Image not available
Illustrative purposes only
170M3140
INDUSTRIAL AND POWER
⚠️ Reference pricing provided. In case of supply shortages, we will connect you with our trusted procurement partners to ensure your project's continuity.
- Manufacturer: EATON / PARTNER STOCK
- Product type: Industrial & Electrical Power Fuses
- SVHC: To Be Advised
| Delivery and price | |
|---|---|
| Units per pack | 3 |
| Price | 387.39 € |
| Current stock | 10+ |
| Lead time | 30 days |
## **High Speed Fuses**
## **Square body DIN 43 653 — 1250V/1300V (IEC/UL): 50-1400A**
## **1250V/1300V (IEC/UL) 50-1400A**
## **Specifications**
**Description:** Square body DIN 43 653 stud-mount high speed fuses.
**Dimensions:** See dimensions illustration.
## **Ratings:**
Volts: — 1250Vac (IEC)
— 1300Vac (UL)
Amps: — 50-1400A
IR: — 100kA RMS Sym.
**Agency Information:** CE, Designed and tested to IEC 60269: Part 4, UL Recognized. Consult Cooper Bussmann for UL Recognition/CSA Component Acceptance status.
**==> picture [243 x 198] intentionally omitted <==**
**----- Start of picture text -----**<br>
Electrical Characteristics<br>1.5<br>Total Clearing I [2] t 1.25 ee K ee ee<br>1.0<br>The total clearing I [2] t at a<br>rated voltage and at a a oe<br>power factor of 15% are 0.5 a<br>given in the electrical 0.4 rf| TT<br>characteristics. For other 0.3 Ft|<br>voltages, the clearing Iis found by multiplying by [2] t 0.2 P|<br>E<br>correction factor, K, given | ot |tT ft| yt g<br>as a function of applied 400 600 800 1000 1200 1400<br>working voltage, Eg, Dashed lines (- - - - - -) apply to the following<br>(rms). amperages:.Size Amps.<br>1* 400A<br>1 500-630A<br>2 630-1000A<br>3 800-1400A<br>**----- End of picture text -----**<br>
## **Arc Voltage**
**==> picture [239 x 244] intentionally omitted <==**
**----- Start of picture text -----**<br>
Arc Voltage 3<br>2.5 UL<br>This curve gives the peak Pepe<br>1.8 ———<br>arc voltage, UL, which may<br>appear across the fuse 1.4 ee Pt ee ee<br>during its operation as a 10 [3] | _{| _|__f}_<br>function of the applied 8 L-dtLsee| [| fT<br>working voltage, Eg, (rms) 6<br>at a power factor of 15%. 5 ae ee<br>4 ea ee e e ee ee<br>Power Losses 3 Eg<br>400 600 800 1000 1200 1400<br>Watts loss at rated current<br>Py<br>is given in the electrical 1.0<br>characteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than the 0.80.60.50.4 |eeoeP| Kp | [||Ty]|[A]]<br>rated current. The correc- 0.3 PT [TYE] ftTy<br>tion factor, Kp, is given as<br>a function of the RMS load 0.2<br>current, Ib, in % of the fiL<br>rated current. 0.1 ALLELE Ib<br>30 40 50 60 70 80 90 100%<br>**----- End of picture text -----**<br>
## **Features and Benefits**
- Excellent dc performance
- Low arc voltage and low energy let-through (I[2] t)
- Low watts loss
- Superior cycling capability
## **Typical Applications**
- DC common bus
- DC drives
- Power converters/rectifiers
- Reduced voltage starters
**==> picture [254 x 154] intentionally omitted <==**
**----- Start of picture text -----**<br>
Dimensions (mm)<br>Type -/110, -TN/110<br>Size A B D** E H 108<br>1* 80 138 58 45 20 A<br>1 80 138 66 53 25<br>2 80 138 75 61 25<br>3 81 139 90 76 30<br>a **Microswitch. i<br>1mm = 0.0394” / 1” = 25.4mm<br>H<br>*<br>ok 11 —*<br>D<br>E B<br>6<br>Sp<br>**----- End of picture text -----**<br>
E
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
**128**
## **High Speed Fuses**
## **Square body DIN 43 653 — 1250V/1300V (IEC/UL): 50-1400A**
## **Catalog Numbers**
|**Catalog Numbers**|**Catalog Numbers**|||||||
|---|---|---|---|---|---|---|---|
|<br>**Catalog Numbers**||||||||
|**-/110**<br>**Visual**<br>**Indicator**|**-TN/110**<br>**Type T**<br>**Indicator**<br>**for Micro**|**Size**||**Electrical Characteristics**||||
||||**Rated**<br>**Current**<br>**RMS-Amps**|**I2t (A2 Sec)**|||**Watts**<br>**Loss**|
|||||**Pre-arc**|**Clearing**<br>**at 1000V**|**Clearing**<br>**at 1250V**||
|170M3138<br>170M3139<br>170M3140<br>170M3141<br>170M3142<br>170M3143<br>170M3144<br>170M3145<br>170M3146<br>170M3147<br>170M3148|170M3188<br>170M3189<br>170M3190<br>170M3191<br>170M3192<br>170M3193<br>170M3194<br>170M3195<br>170M3196<br>170M3197<br>170M3198|1*|50<br>63<br>80<br>100<br>125<br>160<br>200<br>250<br>315<br>350<br>400|135<br>215<br>420<br>750<br>1450<br>2600<br>5150<br>9200<br>18500<br>27000<br>53000|815<br>1300<br>2500<br>4450<br>9000<br>16000<br>31000<br>54500<br>115000<br>165000<br>265000|1100<br>1750<br>3350<br>5950<br>11500<br>21000<br>41000<br>73000<br>150000<br>220000<br>335000|15<br>20<br>25<br>30<br>35<br>40<br>45<br>55<br>60<br>65<br>70|
|170M4138<br>170M4139<br>170M4140<br>170M4141<br>170M4142<br>170M4143<br>170M4144<br>170M4145<br>170M4146<br>170M4147|170M4188<br>170M4189<br>170M4190<br>170M4191<br>170M4192<br>170M4193<br>170M4194<br>170M4195<br>170M4196<br>170M4197|1|160<br>200<br>250<br>315<br>350<br>400<br>450<br>500<br>550<br>†630|1900<br>3800<br>7750<br>15000<br>20000<br>29500<br>42000<br>69500<br>95000<br>130000|11500<br>22500<br>46000<br>90000<br>125000<br>175000<br>250000<br>340000<br>465000<br>660000|15500<br>30000<br>61500<br>120000<br>165000<br>235000<br>335000<br>435000<br>590000|45<br>50<br>60<br>65<br>70<br>75<br>80<br>85<br>95<br>100|
|170M5138<br>170M5139<br>170M5140<br>170M5141<br>170M5142<br>170M5143<br>170M5144<br>170M5145<br>170M5146<br>170M5147<br>170M5148<br>170M5149<br>170M5150|170M5188<br>170M5189<br>170M5190<br>170M5191<br>170M5192<br>170M5193<br>170M5194<br>170M5195<br>170M5196<br>170M5197<br>170M5198<br>170M5199<br>170M5200|2|250<br>280<br>315<br>350<br>400<br>450<br>500<br>550<br>630<br>700<br>800<br>†900<br>†1000|6500<br>9350<br>13000<br>16500<br>23000<br>34000<br>48000<br>62000<br>115000<br>160000<br>245000<br>360000<br>480000|38500<br>55500<br>77500<br>97500<br>140000<br>205000<br>285000<br>370000<br>575000<br>795000<br>1200000<br>1750000<br>2350000|51500<br>74500<br>105000<br>135000<br>180000<br>270000<br>380000<br>495000<br>730000<br>1050000<br>1550000|65<br>70<br>75<br>80<br>85<br>90<br>95<br>100<br>110<br>115<br>120<br>125<br>135|
|170M6138<br>170M6139<br>170M6140<br>170M6141<br>170M6142<br>170M6143<br>170M6144<br>170M6145<br>170M6146<br>170M6147<br>170M6148<br>170M6149<br>170M6150<br>170M6151|170M6188<br>170M6189<br>170M6190<br>170M6191<br>170M6192<br>170M6193<br>170M6194<br>170M6195<br>170M6196<br>170M6197<br>170M6198<br>170M6199<br>170M6200<br>170M6201|3|315<br>350<br>400<br>450<br>500<br>550<br>630<br>700<br>‡800<br>‡900<br>‡1000<br>‡1100<br>†1250<br>†1400|9500<br>13500<br>19500<br>31000<br>39000<br>55000<br>83500<br>115000<br>205000<br>305000<br>450000<br>575000<br>810000<br>1250000|58000<br>81500<br>120000<br>185000<br>235000<br>325000<br>495000<br>705000<br>995000<br>1500000<br>2150000<br>2800000<br>3950000<br>6000000|77500<br>110000<br>160000<br>245000<br>310000<br>435000<br>665000<br>940000<br>1300000<br>1900000<br>2750000<br>3600000|85<br>90<br>95<br>100<br>105<br>110<br>115<br>120<br>125<br>130<br>135<br>140<br>145<br>150|
†Rated voltage (IEC) 1100V.
‡Rated voltage (IEC) 1250V.
- Watts loss provided at rated current.
- Microswitch indicator ordered separately. See accessories on pages 179-180.
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
**129**
## **High Speed Fuses**
## **Square body DIN 43 653 — 1250V/1300V (IEC/UL): 50-1400A**
## **Size 1* — 50-400A:1250V**
**Time-Current Curve**
## **Size 1 — 160-630A: 1250V Time-Current Curve**
## **Peak Let-Through Curve**
**==> picture [217 x 143] intentionally omitted <==**
**----- Start of picture text -----**<br>
105<br>B<br>400A<br>350A<br>315A<br>250A<br>Lo TP eee5 200A160A<br>10 [4] BEI A BBS eesiel 125A100A<br>ner erie 80A<br>63A<br>50A<br>PJ} ere er It<br>»<br> | ee ee Ih<br>103 | eet ceo TM | Tl<br>A<br>2x10 [2] VT TT TT EE<br>1x10 [2] 10 [3] 10 [4] 10 [5] 10 [6]<br>Prospective Short-Circuit Current Symmetrical RMS<br>Peak Let-Through Current<br>**----- End of picture text -----**<br>
**==> picture [242 x 535] intentionally omitted <==**
**----- Start of picture text -----**<br>
104<br>pg i<br>10 [3] SePRae AN Se tt<br>10 [2] a ON<br>BBA ee<br>SS—— PETIA A eeere ees Et e e A e ee<br>10 [1]<br>SERRA<br>ANN), NOSE<br>FEEREF<br>a<br>10 [0]<br>PAPA ESE<br>10 [–1]<br>pT<br>1 |<br>10–2 ee ee<br>10 [–3] PEK NAAN<br>PIAA<br>HSN<br>1x10 [–4] }—} 1x10 PIP 2 1 TTT 103 PNASNANI 104 RATTSST 105<br>Prospective Current In Amperes RMS<br>Peak Let-Through Curve<br>105<br>B<br>630A500A [550A]<br>400A315A [450A][350A]<br>|)es a 250A200A ae<br>10 [4] DAPEeeeeealrril 160A<br>LT AR<br>PB 12 |<br>10 [3] taeA= TIT ECT<br>A<br>2x10 [2] 1x10 ne 2 103 104 105 106<br>Prospective Short-Circuit Current Symmetrical RMS<br>630A fuse is derated to 1100V (IEC).<br>00A550A<br>160A 200A 250A 315A350A400A450A5 630A<br>Virtual Pre-Arcing Time In Seconds<br>Peak Let-Through In Amperes<br>**----- End of picture text -----**<br>
## **Data Sheet: 17056632**
**Data Sheet: 17056630**
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
**130**
## **High Speed Fuses**
## **Square body DIN 43 653 — 1250V/1300V (IEC/UL): 50-1400A**
## **Size 2 — 250-1000A: 1250V**
## **Time-Current Curve**
## **Size 3 — 315-1400A: 1250V**
## **Time-Current Curve**
**==> picture [230 x 317] intentionally omitted <==**
**----- Start of picture text -----**<br>
10 [4]<br>Sea et<br>10 [3] AVN OY G\S Oe<br>ese A) SS<br>po INVA yy SP<br>102 Pa SR<br>| | ah<br>A<br>Pe SS]<br>PTI aS A<br>10 [1] SSSSSSSSSSSstPEEa Seles = SS —— eee<br>A<br>10 [0] REELSSS Seer S St SHES ESe ONet te 6 ee eT<br>PEER<br>a<br>10–1<br>a a a<br>10 [–2]<br>EAM<br>SSS Se eee te eee<br>SEEN AS<br>THAR EEE<br>10 [–3] Po RRO RQ<br>Pr AIRONET<br>SL NNN ANON NGEEL<br>1x10–4 1x10 ee [2] 10 ee [3] SNA 10 [4] 10 [5]<br>Prospective Current In Amperes RMS<br>280A 350A 450A 550A 700A 900A<br>250A 315A 400A 500A 630A 800A 1000A<br>Virtual Pre-Arcing Time In Seconds<br>**----- End of picture text -----**<br>
## **Peak Let-Through Curve**
## **Peak Let-Through Curve**
**==> picture [521 x 176] intentionally omitted <==**
**----- Start of picture text -----**<br>
105 a 2 B 1000A800A 900A 105 FEE B a 1400A 121000A800A50A [1100A] 900A<br>eeeeeyA= ee 250A630A500400A315A — A 700A550A450A350A280A Jeea eee aa —_ 630A500A400A315A 700A550A450A350A<br>a)gs Aert = eee 4 eeoeas —_<br>104 eases 2 eel e 104 See ae ens ee a ee eet<br>EH EAH ee<br>LTen) Zee }—{ A<br>103 a aan ee| | 103 L|tT<br>ae eee eel FE|<br>PA A et th LZ A<br>2x102 1x10 YC 2 103 104 105 106 2x102 1x10 2 2 103 104 105 106<br>Prospective Short-Circuit Current Symmetrical RMS Prospective Short-Circuit Current Symmetrical RMS<br>900-1000A fuses are derated to 1100V (IEC). 1250-1400A fuses are derated to 1100V (IEC).<br>Peak Let-Through Current Peak Let-Through Current<br>**----- End of picture text -----**<br>
## **Data Sheet: 17056636**
**Data Sheet: 17056634**
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
**131**
Updated at April 17, 2026
About Novapart
Novapart is a B2B electronic component broker specialising in stock shortages and cost reduction. We source hard-to-find parts and identify compliant alternatives across a catalogue of 540,000+ components from 500+ manufacturers.
Learn more →Stock Shortage Specialist
When a component is unavailable, discontinued or has an unacceptable lead time, we tap into our network of vetted European and Asian distributors to source what you need — without compromising on quality or traceability.
Request a quote →Compliant Alternatives
We identify pin-to-pin, electrically equivalent substitutes that meet the same certifications (RoHS, AEC-Q100, REACH) as your original specification — validated against datasheets, not just part numbers. Often at a lower cost.
BOM Analysis service →