- Manufacturer: SIEMENS
- Product type: Electronic Circuit Breakers
- SVHC: To Be Advised
- Trip Time: -
- No. of Poles: 4 Pole
- Product Range: SENTRON 3VA2 Series
- Current Rating: 250A
- Supply Voltage: 690V
- Load Current Max: -
- Circuit Breaker Mounting: -
| Delivery and price | |
|---|---|
| Units per pack | 1 |
| Price | 1392.0 € |
| Current stock | 10+ |
| Lead time | 30 days |
**3VA2025-5JP42-0AA0**
**Data sheet**
circuit breaker 3VA2 IEC Frame 100 breaking capacity class M Icu=55 kA @ 415 V 4-pole, line protection ETU550, LSI, In=25 A overload protection Ir=10 A...25 A short-circuit protection Isd=0.6..10x In, Ii=1.5..12x In neutral conductor protection adjustable (OFF, up to 160%) nut keeper kit
|**Model**||
|---|---|
|product brand name|SENTRON|
|product designation|Molded case circuit breaker|
|design of theproduct|Lineprotection|
|design of the overcurrent release|ETU550|
|protection function of the overcurrent release|LSI|
|number of poles|4|
|**General technical data**||
|insulation voltage / rated value|800 V|
|operatingvoltage / at AC / rated value|690 V|
|power loss[W]/ maximum|0.84 W|
|power loss [W] / for rated value of the current / at AC / in hot|0.28 W|
|operatingstate /perpole||
|mechanical service life(operatingcycles)/ typical|25 000|
|electrical endurance(operatingcycles)/ at AC-1 / at 380/415 V|15 000|
|electrical endurance(operatingcycles)/ at AC-1 / at 690 V|10 500|
|product feature / for neutral conductors / upgradable/retrofittable|No|
|/ short-circuit and overloadproof||
|ground-fault monitoringversion|Without|
|product function||
|● communication function|Yes|
|● other measurement function|No|
|Net Weight|2.76 kg|
|**Current**||
|operational current||
|● at 40 °C|25 A|
|● at 45 °C|25 A|
|● at 50 °C|25 A|
|● at 55 °C|25 A|
|● at 60 °C|25 A|
|● at 65 °C|25 A|
|● at 70 °C|25 A|
|**Switching capacity according to IEC 60947**||
|switchingcapacityclass of the circuit breaker|M|
|maximum short-circuit current breakingcapacity (Icu)||
|● at 240 V|85 kA|
Subject to change without notice © Copyright Siemens
3VA20255JP420AA0 Page 1/6
5/31/2026
||● at 415 V|55 kA||
|---|---|---|---|
||● at 440 V|55 kA||
||● at 500 V|36 kA||
||● at 690 V|2 kA||
||operatingshort-circuit current breakingcapacity (Ics)|||
||● at 240 V|85 kA||
||● at 415 V|55 kA||
||● at 440 V|55 kA||
||● at 500 V|36 kA||
||● at 690 V|2 kA||
||short-circuit current makingcapacity (Icm)|||
||● at 240 V|187 kA||
||● at 415 V|121 kA||
||● at 440 V|121 kA||
||● at 500 V|75.5 kA||
||● at 690 V|3 kA||
||**Adjustable parameters**|||
||product feature / for L-tripping/ can be switched on/off|No||
||adjustable response value setting current (Ir) / of the L-trip / with<br>I2t characteristic|||
||● minimum|10 A||
||● maximum|25 A||
||adjustable response value delay time (tr) / for L-tripping / with I2t<br>characteristic|||
||● minimum|0.5 s||
||● maximum|25 s||
||adjustable response value setting current (Isd) / of S-trip / with<br>I0t characteristic|||
||● minimum|15 A||
||● maximum|250 A||
||adjustable response value setting current (Isd) / of S-trip / with<br>I2t characteristic|||
||● minimum|15 A||
||● maximum|250 A||
||adjustable response value delay time (tsd) / for S-tripping / with<br>I0t characteristic|||
||● minimum|0.05 s||
||● maximum|0.5 s||
||adjustable response value delay time (tsd) / for S-tripping / with<br>I2t characteristic|||
||● minimum|0.05 s||
||● maximum|0.5 s||
||adjustable response value settingcurrent(Ii)/ for I-tripping|||
||● minimum|37 A||
||● maximum|300 A||
||adjustable settingcurrent(InN)/ for N-tripping|||
||● minimum|10 A||
||● maximum|40 A||
||design of the N-conductorprotection|adjustable OFF; 40% to 160%||
||product function /groundingprotection|No||
||**Mechanical Design**|||
||product component|||
||● undervoltage release|No||
||● voltage trigger|No||
||● tripindicator|No||
||height[in]|7.13 in||
||height|181 mm||
||width[in]|5.51 in||
||width|140 mm||
||depth[in]|3.39 in||
||depth|86 mm||
Subject to change without notice © Copyright Siemens
3VA20255JP420AA0 Page 2/6
5/31/2026
**==> picture [511 x 677] intentionally omitted <==**
**----- Start of picture text -----**<br>
|||||||
|---|---|---|---|---|---|
|a|Connections|
|arrangement of electrical connectors / for main current circuit|Front terminal|
|type of electrical connection / for main current circuit|on both sides nut keeper kit|
|type of connectable conductor cross-sections / for flat-bar|13 x 1 mm|
|terminal connection / minimum|
|type of connectable conductor cross-sections / for flat-bar|25 x 8 mm|
|terminal connection / maximum|
|design of the surface / of the connections / on the top of the|tin|
|switch (N, 1, 3, 5)|
|design of the surface / of the connections / on the bottom of the|tin|
|switch (N, 2, 4, 6)|
|a|Auxiliary circuit|
|number of CO contacts / for auxiliary contacts|0|
|a|Accessories|
|product extension / optional / motor drive|Yes|
|Environmental conditions|
|ee|
|protection class IP / on the front|IP40|
|ambient temperature|
|● during operation / minimum|-25 °C|
|● during operation / maximum|70 °C|
|● during storage / minimum|-40 °C|
|● during storage / maximum|80 °C|
|ee|Environmental footprint|
|global warming|potential [CO2 eq] / total|61.814 kg|
|global warming|potential [CO2 eq] / during manufacturing|14.6 kg|
|global warming|potential [CO2 eq] / during operation|48.9 kg|
|global warming|potential [CO2 eq] / after end of life|-2.2 kg|
|re|Siemens Eco Profile (SEP)|Siemens EcoTech|
|reference code / according to IEC 81346-2|Q|
|Approvals / Certificates|
|General Product Approval|
|~~|Miscellaneous|FAL|_|Confirmation|
|General Product Approval|EMV|Test Certificates|
|Miscellaneous|Special Test Certific-|Type Test Certific-|
|ate|ates/Test Report|
|UKca|Sf|@|——_—_—|
|Maritime application|
|-|
|CCS (China Classifica|
|tion Society)|
|7|a|us|=|os|os|
|other|Dangerous goods|Environment|
|ss|Miscellaneous|Miscellaneous|Confirmation|Transport Information|Environmental Con-|
|firmations|
**----- End of picture text -----**<br>
**Environment**
Subject to change without notice © Copyright Siemens
3VA20255JP420AA0 Page 3/6
5/31/2026
firmations ~~—_—_~~
## Environmental Confirmations
~~e~~ **Further information Information on the packaging** https://support.industry.siemens.com/cs/ww/en/view/109813875 **Information for data generation and storage** https://support.industry.siemens.com/cs/ww/en/view/109995012 **Information- and Downloadcenter (Catalogs, Brochures,…)** https://www.siemens.com/lowvoltage/catalogs **Industry Mall (Online ordering system)** https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3VA2025-5JP42-0AA0 **Service&Support (Manuals, Certificates, Characteristics, FAQs,...)** https://support.industry.siemens.com/cs/ww/en/ps/3VA2025-5JP42-0AA0 **Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)** https://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VA2025-5JP42-0AA0 **CAx-Online-Generator** https://www.siemens.com/cax **Tender specifications** https://www.siemens.com/specifications
**Characteristic curves** https://curves.simaris.siemens.com/curves/<mmp_prod_noCOMP="HAUPT"></mmp_prod__no>
Subject to change without notice © Copyright Siemens
3VA20255JP420AA0 Page 4/6
5/31/2026
**==> picture [259 x 330] intentionally omitted <==**
**----- Start of picture text -----**<br>
-Q<br>cHr ~y ve yi VL ETU550<br>L<br>I> S<br>EER] I> I> I> I> | x I>> I<br>N N<br>PETE} |r<br>I>> I>> I>> I>><br>aan<br>——<br>| |<br>¢ ||<br>| [|]<br>¢ |<br>| [|]<br>{|<br>EFB RCD<br>| [|]<br>1 3 5 7<br>N<br>N<br>2 4 6 8 -X2 -X3<br>**----- End of picture text -----**<br>
**last modified:**
4/23/2026
Subject to change without notice © Copyright Siemens
3VA20255JP420AA0 Page 5/6
5/31/2026
Subject to change without notice © Copyright Siemens
3VA20255JP420AA0 Page 6/6
5/31/2026
Updated at April 28, 2026
About Novapart
Novapart is a B2B electronic component broker specialising in stock shortages and cost reduction. We source hard-to-find parts and identify compliant alternatives across a catalogue of 410,000+ components from 500+ manufacturers.
Learn more →Stock Shortage Specialist
When a component is unavailable, discontinued or has an unacceptable lead time, we tap into our network of vetted European and Asian distributors to source what you need — without compromising on quality or traceability.
Request a quote →Compliant Alternatives
We identify pin-to-pin, electrically equivalent substitutes that meet the same certifications (RoHS, AEC-Q100, REACH) as your original specification — validated against datasheets, not just part numbers. Often at a lower cost.
BOM Analysis service →