Image not available
Illustrative purposes only
3RV2332-4SC10
Thermal Magnetic Circuit Breaker, SIRIUS 3RV2 Series, 14 A, 3 Pole, 690 V, DIN Rail
⚠️ Reference pricing provided. In case of supply shortages, we will connect you with our trusted procurement partners to ensure your project's continuity.
- Manufacturer: SIEMENS
- Product type: Thermal Magnetic Circuit Breakers
- No. of Poles: 3 Pole
- Product Range: SIRIUS 3RV2 Series
- Current Rating: 14A
- Voltage Rating VAC: 690V
- Voltage Rating VDC: -
- Circuit Breaker Mounting: DIN Rail
| Delivery and price | |
|---|---|
| Units per pack | 1 |
| Price | 248.22 € |
| Current stock | 10+ |
| Lead time | 30 days |
**3RV2332-4SC10**
**Data sheet**
Circuit breaker size S2 for starter combination Rated current 14 A N-release 208 A screw terminal increased switching capacity
|**product brand name**|SIRIUS|
|---|---|
|**product designation**|Circuit breaker|
|**design of theproduct**|For starter combinations|
|**product type designation**|3RV2|
|**General technical data**||
|**Product equipment of circuit breaker for motor protection**|Yes|
|**complete unit withprotection device**||
|**size of the circuit-breaker**|S2|
|**size of contactor can be combined company-specific**|S2|
|product function disconnector functionality|Yes|
|product extension auxiliaryswitch|Yes|
|**power loss[W] for rated value of the current**||
|● at AC in hot operatingstate|12.5 W|
|● at AC in hot operatingstateperpole|4.2 W|
|**type of calculation ofpower loss current-dependent**|quadratic|
|insulation voltage with degree ofpollution 3 at AC rated value|690 V|
|**surge voltage resistance rated value**|6 kV|
|**maximumpermissible voltage forprotective separation**||
|● in networks with ungrounded star point between main and|400 V|
|auxiliarycircuit||
|● in networks with grounded star point between main and|400 V|
|auxiliarycircuit||
|**protection class IP**||
|● on the front accordingto IEC 60529|IP20|
|● on the front|IP20|
|● of the terminal|IP00|
|**shock resistance according to IEC 60068-2-27**|25g/ 11 ms Sinus|
|**mechanical service life(operating cycles)**||
|● of the main contacts typical|50 000|
|● of auxiliarycontacts typical|50 000|
|electrical endurance(operatingcycles)typical|50 000|
|**reference code according to IEC 81346-2**|Q|
|**continuous current rated value**|14 A|
|**Substance Prohibitance(day/month/year)**|10/15/2014|
|**SVHC substance name**|Lead CAS-No. 7439-92-1|
|**Net Weight**|1.132 kg|
|**Ambient conditions**||
|installation altitude at height above sea level maximum|2 000 m|
|**ambient temperature**||
|● duringoperation|-20 ... +60 °C|
|● duringstorage|-50 ... +80 °C|
|● duringtransport|-50 ... +80 °C|
|relative humidityduringoperation|10 ... 95 %|
|**Main circuit**||
|**number ofpoles for main current circuit**|3|
|**type of voltage for main current circuit**|AC|
|**operating voltage**||
|● rated value|690 V|
|● rated value|20 ... 690 V|
3RV23324SC10 Page 1/5
Subject to change without notice © Copyright Siemens
5/30/2026
||● at AC-3 rated value maximum|690 V||
|---|---|---|---|
||● at AC-3e rated value maximum|690 V||
||**operating frequency rated value**|50 ... 60 Hz||
||**operational current rated value**|14 A||
||**operational current**|||
||● at AC-3 at 400 V rated value|14 A||
||● at AC-3e at 400 V rated value|14 A||
||**operating power**|||
||● at AC-3|||
||— at 230 V rated value|3 kW||
||— at 400 V rated value|5.5 kW||
||— at 500 V rated value|7.5 kW||
||— at 690 V rated value|11 kW||
||● at AC-3e|||
||— at 230 V rated value|3 kW||
||— at 400 V rated value|5.5 kW||
||— at 500 V rated value|7.5 kW||
||— at 690 V rated value|11 kW||
||**operating frequency**|||
||● at AC-3 maximum|15 1/h||
||● at AC-3e maximum|15 1/h||
||**Auxiliary circuit**|||
||**type of voltage for auxiliary and control circuit**|AC/DC||
||**number of NC contacts for auxiliary contacts**|0||
||**number of NO contacts for auxiliary contacts**|0||
||number of CO contacts for auxiliarycontacts|0||
||**Protective and monitoring functions**|||
||**product function**|||
||●ground fault detection|No||
||●phase failure detection|No||
||**trip class**|CLASS 10||
||**protection function thermal overloadprotection(ANSI 49)**|No||
||**maximum short-circuit current breaking capacity (Icu)**|||
||● at AC at 240 V rated value|100 kA||
||● at AC at 400 V rated value|100 kA||
||● at AC at 500 V rated value|18 kA||
||● at AC at 690 V rated value|8 kA||
||**operating short-circuit current breaking capacity (Ics) at AC**|||
||● at 240 V rated value|100 kA||
||● at 400 V rated value|50 kA||
||● at 500 V rated value|10 kA||
||● at 690 V rated value|5 kA||
||response value current of instantaneous short-circuit trip unit|208 A||
||**UL/CSA ratings**|||
||**full-load current(FLA) for 3-phase AC motor**|||
||● at 480 V rated value|14 A||
||● at 600 V rated value|14 A||
||**yielded mechanicalperformance[hp]**|||
||● for single-phase AC motor|||
||— at 110/120 V rated value|1.5 hp||
||— at 230 V rated value|3 hp||
||● for 3-phase AC motor|||
||— at 200/208 V rated value|5 hp||
||— at 220/230 V rated value|5 hp||
||— at 460/480 V rated value|10 hp||
||— at 575/600 V rated value|15 hp||
||**Short-circuit protection**|||
||**product function short circuitprotection**|Yes||
||**design of the short-circuit trip**|magnetic||
3RV23324SC10 Page 2/5
Subject to change without notice © Copyright Siemens
5/30/2026
||**design of the fuse link for IT network for short-circuit**<br>**protection of the main circuit**|||
|---|---|---|---|
||● at 240 V|none required||
||● at 400 V|100||
||● at 500 V|80||
||● at 690 V|63||
||**Installation/ mounting/ dimensions**|||
||**mounting position**|any||
||**fastening method**|screw and snap-on mountingonto 35 mm DIN rail accordingto DIN EN 60715||
||**Mounting method of circuit breaker for Transformer**<br>**protection, Generator protection and system protection**<br>**optional standard bar mounting**|Yes||
||**height**|140 mm||
||**width**|55 mm||
||**depth**|149 mm||
||**required spacing**|||
||● with side-by-side mounting|||
||— forwards|0 mm||
||— backwards|0 mm||
||— upwards|50 mm||
||— downwards|50 mm||
||— at the side|0 mm||
||● forgroundedparts|||
||— forwards|0 mm||
||— backwards|0 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||— downwards|50 mm||
||● for liveparts|||
||— forwards|0 mm||
||— backwards|0 mm||
||— upwards|50 mm||
||— downwards|50 mm||
||— at the side|10 mm||
||● forgroundedparts at 400 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● for liveparts at 400 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● forgroundedparts at 500 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● for liveparts at 500 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● forgroundedparts at 690 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— backwards|0 mm||
||— at the side|10 mm||
||— forwards|0 mm||
||● for liveparts at 690 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— backwards|0 mm||
3RV23324SC10 Page 3/5
Subject to change without notice © Copyright Siemens
5/30/2026
|— at the side|10 mm|10 mm|
|---|---|---|
|— forwards|0 mm||
|**Connections/ Terminals**|||
|**product component removable terminal for auxiliary and**<br>**control circuit**|No||
|**type of electrical connection**|||
|● for main current circuit|screw-type terminals||
|**arrangement of electrical connectors for main current**<br>**circuit**|Top and bottom||
|**type of connectable conductor cross-sections**|||
|● for main contacts|||
|— solid or stranded|2x(1 ... 35 mm²), 1x(1 ... 50 mm²)||
|— finelystranded with core endprocessing|2x(1 ... 25 mm²), 1x(1 ... 35 mm²)||
|● for AWG cables for main contacts|2x(18 ... 2), 1x(18 ... 1)||
|**connectable conductor cross-section for main contacts**|||
|● solid or stranded|1 ... 50 mm²||
|● finelystranded with core endprocessing|1 ... 35 mm²||
|**AWG number as coded connectable conductor cross**<br>**section for main contacts**|18 ... 1||
|**tightening torque**|||
|● for main contacts with screw-type terminals|3 ... 4.5 N·m||
|**design of screwdriver shaft**|Diameter 5 to 6 mm||
|**size of the screwdriver tip**|Pozidriv size 2||
|**design of the thread of the connection screw**|||
|● for main contacts|M6||
|**Safety related data**|||
|product function suitable for safetyfunction|Yes||
|**suitability for use**|||
|● safety-related switchingon|No||
|● safety-related switchingOFF|Yes||
|**service life maximum**|10 a||
|**test wear-related service life necessary**|Yes||
|**proportion of dangerous failures**|||
|● with low demand rate accordingto SN 31920|40 %||
|● with high demand rate accordingto SN 31920|50 %||
|**B10 value with high demand rate according to SN 31920**|5 000||
|**failure rate [FIT] with low demand rate according to SN**<br>**31920**|50 FIT||
|ISO 13849|||
|**device type according to ISO 13849-1**|3||
|**overdimensioning according to ISO 13849-2 necessary**|Yes||
|IEC 61508|||
|**safety device type according to IEC 61508-2**|Type A||
|**T1 value**|||
|● for proof test interval or service life according to IEC<br>61508|10 a||
|Electrical Safety|||
|**protection class IP on the front according to IEC 60529**|IP20||
|**touch protection on the front according to IEC 60529**|finger-safe, for vertical contact from the front||
|**Display**|||
|displayversion for switchingstatus|Handle||
|**Approvals Certificates**|||
|Environmental Product Declaration|||
|● global warming potential [CO2 eq] / during manufacturing<br>12.8 kg<br>● global warming potential [CO2 eq] / during sales<br>0.477 kg<br>● global warming potential [CO2 eq] / during operation<br>230 kg<br>● global warming potential [CO2 eq] / after end of life<br>-3.4 kg<br>● global warming potential [CO2 eq] / total<br>239.877 kg<br>**Environment**<br>**General Product Approval**|12.8 kg||
||0.477 kg||
||230 kg||
||-3.4 kg||
||239.877 kg||
|||**General Product Approval**|
3RV23324SC10 Page 4/5
Subject to change without notice © Copyright Siemens
5/30/2026
Environmental Confirmations ~~a~~ ae © {E **General Product Approval Test Certificates** - - Special Test Certific Type Test Certific ate ates/Test Report EAL c cf **Maritime application** 8 = 9 ¢ **other Railway** Confirmation ~~SO~~ Miscellaneous Confirmation Miscellaneous ~~a~~ Confirmation **Railway** - Special Test Certific ate ~~e~~ **Further information** ~~e~~ **Information on the packaging** https://support.industry.siemens.com/cs/ww/en/view/109813875 **Information for data generation and storage** https://support.industry.siemens.com/cs/ww/en/view/109995012 **Information- and Downloadcenter (Catalogs, Brochures,…)** https://www.siemens.com/ic10 **Industry Mall (Online ordering system)** https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2332-4SC10 **Service&Support (Manuals, Certificates, Characteristics, FAQs,...)** https://support.industry.siemens.com/cs/ww/en/ps/3RV2332-4SC10 **Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)** https://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2332-4SC10&lang=en **Cax online generator** https://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2332-4SC10 **Characteristic curves** https://curves.simaris.siemens.com/curves/<mmp_prod_noCOMP="HAUPT"></mmp_prod__no> ~~ane~~ **last modified:** 5/5/2026
3RV23324SC10 Page 5/5
Subject to change without notice © Copyright Siemens
5/30/2026
Updated at April 27, 2026
About Novapart
Novapart is a B2B electronic component broker specialising in stock shortages and cost reduction. We source hard-to-find parts and identify compliant alternatives across a catalogue of 410,000+ components from 500+ manufacturers.
Learn more →Stock Shortage Specialist
When a component is unavailable, discontinued or has an unacceptable lead time, we tap into our network of vetted European and Asian distributors to source what you need — without compromising on quality or traceability.
Request a quote →Compliant Alternatives
We identify pin-to-pin, electrically equivalent substitutes that meet the same certifications (RoHS, AEC-Q100, REACH) as your original specification — validated against datasheets, not just part numbers. Often at a lower cost.
BOM Analysis service →