**3RV2711-0CD10**
**Data sheet**
circuit breaker frame size S00 for system protection with approval circuit breaker UL 489, CSA C22.2 no. 5-02 thermal overload release 0.25 A short-circuit release 3.3 A screw terminal standard switching capacity
|circuit breaker frame size S00 for system protection with approval circuit breaker<br>UL 489, CSA C22.2 no. 5-02 thermal overload release 0.25 A short-circuit release<br>3.3 A screw terminal standard switching capacity<br>**product brand name**<br>SIRIUS<br>**product designation**<br>Circuit breaker<br>**design of theproduct**<br>For systemprotection accordingto UL 489/CSA C22.2 No. 5<br>**product type designation**<br>3RV2<br>**General technical data**<br>**Product equipment of circuit breaker for motor protection**<br>**complete unit withprotection device**<br>Yes<br>**size of the circuit-breaker**<br>S00<br>product function disconnector functionality<br>Yes<br>product extension auxiliaryswitch<br>Yes<br>**power loss[W] for rated value of the current**<br>● at AC in hot operatingstate<br>5.5 W<br>● at AC in hot operatingstateperpole<br>1.8 W<br>**type of calculation ofpower loss current-dependent**<br>quadratic<br>insulation voltage with degree ofpollution 3 at AC rated value<br>690 V<br>**surge voltage resistance rated value**<br>6 kV<br>**maximumpermissible voltage forprotective separation**<br>● in networks with ungrounded star point between main and<br>auxiliarycircuit<br>400 V<br>● in networks with grounded star point between main and<br>auxiliarycircuit<br>400 V<br>**protection class IP**<br>● on the front accordingto IEC 60529<br>IP20<br>● on the front<br>IP20<br>● of the terminal<br>IP00<br>**shock resistance according to IEC 60068-2-27**<br>25g/ 11 ms(rectangular impulse and sinepulse)<br>**mechanical service life(operating cycles)**<br>● of the main contacts typical<br>100 000<br>● of auxiliarycontacts typical<br>100 000<br>electrical endurance(operatingcycles)typical<br>100 000<br>**reference code according to IEC 81346-2**<br>Q<br>**continuous current rated value**<br>0.25 A<br>**Substance Prohibitance(day/month/year)**<br>10/01/2009<br>**SVHC substance name**<br>Lead CAS-No. 7439-92-1<br>**Net Weight**<br>0.425g<br>**Ambient conditions**<br>installation altitude at height above sea level maximum<br>2 000 m<br>**ambient temperature**<br>● duringoperation<br>-20 ... +60 °C<br>● duringstorage<br>-50 ... +80 °C<br>● duringtransport<br>-50 ... +80 °C<br>**temperature compensation**<br>-20 ... +60 °C<br>relative humidityduringoperation<br>10 ... 95 %<br>**Main circuit**<br>**number ofpoles for main current circuit**<br>3<br>**type of voltage for main current circuit**<br>AC<br>**operating voltage**<br>● rated value<br>690 V<br>● rated value<br>20 ... 690 V<br>Siemens~~@~~<br>EcoTech|circuit breaker frame size S00 for system protection with approval circuit breaker<br>UL 489, CSA C22.2 no. 5-02 thermal overload release 0.25 A short-circuit release<br>3.3 A screw terminal standard switching capacity||
|---|---|---|
||SIRIUS||
||Circuit breaker||
||For systemprotection accordingto UL 489/CSA C22.2 No. 5||
||3RV2||
||3||
||AC||
||||
||690 V||
||20 ... 690 V||
3RV27110CD10 Page 1/5
Subject to change without notice © Copyright Siemens
5/30/2026
|● at AC-3 rated value maximum|690 V|
|---|---|
|● at AC-3e rated value maximum|690 V|
|**operating frequency rated value**|50 ... 60 Hz|
|**operational current rated value**|0.25 A|
|**operational current**||
|● at AC-3 at 400 V rated value|0.25 A|
|● at AC-3e at 400 V rated value|0.25 A|
|**operating power**||
|● at AC-3||
|— at 230 V rated value|0 kW|
|— at 400 V rated value|0.1 kW|
|— at 500 V rated value|0.1 kW|
|— at 690 V rated value|0.1 kW|
|● at AC-3e||
|— at 230 V rated value|0 kW|
|— at 400 V rated value|0.1 kW|
|— at 500 V rated value|0.1 kW|
|— at 690 V rated value|0.1 kW|
|**operating frequency**||
|● at AC-3 maximum|15 1/h|
|● at AC-3e maximum|15 1/h|
|**Auxiliary circuit**||
|**type of voltage for auxiliary and control circuit**|AC/DC|
|**number of NC contacts for auxiliary contacts**|0|
|**number of NO contacts for auxiliary contacts**|0|
|number of CO contacts for auxiliarycontacts|0|
|**Protective and monitoring functions**||
|**product function**||
|●ground fault detection|No|
|●phase failure detection|No|
|**design of the overload release**|thermal|
|**protection function thermal overloadprotection(ANSI 49)**|Yes|
|**maximum short-circuit current breaking capacity (Icu)**||
|● at AC at 240 V rated value|100 kA|
|● at AC at 400 V rated value|100 kA|
|● at AC at 500 V rated value|100 kA|
|● at AC at 690 V rated value|100 kA|
|● at 480 AC Y/277 V accordingto UL 489 rated value|65 kA|
|**operating short-circuit current breaking capacity (Ics) at AC**||
|● at 240 V rated value|100 kA|
|● at 400 V rated value|100 kA|
|● at 500 V rated value|100 kA|
|● at 690 V rated value|100 kA|
|response value current of instantaneous short-circuit trip unit|3.3 A|
|**Short-circuit protection**||
|**product function short circuitprotection**|Yes|
|**design of the short-circuit trip**|magnetic|
|**Installation/ mounting/ dimensions**||
|**mounting position**|any|
|**fastening method**|screw and snap-on mountingonto 35 mm DIN rail accordingto DIN EN 60715|
|**Mounting method of circuit breaker for Transformer**<br>**protection, Generator protection and system protection**<br>**optional standard bar mounting**|Yes|
|**height**|144 mm|
|**width**|45 mm|
|**depth**|97 mm|
|**required spacing**||
|● forgroundedparts at 400 V||
|— downwards|30 mm|
3RV27110CD10 Page 2/5
Subject to change without notice © Copyright Siemens
5/30/2026
||— upwards|30 mm||
|---|---|---|---|
||— at the side|30 mm||
||● for liveparts at 400 V|||
||— downwards|30 mm||
||— upwards|30 mm||
||— at the side|30 mm||
||● forgroundedparts at 500 V|||
||— downwards|30 mm||
||— upwards|30 mm||
||— at the side|30 mm||
||● for liveparts at 500 V|||
||— downwards|30 mm||
||— upwards|30 mm||
||— at the side|30 mm||
||● forgroundedparts at 690 V|||
||— downwards|70 mm||
||— upwards|70 mm||
||— backwards|0 mm||
||— at the side|30 mm||
||— forwards|0 mm||
||● for liveparts at 690 V|||
||— downwards|70 mm||
||— upwards|70 mm||
||— backwards|0 mm||
||— at the side|30 mm||
||— forwards|0 mm||
||**Connections/ Terminals**|||
||**product component removable terminal for auxiliary and**<br>**control circuit**|No||
||**type of electrical connection**|||
||● for main current circuit|screw-type terminals||
||**arrangement of electrical connectors for main current**<br>**circuit**|Top and bottom||
||**type of connectable conductor cross-sections**|||
||● for main contacts|||
||— solid or stranded|1 ... 10 mm², max. 2x 10 mm²||
||— finelystranded with core endprocessing|1 ... 16 mm², max. 6 + 16 mm²||
||● for AWG cables for main contacts|2x(14 ... 10)||
||**connectable conductor cross-section for main contacts**|||
||● solid or stranded|1 ... 10 mm²||
||● finelystranded with core endprocessing|1 ... 16 mm²||
||**AWG number as coded connectable conductor cross**<br>**section for main contacts**|14 ... 10||
||**tightening torque**|||
||● for main contacts with screw-type terminals|2.5 ... 3 N·m||
||**design of screwdriver shaft**|Diameter 5 to 6 mm||
||**size of the screwdriver tip**|Pozidriv size 2||
||**design of the thread of the connection screw**|||
||● for main contacts|M4||
||**Safety related data**|||
||product function suitable for safetyfunction|Yes||
||**suitability for use**|||
||● safety-related switchingon|No||
||● safety-related switchingOFF|Yes||
||**service life maximum**|10 a||
||**test wear-related service life necessary**|Yes||
||**proportion of dangerous failures**|||
||● with low demand rate accordingto SN 31920|40 %||
||● with high demand rate accordingto SN 31920|50 %||
||**B10 value with high demand rate according to SN 31920**|5 000||
||— upwards|30 mm||
|---|---|---|---|
||— at the side|30 mm||
||● for liveparts at 400 V|||
||— downwards|30 mm||
||— upwards|30 mm||
||— at the side|30 mm||
||● forgroundedparts at 500 V|||
||— downwards|30 mm||
||— upwards|30 mm||
||— at the side|30 mm||
||● for liveparts at 500 V|||
||— downwards|30 mm||
||— upwards|30 mm||
||— at the side|30 mm||
||● forgroundedparts at 690 V|||
||— downwards|70 mm||
||— upwards|70 mm||
||— backwards|0 mm||
||— at the side|30 mm||
||— forwards|0 mm||
||● for liveparts at 690 V|||
||— downwards|70 mm||
||— upwards|70 mm||
||— backwards|0 mm||
||— at the side|30 mm||
||— forwards|0 mm||
||**Connections/ Terminals**|||
||**product component removable terminal for auxiliary and**<br>**control circuit**|No||
||**type of electrical connection**|||
||● for main current circuit|screw-type terminals||
||**arrangement of electrical connectors for main current**<br>**circuit**|Top and bottom||
||**type of connectable conductor cross-sections**|||
||● for main contacts|||
||— solid or stranded|1 ... 10 mm², max. 2x 10 mm²||
||— finelystranded with core endprocessing|1 ... 16 mm², max. 6 + 16 mm²||
||● for AWG cables for main contacts|2x(14 ... 10)||
||**connectable conductor cross-section for main contacts**|||
||● solid or stranded|1 ... 10 mm²||
||● finelystranded with core endprocessing|1 ... 16 mm²||
||**AWG number as coded connectable conductor cross**<br>**section for main contacts**|14 ... 10||
||**tightening torque**|||
||● for main contacts with screw-type terminals|2.5 ... 3 N·m||
||**design of screwdriver shaft**|Diameter 5 to 6 mm||
||**size of the screwdriver tip**|Pozidriv size 2||
||**design of the thread of the connection screw**|||
||● for main contacts|M4||
||**Safety related data**|||
||product function suitable for safetyfunction|Yes||
||**suitability for use**|||
||● safety-related switchingon|No||
||● safety-related switchingOFF|Yes||
||**service life maximum**|10 a||
||**test wear-related service life necessary**|Yes||
||**proportion of dangerous failures**|||
||● with low demand rate accordingto SN 31920|40 %||
||● with high demand rate accordingto SN 31920|50 %||
||**B10 value with high demand rate according to SN 31920**|5 000||
3RV27110CD10 Page 3/5
Subject to change without notice © Copyright Siemens
5/30/2026
**failure rate [FIT] with low demand rate according to SN** 50 FIT **31920** ISO 13849 ~~ee re~~ **device type according to ISO 13849-1** 3 **overdimensioning according to ISO 13849-2 necessary** Yes IEC 61508 **safety device type according to IEC 61508-2** Type A **T1 value** ● for proof test interval or service life according to IEC 10 a 61508 ~~ee~~ Electrical Safety **protection class IP on the front according to IEC 60529** IP20 **touch protection on the front according to IEC 60529** finger-safe, for vertical contact from the front ~~er~~ **Display** display version for switching status Handle **Approvals Certificates** ~~Se~~ Environmental Product Declaration ● global warming potential [CO2 eq] / during manufacturing 1.98 kg ● global warming potential [CO2 eq] / during sales 0.134 kg ● global warming potential [CO2 eq] / during operation 72.7 kg ● global warming potential [CO2 eq] / after end of life -0.116 kg ● global warming potential [CO2 eq] / total 74.698 kg **Environment General Product Approval** Environmental Confirmations ~~—~~ Be sex© ® {GC
**General Product Approval Test Certificates** - - Special Test Certific Type Test Certific ate ates/Test Report FAL ce ec **Maritime application other** Confirmation Miscellaneous Confirmation Miscellaneous ~~ee~~ aa “ **other Railway** - Special Test Certific ate QC PASS ~~fn e~~ **Further information** ~~e~~ **Information on the packaging** https://support.industry.siemens.com/cs/ww/en/view/109813875 **Information for data generation and storage** https://support.industry.siemens.com/cs/ww/en/view/109995012 **Information- and Downloadcenter (Catalogs, Brochures,…)** https://www.siemens.com/ic10
**Industry Mall (Online ordering system)** https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2711-0CD10 **Service&Support (Manuals, Certificates, Characteristics, FAQs,...)** https://support.industry.siemens.com/cs/ww/en/ps/3RV2711-0CD10
**Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)** https://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2711-0CD10&lang=en
3RV27110CD10 Page 4/5
Subject to change without notice © Copyright Siemens
5/30/2026
**Cax online generator** https://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2711-0CD10 **Characteristic curves** https://curves.simaris.siemens.com/curves/<mmp_prod_noCOMP="HAUPT"></mmp_prod__no>
**last modified:** 5/5/2026
3RV27110CD10 Page 5/5
Subject to change without notice © Copyright Siemens
5/30/2026
Updated at March 30, 2026
About Novapart
Novapart is a B2B electronic component broker specialising in stock shortages and cost reduction. We source hard-to-find parts and identify compliant alternatives across a catalogue of 410,000+ components from 500+ manufacturers.
Learn more →Stock Shortage Specialist
When a component is unavailable, discontinued or has an unacceptable lead time, we tap into our network of vetted European and Asian distributors to source what you need — without compromising on quality or traceability.
Request a quote →Compliant Alternatives
We identify pin-to-pin, electrically equivalent substitutes that meet the same certifications (RoHS, AEC-Q100, REACH) as your original specification — validated against datasheets, not just part numbers. Often at a lower cost.
BOM Analysis service →