 14 in**<br>**Model MA196-14-BK*****_(Waterproof IP67)_**|3.9 in<br>(99 mm)<br>(14 in sensor)|± 1 %|0°|100 mA to 12,000 Aac(1)|||PEL 115<br>8436|2140.79|
|**AC Current Probe Model MN94**<br>-|0.25 in<br>(7 mm)|± 0.2 %|0.1°|50 mA to 200 Aac|||PEL 52<br>8345|2140.81|
|**AC / DC Current Probe Model E94**|.464 in<br>(11.8 mm)|± 3 %|1.5°|10 A||100 mA to<br>10 AAC|PEL 112<br>PEL 113<br>PEL 115<br>8345|2140.82|
|||± 4 %|1°|100 A||500 mA to<br>100 AAC|||
* Maximum current reduced by a factor of 2 for 400 Hz fundamental frequency.
All current sensors can be used with Models PEL 115 and 8436. However, only the MA196-14-BK and 196A-24-BK flexible sensors are waterproof.
(1) Current range may be limited by sensor size or meter type. Consult factory for NIST Calibration prices.
**Vol. 24 Rev.0** 20 **0** 63 **/202** 4 5 **Technical Assistance (800) 343-1391 www.aemc.com** © 2024 Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All Rights Reserved.
**131**
## **POWER QUALITY / ENERGY ANALYZERS, METERS & LOGGERS SELECTION CHART**
|**MODEL**<br>~~eee~~|**CAT. #**<br>~~eee~~|**DISTRIBUTION**<br>**SYSTEMS**<br>~~eee~~|**PHASE**<br>**ROTATION**<br>~~eee~~|**WAVEFORM**<br>**MODE**<br>~~eee~~|**TRANSIENT**<br>**MODE**<br>~~eee~~|**TRUE INRUSH**<br>**®**<br>**MODE / TYPE /**<br>**DURATION**<br>~~eee~~|**ALARM**<br>**MODE**<br>~~eee~~|**SNAPSHOT**<br>**MODE**<br>~~eee~~|**HARMONIC MODE /**<br>**INTERHARMONIC**<br>**MODE**<br>~~eee~~|**TYPE LCD**<br>~~eee~~|**POWER**<br>**SOURCE**<br>~~eee~~|
|---|---|---|---|---|---|---|---|---|---|---|---|
|**8333**|2136.10|1 P-2 W, 2 P-3 W,<br>3 P-3 W, 3 P-4 W|Yes|||No|10 types /<br>up to 2<br>active /<br>4662<br>recorded|Yes (12)|Yes / No|TFT - 5.7 in<br>diagonal<br>320 x 240<br>resolution|External<br>adapter with<br>internal NiMH<br>battery pack|
|**8336**|2136.30|1 P-2 W, 1 P-3 W,2 P-2<br>W, 2 P-3 W, 2 P-4 W, 3<br>P-3 W,3 P-4 W, 3 P-5 W|Yes|||Yes<br>(RMS+PEAK<br>& RMS) up to 1<br>& 10 min|40 types /<br>up to 7<br>active /<br>16,362<br>recorded|Yes (50)|Yes / No|TFT - 5.7 in<br>diagonal<br>320 x 240<br>resolution|External<br>adapter with<br>internal NiMH<br>battery pack|
|**8345**|2136.35|1 P-2 W, 1 P-3 W,2 P-2<br>W, 2 P-3 W, 2 P-4 W, 3<br>P-3 W,3 P-4 W, 3 P-5 W|Yes|||Yes(rms+PEaK<br>& rms)up to10<br>& 30min|(rms+PEaK<br>40types /<br>20,000<br>w / email<br>notifications|Yes<br>(no limit with<br>SD card)|DC to 127thorder;<br>< 3 % Udin /<br>0 to 62nd order;<br>< 0.5 % Udin|7 in color LCD<br>touch screen:<br>800 x 480<br>(WVGA)|External<br>adapter with<br>Li-ion battery<br>pack|
|**8436**|2136.43|1 P-2 W, 1 P-3 W,2 P-2<br>W, 2 P-3 W, 2 P-4 W, 3<br>P-3 W,3 P-4 W, 3 P-5 W|Yes|||Yes<br>(RMS+PEAK<br>& RMS) up to 1<br>& 10 min|40 types /<br>up to 7<br>active /<br>16,362<br>recorded|Yes (50)|Yes / No|TFT - 5.7 in<br>diagonal<br>320 x 240<br>resolution|Line Power<br>with internal<br>NiMH battery<br>pack|
|**PEL 52**|2137.71|1 P-2 W,2 P-3 W, 1<br>P-3 W|Yes|No||||||Monochrome<br>LCD|Power phase<br>input with<br>internal NiMH<br>battery pack|
|**PEL 112**|2137.63|1 P-2 W, 1 P-3 W, 3 P-3<br>W D2, 3 P-3 W O2, 3 P-3<br>W Y2, 3 P-3 W D3, 3 P-3<br>W O3, 3 P-3 W Y, 3P-3<br>W DB, 3 P-4 W Y, 3 P-4<br>W YB, 3 P-4 W Y2 1/2,<br>3 P-4 W D, 3 P-4 WOD,<br>DC-2 W DC-3 W, DC-4 W|W D2, 3 P-3 W O2, 3 P-3<br>W Y2, 3 P-3 W D3, 3 P-3<br>Yes|No|||||Yes / No|None|Line Power<br>with internal<br>NiMH battery<br>pack|
|**PEL 113**|2137.64|1 P-2 W, 1 P-3 W, 3 P-3<br>W D2, 3 P-3 W O2, 3 P-3<br>W Y2, 3 P-3 W D3, 3 P-3<br>W O3, 3 P-3 W Y, 3P-3<br>W DB, 3 P-4 W Y, 3 P-4<br>W YB, 3 P-4 W Y2 1/2,<br>3 P-4 W D, 3 P-4 WOD,<br>DC-2 W DC-3 W, DC-4 W|W D2, 3 P-3 W O2, 3 P-3<br>W Y2, 3 P-3 W D3, 3 P-3<br>Yes|No|||||Yes / No|Monochrome<br>LCD|Line Power<br>with internal<br>NiMH battery<br>pack|
|**PEL 115**|2137.56|1 P-2 W, 1 P-3 W, 3 P-3<br>W D2, 3 P-3 W O2, 3 P-3<br>W Y2, 3 P-3 W D3, 3 P-3<br>W O3, 3 P-3 W Y, 3P-3<br>W DB, 3 P-4 W Y, 3 P-4<br>W YB, 3 P-4 W Y2 1/2,<br>3 P-4 W D, 3 P-4 WOD,<br>DC-2 W DC-3 W, DC-4 W|W D2, 3 P-3 W O2, 3 P-3<br>W Y2, 3 P-3 W D3, 3 P-3<br>Yes|No|||||Yes / No|Monochrome<br>LCD|Power<br>phase input<br>or external<br>adapter with<br>internal NiMH<br>battery pack|
~~i~~ **132 www.aemc.com Technical Assistance (800) 343-1391 Vol. 24 Rev.0** 10 **0** 63 **/202** 45 _@AEMC © 2024 Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All Rights Reserved.
**POWER QUALITY / ENERGY ANALYZERS, METERS & LOGGERS**
## Data Analysis and Reporting Software
## **Configure all functions:**
- Display and analyze real-time data on your PC
- Configure functions and parameters from your PC
- Customize views, templates and reports to your exact needs
- Create and store a complete library of configurations that can be uploaded as needed
- Zoom in and out and pan through sections of the graph to analyze the data
- Download, display and analyze recorded data
- Display waveforms, trend graphs, harmonic spectrums, text summaries, transients, event logs and stored alarms
- Print reports using standard or custom templates you design
- Free updates available on our website **www.aemc.com**
**Reports can be displayed on a PC and printed. Each report includes all test results in a tabular and graphic format, as well as operator and test site information. Comments typed by the operator will also be included.**
Vol. 24 Rev.00 06/2024 **Technical Assistance (800) 343-1391** www.aemc.com 133 © 2024 Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All Rights Reserved.
**POWER QUALITY / ENERGY ANALYZERS, METERS & LOGGERS**
## Data Analysis and Reporting Software
_**DataView ® software, user manual and**_ www.aemc.com - _**quick start guide are included in the USB Drive**_
Configure basic information regarding Auto Power OFF, instrument name and location, display contrast and brightness _(Models PEL 113 & PEL 115)_ , setting of the real-time clock and SD-card formatting is easily accomplished from the General tab.
## **Typical DataView® Functional Digital & Graphical Display**
## **Control Panel Trend View**
_In the PEL Control Panel you will find all the necessary tools and selection buttons to review recorded data as trend plots or tabular lists._
The Measurement tab specifies the electrical distribution system, voltage ratios, and nominal frequency.
> Title Bar ~~a~~ Menu Bar ~~SH~~ ] ric cast View instrument
> Tool Bar ~~SP~~ R B66 Parameter Se5 fflWorkstationPEL Network SelectionButtons ff G{QPEL102-165908KGHReal-timeRecorded Data @ Pecordedratte Tabular ~~19~~ @ Recorded ~~ca-time Data~~ Listing [Q Realtime Data of Data Eft JPO Office PEL at Cursor Position Af Conference[G& Realtime[Recorded] PEL Dat
> © 0aMy 30Openffessions 44 Fox10 min Navigation [9 tsfteasrements Tree | El event tog Data Plot/ Listing Area Movable Cursor
In the Recording tab, configure the instrument to measure _(and record)_ over a user selectable recording period. Select demand intervals and view available memory for data storage.
## _**NEW!**_ **Effortlessly Perform**
**134 www.aemc.com Technical Assistance (800) 343-1391 Vol. 24 Rev.0** 10 **0** 63 **/202** 45 © 2024 Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All Rights Reserved.
Updated at June 4, 2026
About Novapart
Novapart is a B2B electronic component broker specialising in stock shortages and cost reduction. We source hard-to-find parts and identify compliant alternatives across a catalogue of 410,000+ components from 500+ manufacturers.
Learn more →Stock Shortage Specialist
When a component is unavailable, discontinued or has an unacceptable lead time, we tap into our network of vetted European and Asian distributors to source what you need — without compromising on quality or traceability.
Request a quote →Compliant Alternatives
We identify pin-to-pin, electrically equivalent substitutes that meet the same certifications (RoHS, AEC-Q100, REACH) as your original specification — validated against datasheets, not just part numbers. Often at a lower cost.
BOM Analysis service →