Image not available
Illustrative purposes only
3RV2131-4KA10
Thermal Magnetic Circuit Breaker, MPCB, 3RV2, 3P, 65 kA, 400 V, 73 A
⚠️ Reference pricing provided. In case of supply shortages, we will connect you with our trusted procurement partners to ensure your project's continuity.
- Manufacturer: SIEMENS
- Product type: Thermal Magnetic Circuit Breakers
- Product Range: SIRIUS 3RV2 Series
| Delivery and price | |
|---|---|
| Units per pack | 1 |
| Price | 375.01 € |
| Current stock | 10+ |
| Lead time | 30 days |
**3RV2131-4KA10**
**Data sheet**
circuit breaker size S2 for motor protection, Class 10 with overload relay function thermal release 62...73 A short-circuit release 949 A screw terminal standard switching capacity
|Siemens~~@~~<br>EcoTech|circuit breaker size S2 for motor protection, Class 10 with overload relay function<br>thermal release 62...73 A short-circuit release 949 A screw terminal standard<br>switching capacity|
|---|---|
|**product brand name**|SIRIUS|
|**product designation**|Circuit breaker|
|**design of theproduct**|For motorprotection with overload relayfunction|
|**product type designation**|3RV2|
|**General technical data**||
|**Product equipment of circuit breaker for motor protection**<br>**complete unit withprotection device**|Yes|
|**size of the circuit-breaker**|S2|
|**size of contactor can be combined company-specific**|S2|
|product function disconnector functionality|Yes|
|product extension auxiliaryswitch|Yes|
|**power loss[W] for rated value of the current**||
|● at AC in hot operatingstate|29.5 W|
|● at AC in hot operatingstateperpole|9.8 W|
|**type of calculation ofpower loss current-dependent**|quadratic|
|insulation voltage with degree ofpollution 3 at AC rated value|690 V|
|**surge voltage resistance rated value**|6 kV|
|**maximumpermissible voltage forprotective separation**||
|● in networks with ungrounded star point between main and<br>auxiliarycircuit|400 V|
|● in networks with grounded star point between main and<br>auxiliarycircuit|400 V|
|**protection class IP**||
|● on the front accordingto IEC 60529|IP20|
|● on the front|IP20|
|● of the terminal|IP00|
|**shock resistance according to IEC 60068-2-27**|25g/ 11 ms Sinus|
|**mechanical service life(operating cycles)**||
|● of the main contacts typical|20 000|
|● of auxiliarycontacts typical|20 000|
|electrical endurance(operatingcycles)typical|20 000|
|**reference code according to IEC 81346-2**|Q|
|**continuous current rated value**|73 A|
|**Substance Prohibitance(day/month/year)**|03/01/2017|
|**SVHC substance name**|Lead CAS-No. 7439-92-1|
|**Net Weight**|1.235 kg|
|**Ambient conditions**||
|installation altitude at height above sea level maximum|2 000 m|
|**ambient temperature**||
|● duringoperation|-20 ... +60 °C|
|● duringstorage|-50 ... +80 °C|
|● duringtransport|-50 ... +80 °C|
|**temperature compensation**|-20 ... +60 °C|
|relative humidityduringoperation|10 ... 95 %|
|**Main circuit**||
|**number ofpoles for main current circuit**|3|
|**adjustable current response value current of the current-**<br>**dependent overload release**|62 ... 73 A|
|**type of voltage for main current circuit**|AC|
Subject to change without notice © Copyright Siemens
3RV21314KA10 Page 1/6
5/31/2026
|**operating voltage**||
|---|---|
|● rated value|690 V|
|● rated value|20 ... 690 V|
|● at AC-3 rated value maximum|690 V|
|**operating frequency rated value**|50 ... 60 Hz|
|**operational current rated value**|73 A|
|**operational current**||
|● at AC-3 at 400 V rated value|73 A|
|**operating power**||
|● at AC-3||
|— at 230 V rated value|22 kW|
|— at 400 V rated value|37 kW|
|— at 500 V rated value|45 kW|
|— at 690 V rated value|55 kW|
|**operating frequency**||
|● at AC-3 maximum|15 1/h|
|**Auxiliary circuit**||
|**design of the auxiliary switch**|laterally|
|**type of voltage for auxiliary and control circuit**|AC/DC|
|**number of NC contacts for auxiliary contacts**|0|
|**number of NO contacts for auxiliary contacts**|0|
|number of CO contacts for auxiliarycontacts|0|
|**Protective and monitoring functions**||
|**product function**||
|●ground fault detection|No|
|●phase failure detection|Yes|
|**trip class**|CLASS 10|
|**design of the overload release**|thermal|
|**protection function thermal overloadprotection(ANSI 49)**|Yes|
|**maximum short-circuit current breaking capacity (Icu)**||
|● at AC at 240 V rated value|65 kA|
|● at AC at 400 V rated value|65 kA|
|● at AC at 500 V rated value|8 kA|
|● at AC at 690 V rated value|4 kA|
|**operating short-circuit current breaking capacity (Ics) at AC**||
|● at 240 V rated value|65 kA|
|● at 400 V rated value|30 kA|
|● at 500 V rated value|5 kA|
|● at 690 V rated value|2 kA|
|response value current of instantaneous short-circuit trip unit|949 A|
|**UL/CSA ratings**||
|**full-load current(FLA) for 3-phase AC motor**||
|● at 480 V rated value|65 A|
|● at 600 V rated value|62 A|
|**yielded mechanicalperformance[hp]**||
|● for 3-phase AC motor||
|— at 200/208 V rated value|20 hp|
|— at 220/230 V rated value|25 hp|
|— at 460/480 V rated value|50 hp|
|— at 575/600 V rated value|60 hp|
|**Short-circuit protection**||
|**product function short circuitprotection**|Yes|
|**design of the short-circuit trip**|magnetic|
|**design of the fuse link for IT network for short-circuit**<br>**protection of the main circuit**||
|● at 240 V|none required|
|● at 400 V|160|
|● at 500 V|125|
|● at 690 V|100|
Subject to change without notice © Copyright Siemens
3RV21314KA10 Page 2/6
5/31/2026
||**Installation/ mounting/ dimensions**|**Installation/ mounting/ dimensions**||
|---|---|---|---|
||**mounting position**|any||
||**fastening method**|screw and snap-on mountingonto 35 mm DIN rail accordingto DIN EN 60715||
||**Mounting method of circuit breaker for Transformer**<br>**protection, Generator protection and system protection**<br>**optional standard bar mounting**|Yes||
||**height**|140 mm||
||**width**|75 mm||
||**depth**|149 mm||
||**required spacing**|||
||● with side-by-side mounting|||
||— forwards|0 mm||
||— backwards|0 mm||
||— upwards|50 mm||
||— downwards|50 mm||
||— at the side|0 mm||
||● forgroundedparts|||
||— forwards|0 mm||
||— backwards|0 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||— downwards|50 mm||
||● for liveparts|||
||— forwards|0 mm||
||— backwards|0 mm||
||— upwards|50 mm||
||— downwards|50 mm||
||— at the side|10 mm||
||● forgroundedparts at 400 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● for liveparts at 400 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● forgroundedparts at 500 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● for liveparts at 500 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● forgroundedparts at 690 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— backwards|0 mm||
||— at the side|10 mm||
||— forwards|0 mm||
||● for liveparts at 690 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— backwards|0 mm||
||— at the side|10 mm||
||— forwards|0 mm||
||**Connections/ Terminals**|||
||**product component removable terminal for auxiliary and**<br>**control circuit**|No||
||**type of electrical connection**|||
||**Installation/ mounting/ dimensions**|**Installation/ mounting/ dimensions**||
|---|---|---|---|
||**mounting position**|any||
||**fastening method**|screw and snap-on mountingonto 35 mm DIN rail accordingto DIN EN 60715||
||**Mounting method of circuit breaker for Transformer**<br>**protection, Generator protection and system protection**<br>**optional standard bar mounting**|Yes||
||**height**|140 mm||
||**width**|75 mm||
||**depth**|149 mm||
||**required spacing**|||
||● with side-by-side mounting|||
||— forwards|0 mm||
||— backwards|0 mm||
||— upwards|50 mm||
||— downwards|50 mm||
||— at the side|0 mm||
||● forgroundedparts|||
||— forwards|0 mm||
||— backwards|0 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||— downwards|50 mm||
||● for liveparts|||
||— forwards|0 mm||
||— backwards|0 mm||
||— upwards|50 mm||
||— downwards|50 mm||
||— at the side|10 mm||
||● forgroundedparts at 400 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● for liveparts at 400 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● forgroundedparts at 500 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● for liveparts at 500 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— at the side|10 mm||
||● forgroundedparts at 690 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— backwards|0 mm||
||— at the side|10 mm||
||— forwards|0 mm||
||● for liveparts at 690 V|||
||— downwards|50 mm||
||— upwards|50 mm||
||— backwards|0 mm||
||— at the side|10 mm||
||— forwards|0 mm||
||**Connections/ Terminals**|||
||**product component removable terminal for auxiliary and**<br>**control circuit**|No||
||**type of electrical connection**|||
Subject to change without notice © Copyright Siemens
3RV21314KA10 Page 3/6
5/31/2026
|● for main current circuit|screw-type terminals|screw-type terminals|
|---|---|---|
|● for auxiliaryand control circuit|screw-type terminals||
|**arrangement of electrical connectors for main current**<br>**circuit**|Top and bottom||
|**type of connectable conductor cross-sections**|||
|● for main contacts|||
|— solid or stranded|2x(1 ... 35 mm²), 1x(1 ... 50 mm²)||
|— finelystranded with core endprocessing|2x(1 ... 25 mm²), 1x(1 ... 35 mm²)||
|● for AWG cables for main contacts|2x(18 ... 2), 1x(18 ... 1)||
|**connectable conductor cross-section for main contacts**|||
|● solid or stranded|1 ... 50 mm²||
|● finelystranded with core endprocessing|1 ... 35 mm²||
|**AWG number as coded connectable conductor cross**<br>**section for main contacts**|18 ... 1||
|**tightening torque**|||
|● for main contacts with screw-type terminals|3 ... 4.5 N·m||
|● for auxiliarycontacts with screw-type terminals|0.8 ... 1.2 N·m||
|**design of screwdriver shaft**|Diameter 5 to 6 mm||
|**size of the screwdriver tip**|Pozidriv size 2||
|**design of the thread of the connection screw**|||
|● for main contacts|M6||
|● of the auxiliaryand control contacts|M3||
|**Safety related data**|||
|product function suitable for safetyfunction|Yes||
|**suitability for use**|||
|● safety-related switchingon|No||
|● safety-related switchingOFF|Yes||
|**service life maximum**|10 a||
|**test wear-related service life necessary**|Yes||
|**proportion of dangerous failures**|||
|● with low demand rate accordingto SN 31920|40 %||
|● with high demand rate accordingto SN 31920|50 %||
|**B10 value with high demand rate according to SN 31920**|5 000||
|**failure rate [FIT] with low demand rate according to SN**<br>**31920**|50 FIT||
|ISO 13849|||
|**device type according to ISO 13849-1**|3||
|**overdimensioning according to ISO 13849-2 necessary**|Yes||
|IEC 61508|||
|**safety device type according to IEC 61508-2**|Type A||
|**T1 value**|||
|● for proof test interval or service life according to IEC<br>61508|10 a||
|Electrical Safety|||
|**protection class IP on the front according to IEC 60529**|IP20||
|**touch protection on the front according to IEC 60529**|finger-safe, for vertical contact from the front||
|**Display**|||
|displayversion for switchingstatus|Handle||
|**Approvals Certificates**|||
|Environmental Product Declaration|||
|● global warming potential [CO2 eq] / during manufacturing<br>12.8 kg<br>● global warming potential [CO2 eq] / during sales<br>0.477 kg<br>● global warming potential [CO2 eq] / during operation<br>230 kg<br>● global warming potential [CO2 eq] / after end of life<br>-3.4 kg<br>● global warming potential [CO2 eq] / total<br>239.877 kg<br>**Environment**<br>**General Product Approval**|12.8 kg||
||0.477 kg||
||230 kg||
||-3.4 kg||
||239.877 kg||
|||**General Product Approval**|
Subject to change without notice © Copyright Siemens
3RV21314KA10 Page 4/6
5/31/2026
**==> picture [510 x 489] intentionally omitted <==**
**----- Start of picture text -----**<br>
Environmental Con-<br>firmations<br>a ae © {E<br>General Product Approval Test Certificates<br>- -<br>Special Test Certific Type Test Certific<br>ate ates/Test Report<br>EAL c cf<br>Maritime application<br>8 = 9 ¢<br>other Railway<br>Confirmation SO Miscellaneous Confirmation Miscellaneous a Confirmation<br>Railway<br>-<br>Special Test Certific<br>ate<br>e Further information e<br>Information on the packaging<br>https://support.industry.siemens.com/cs/ww/en/view/109813875<br>Information for data generation and storage<br>https://support.industry.siemens.com/cs/ww/en/view/109995012<br>Information- and Downloadcenter (Catalogs, Brochures,…)<br>https://www.siemens.com/ic10<br>**----- End of picture text -----**<br>
**Industry Mall (Online ordering system)** https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2131-4KA10 **Service&Support (Manuals, Certificates, Characteristics, FAQs,...)** https://support.industry.siemens.com/cs/ww/en/ps/3RV2131-4KA10 **Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)** https://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2131-4KA10&lang=en **Cax online generator** https://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2131-4KA10 **Characteristic curves** https://curves.simaris.siemens.com/curves/<mmp_prod_noCOMP="HAUPT"></mmp_prod__no>
Subject to change without notice © Copyright Siemens
3RV21314KA10 Page 5/6
5/31/2026
**last modified:**
5/5/2026
Subject to change without notice © Copyright Siemens
3RV21314KA10 Page 6/6
5/31/2026
Updated at April 27, 2026
About Novapart
Novapart is a B2B electronic component broker specialising in stock shortages and cost reduction. We source hard-to-find parts and identify compliant alternatives across a catalogue of 410,000+ components from 500+ manufacturers.
Learn more →Stock Shortage Specialist
When a component is unavailable, discontinued or has an unacceptable lead time, we tap into our network of vetted European and Asian distributors to source what you need — without compromising on quality or traceability.
Request a quote →Compliant Alternatives
We identify pin-to-pin, electrically equivalent substitutes that meet the same certifications (RoHS, AEC-Q100, REACH) as your original specification — validated against datasheets, not just part numbers. Often at a lower cost.
BOM Analysis service →