Image not available
Illustrative purposes only
3VA2010-6KQ42-0AA0
Electronic Circuit Breaker, MCCB, 3VA2, 4P, 85 kA, 415 V, 100 A, Without Auxiliary Contact
⚠️ Reference pricing provided. In case of supply shortages, we will connect you with our trusted procurement partners to ensure your project's continuity.
- Manufacturer: SIEMENS
- Product type: Electronic Circuit Breakers
- SVHC: To Be Advised
- Trip Time: -
- No. of Poles: 4 Pole
- Product Range: SENTRON 3VA2 Series
- Current Rating: 100A
- Supply Voltage: 690V
- Load Current Max: -
- Circuit Breaker Mounting: -
| Delivery and price | |
|---|---|
| Units per pack | 1 |
| Price | 1992.3 € |
| Current stock | 10+ |
| Lead time | 30 days |
**3VA2010-6KQ42-0AA0**
**Data sheet**
circuit breaker 3VA2 IEC Frame 100 breaking capacity class H Icu=85 kA @ 415 V 4-pole, line protection ETU860, LSIG, In=100 A overload protection Ir=40 A...100 A short-circuit protection Isd=0.6..10x In, Ii=1.5..12x In neutral conductor protection adjustable (OFF, up to 100%) ground-fault protection, can be switched off Ig=0.2...1 x In= tg=0.05-0.8s nut keeper kit
|**Model**||
|---|---|
|product brand name|SENTRON|
|product designation|Molded case circuit breaker|
|design of theproduct|Lineprotection|
|design of the overcurrent release|ETU860|
|protection function of the overcurrent release|LSIG|
|number of poles|4|
|**General technical data**||
|insulation voltage / rated value|800 V|
|operatingvoltage / at AC / rated value|690 V|
|power loss[W]/ maximum|13.5 W|
|power loss [W] / for rated value of the current / at AC / in hot|4.5 W|
|operatingstate /perpole||
|mechanical service life(operatingcycles)/ typical|25 000|
|electrical endurance(operatingcycles)/ at AC-1 / at 380/415 V|15 000|
|electrical endurance(operatingcycles)/ at AC-1 / at 690 V|10 500|
|product feature / for neutral conductors / upgradable/retrofittable|No|
|/ short-circuit and overloadproof||
|ground-fault monitoringversion|Summation current formation L + N conductor|
|product function||
|● communication function|Yes|
|● other measurement function|Yes|
|Net Weight|2.687 kg|
|**Current**||
|operational current||
|● at 40 °C|100 A|
|● at 45 °C|100 A|
|● at 50 °C|100 A|
|● at 55 °C|100 A|
|● at 60 °C|100 A|
|● at 65 °C|100 A|
|● at 70 °C|100 A|
|**Switching capacity according to IEC 60947**||
|switchingcapacityclass of the circuit breaker|H|
|maximum short-circuit current breakingcapacity (Icu)||
|● at 240 V|110 kA|
3VA20106KQ420AA0 Page 1/7
Subject to change without notice © Copyright Siemens
5/30/2026
|● at 415 V|85 kA|
|---|---|
|● at 440 V|85 kA|
|● at 500 V|55 kA|
|● at 690 V|2 kA|
|operatingshort-circuit current breakingcapacity (Ics)||
|● at 240 V|110 kA|
|● at 415 V|85 kA|
|● at 440 V|85 kA|
|● at 500 V|55 kA|
|● at 690 V|2 kA|
|short-circuit current makingcapacity (Icm)||
|● at 240 V|242 kA|
|● at 415 V|187 kA|
|● at 440 V|187 kA|
|● at 500 V|121 kA|
|● at 690 V|3 kA|
|**Adjustable parameters**||
|product feature / for L-tripping/ can be switched on/off|No|
|adjustable response value setting current (Ir) / of the L-trip / with<br>I2t characteristic||
|● minimum|40 A|
|● maximum|100 A|
|adjustable response value delay time (tr) / for L-tripping / with I2t<br>characteristic||
|● minimum|0.5 s|
|● maximum|25 s|
|adjustable response value setting current (Isd) / of S-trip / with<br>I0t characteristic||
|● minimum|60 A|
|● maximum|1 000 A|
|adjustable response value setting current (Isd) / of S-trip / with<br>I2t characteristic||
|● minimum|60 A|
|● maximum|1 000 A|
|adjustable response value delay time (tsd) / for S-tripping / with<br>I0t characteristic||
|● minimum|0.05 s|
|● maximum|0.5 s|
|adjustable response value delay time (tsd) / for S-tripping / with<br>I2t characteristic||
|● minimum|0.05 s|
|● maximum|0.5 s|
|adjustable response value settingcurrent(Ii)/ for I-tripping||
|● minimum|150 A|
|● maximum|1 200 A|
|adjustable current response value current / for G-tripping / with<br>standard characteristic||
|● initial value|20 A|
|● full-scale value|100 A|
|adjustable response value delay time (tg) / for G-tripping / with<br>I0t characteristic||
|● minimum|0.05 s|
|● maximum|0.8 s|
|adjustable response value setting current (Ig) / for G-tripping /<br>with I2t characteristic||
|● minimum|20 A|
|● maximum|100 A|
|adjustable response value delay time (tg) / for G-tripping / with<br>I2t characteristic||
|● minimum|0.05 s|
|● maximum|0.8 s|
|adjustable setting current (InN) / for N-tripping||
3VA20106KQ420AA0 Page 2/7
Subject to change without notice © Copyright Siemens
5/30/2026
|● minimum|20 A|
|---|---|
|● maximum|100 A|
|design of the N-conductorprotection<br>~~re~~|adjustable OFF; 20% to 100%<br>~~re~~|
|product function /groundingprotection<br>~~re~~|Yes<br>~~re~~|
|**Mechanical Design**||
|product component||
|● undervoltage release|No|
|● voltage trigger|No|
|● tripindicator|No|
|height[in]|7.13 in|
|height|181 mm|
|width[in]|5.51 in|
|width<br>~~ee~~|140 mm<br>~~ee~~|
|depth[in]<br>~~ee~~|3.39 in<br>~~ee~~|
|depth<br>~~ee~~|86 mm<br>~~ee~~|
|**Connections**||
|arrangement of electrical connectors / for main current circuit|Front terminal|
|type of electrical connection / for main current circuit|on both sides nut keeper kit|
|type of connectable conductor cross-sections / for flat-bar<br>terminal connection / minimum|13 x 1 mm|
|type of connectable conductor cross-sections / for flat-bar<br>terminal connection / maximum|25 x 8 mm|
|design of the surface / of the connections / on the top of the<br>switch(N, 1, 3, 5)|tin|
|design of the surface / of the connections / on the bottom of the<br>switch(N, 2, 4, 6)|tin|
|**Auxiliary circuit**<br>~~|~~||
|number of CO contacts / for auxiliarycontacts<br>~~|~~|0<br>~~|~~|
|**Accessories**<br>~~|~~||
|product extension / optional / motor drive<br>~~|~~|Yes<br>~~|~~|
|**Environmental conditions**<br>~~|~~||
|protection class IP / on the front<br>~~|~~|IP40<br>~~|~~|
|ambient temperature||
|● duringoperation / minimum|-25 °C|
|● duringoperation / maximum|70 °C|
|● duringstorage / minimum|-40 °C|
|● duringstorage / maximum|80 °C|
|**Environmental footprint**<br>~~|~~||
|global warming potential[CO2 eq]/ total<br>~~|~~|61.814 kg<br>~~|~~|
|global warming potential[CO2 eq]/ duringmanufacturing|14.6 kg|
|global warming potential[CO2 eq]/ duringoperation|48.9 kg|
|global warming potential[CO2 eq]/ after end of life<br>~~re~~|-2.2 kg<br>~~re~~|
|Siemens Eco Profile(SEP)<br>~~re~~|Siemens EcoTech<br>~~re~~|
|**reference code / according to IEC 81346-2**<br>~~re~~|Q<br>~~re~~|
|**Approvals / Certificates**||
|**General Product Approval**||
**General Product ApEMV proval**
**Test Certificates**
**Maritime application**
Miscellaneous Special Test CertificType Test Certificate ates/Test Report Q ~~®~~ — ~~~~~~ @
3VA20106KQ420AA0 Page 3/7
Subject to change without notice © Copyright Siemens
5/30/2026
**Maritime application other** CCS (China ClassificaMiscellaneous tion Society) 8 = ~~8~~ di mr os RMRS **other Dangerous goods Environment** Miscellaneous Confirmation Transport Information Environmental Con- ~~— —~~ [F288]QC PASS ~~—— —~~ firmations ese ~© **Environment** Environmental Confirmations —_ a EPD ~~a~~ **Further information Information on the packaging** https://support.industry.siemens.com/cs/ww/en/view/109813875 **Information for data generation and storage** https://support.industry.siemens.com/cs/ww/en/view/109995012 **Information- and Downloadcenter (Catalogs, Brochures,…)** https://www.siemens.com/lowvoltage/catalogs **Industry Mall (Online ordering system)** https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3VA2010-6KQ42-0AA0 **Service&Support (Manuals, Certificates, Characteristics, FAQs,...)** https://support.industry.siemens.com/cs/ww/en/ps/3VA2010-6KQ42-0AA0 **Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)** https://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VA2010-6KQ42-0AA0 **CAx-Online-Generator** https://www.siemens.com/cax **Tender specifications** https://www.siemens.com/specifications **Characteristic curves** https://curves.simaris.siemens.com/curves/<mmp_prod_noCOMP="HAUPT"></mmp_prod__no>
3VA20106KQ420AA0 Page 4/7
Subject to change without notice © Copyright Siemens
5/30/2026
**==> picture [239 x 331] intentionally omitted <==**
**----- Start of picture text -----**<br>
-Q<br>ETU860<br>L<br>! C c]<br>I> S<br>- x<br>- cl s isis| | &<br>I>> I<br>I> I> I> I><br>| Py | fl |<br>N N<br>| I>> I>> I>> I>> |<br>G<br>- TT I>> I>> I>> I>> | &<br>P MF<br>LTT<br>ee<br>f |<br>¢, [ | |<br>[fT<br>{| |<br>[ (|<br>EFB RCD<br>| LOL<br>1 3 5 7<br>N<br>N<br>2 4 6 8 -X2 -X3<br>**----- End of picture text -----**<br>
**last modified:**
4/18/2025
3VA20106KQ420AA0 Page 5/7
Subject to change without notice © Copyright Siemens
5/30/2026
3VA20106KQ420AA0 Page 6/7
Subject to change without notice © Copyright Siemens
5/30/2026
3VA20106KQ420AA0 Page 7/7
Subject to change without notice © Copyright Siemens
5/30/2026
Updated at April 28, 2026
About Novapart
Novapart is a B2B electronic component broker specialising in stock shortages and cost reduction. We source hard-to-find parts and identify compliant alternatives across a catalogue of 410,000+ components from 500+ manufacturers.
Learn more →Stock Shortage Specialist
When a component is unavailable, discontinued or has an unacceptable lead time, we tap into our network of vetted European and Asian distributors to source what you need — without compromising on quality or traceability.
Request a quote →Compliant Alternatives
We identify pin-to-pin, electrically equivalent substitutes that meet the same certifications (RoHS, AEC-Q100, REACH) as your original specification — validated against datasheets, not just part numbers. Often at a lower cost.
BOM Analysis service →