G3NA-425B-UTU-2 DC5-24 BY OMZ
Solid State Relay, SPST-NO, 25 A, 480 VAC, Panel Mount, Screw, Zero Crossing
- Manufacturer: OMRON INDUSTRIAL AUTOMATION
- Product type:
- Contact Configuration:SPST-NO; Load Current:25A; Operating Voltage Max:480VAC; Relay Mounting:Panel; Relay Terminals:Screw; Switching Mode:Zero Crossing; Operating Voltage Min:200VAC
- Load Current: 25A
- Product Range: G3NA Series
- Relay Mounting: Panel Mount
- Switching Mode: Zero Crossing
- Relay Terminals: Screw
- Control Voltage Max: 24VDC
- Control Voltage Min: 5VDC
- Contact Configuration: SPST-NO
- Operating Voltage Max: 480VAC
- Operating Voltage Min: 200VAC
| Delivery and price | |
|---|---|
| Units per pack | 10 |
| Price | 64.4 € |
| Current stock | 10+ |
| Lead time | 30 days |
## **Solid State Relay G3NA**
## **New Models with 75-A and 90-A Output Join the Previous Models with 5- to 50-A Output.**
- AC Output Relays with 75-A and 90-A output added.
- All models feature a uniform mounting pitch.
- Built-in varistor effectively absorbs external surges. (except G3NA-D210B)
- Operation indicator enables monitoring operation.
- Protective cover for greater safety.
- Standard models certified by UL and CSA and -UTU models by VDE (TÜV). (except G3NA-410B, G3NA-420B, and G3NA-440B(-2))
## **Orderin Information g**
To Order: Select the part number and add the desired rated input voltage, (e.g., G3NA-240B- _100 to 120 VAC_ )
.
|**Isolation**|**Zero cross**<br>**function**|**Indicator**|**Rated output load**<br>**(applicable output load)**|**Rated input voltage**|**Model**|
|---|---|---|---|---|---|
|Phototriac|Yes|Yes|5 A at 24 to 240 VAC*<br>(19 to 264 VAC)|5 to 24 VDC|**G3NA-205B**|
|Photocoupler||||100 to 120 VAC||
|||||200 to 240 VAC||
|Phototriac|||10 A at 24 to 240 VAC*<br>(19 to 264 VAC)|5 to 24 VDC|**G3NA-210B**|
|Photocoupler||||100 to 120 VAC||
|||||200 to 240 VAC||
|Phototriac|||20 A at 24 to 240 VAC*<br>(19 to 264 VAC)|5 to 24 VDC|**G3NA-220B**|
|Photocoupler||||100 to 120 VAC||
|||||200 to 240 VAC||
||||25 A at 24 to 240 VAC*<br>(19 to 264 VAC)|5 to 24 VDC|**G3NA-225B**|
|||||100 to 120 VAC||
|||||200 to 240 VAC||
||||25 A at 200 to 480 VAC*<br>(180 to 528 VAC)|5 to 24 VDC|**G3NA-425B**|
|||||100 to 240 VAC||
(Table continued on next page.)
Solid State Relay **G3NA** 469
**Isolation Zero cross Indicator Rated output load Rated input voltage Model function (applicable output load)** Phototriac Yes Yes 40 A at 24 to 240 VAC* 5 to 24 VDC **G3NA-240B** Photocoupler (19 to 264 VAC) 100 to 120 VAC 200 to 240 VAC Phototriac 75 A at 24 to 240 VAC* 5 to 24 VDC **G3NA-275B-UTU-2** Photocoupler (19 to 264 VAC) 100 to 240 VAC Phototriac 90 A at 24 to 240 VAC* 5 to 24 VDC **G3NA-290B-UTU-2** Photocoupler (19 to 264 VAC) 100 to 240 VAC — 10 A at 5 to 200 VDC 5 to 24 VDC **G3NA-D210B** (4 to 220 VDC) 100 to 240 VAC Yes 10 A at 200 to 480 VAC* 5 to 24 VDC **G3NA-410B** (180 to 528 VAC) 100 to 240 VAC 20 A at 200 to 480 VAC* 5 to 24 VDC **G3NA-420B** (180 to 528 VAC) 100 to 240 VAC 40 A at 200 to 480 VAC* 5 to 24 VDC **G3NA-440B-2** (180 to 528 VAC) 100 to 240 VAC 50 A at 200 to 480 VAC* 5 to 24 VDC **G3NA-450B-2** (180 to 528 VAC) 75 A at 200 to 480 VAC* 5 to 24 VDC **G3NA-475B-UTU-2** (180 to 528 VAC) 100 to 240 VAC 90 A at 200 to 480 VAC* 5 to 24 VDC **G3NA-490B-UTU-2** ~~HEi=~~ (180 to 528 VAC) 100 to 240 VAC *Loss time increases under 75 VAC. **Note: 1.** Standard models are certified by UL and CSA. **2.** When ordering a UL, CSA and TÜV-approved model, add “-UTU” to the model number as shown below: Example: G3NA-210B- _UTU._ **3.** The applicable load is the value for when the SSR is used with silicon grease applied to the specified heat sink. The applicable load depends upon the ambient temperature. Refer to _Load Current vs. Ambient Temperature_ charts in the Engineering Data section. ■ **Accessories Heat Sinks Types Applicable solid-state relays Model** Standard mount G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-220B, G3NA-410B, G3NA-420B **Y92B-A100** G3NA-225B, G3NA-240B-2, G3NA-425B, G3NA-440B-2 **Y92B-A150N** G3NA-440B-2 **Y92B-A250** Track mount G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-410B **Y92B-N50** G3NA-220B, G3NA-420B **Y92B-N100** G3NA-225B, G3NA-240B, G3NA-425B, G3NA-440B-2 **Y92B-N150** G3NA-450B-2 **Y92B-P250** G3NA-275B-UTU-2, G3NA-290B-UTU-2, G3NA-475B-UTU-2, G3NA-490B-UTU-2 **Y92B-P250NF** ~~—————s~~ **Mounting Track and Accessories Description Model** Mounting bracket for G3NA-240B and G3NA-440B-2. Changes pitch to 56 mm (2.21 in.) from 47.5 mm (1.73 in.), **R99-11** the same pitch as G3N-240B. DIN Rail Track, 50 cm (1.64 feet) length; use with Y92B-N❏❏❏ heat sinks **PFP-50N** DIN Rail Track, 1 m (3.28 feet) length; use with Y92B-N❏❏❏ heat sinks **PFP-100N** Spacer **PFP-S** End cap **PFP-M** ~~—S==—~~ One-touch mounting plate **R99-12 FOR G3NA**
Solid State Relay **G3NA**
470
**S ecifications p**
## ■ **Input Ratings**
(Ambient temperature: 25°C [77°F])
|**Type**<br>~~a~~|**Rated**<br>**voltage**<br>~~a~~<br>~~es~~|**Operating**<br>**voltage range**<br>~~a~~<br>~~es~~|**Impedance**<br>**(See note 1)**<br>~~SP~~<br>~~a~~|**Voltage level**<br>~~SP~~<br>~~a~~|**Voltage level**<br>~~SP~~<br>~~a~~|
|---|---|---|---|---|---|
|||||**Must operate voltage**<br>~~SP~~<br>~~a~~|**Must release voltage**<br>~~a~~|
|G3NA-2❏❏B<br>~~I———_—_——~~|5 to 24 VDC<br>~~es~~<br>~~Rs~~|4 to 32 VDC<br>~~es~~<br>~~nD~~|7 mA max.(see note 2)|4 VDC max.|1 VDC min.|
||100 to 120 VAC<br>~~es ~~<br>~~Rs~~|75 to 132 VAC<br> ~~es~~<br>~~nD~~|36 kΩ ±20%(see note 4)|75 VAC max.(see note 3)|20 VAC min.(see note 3)|
||200 to 240 VAC<br>~~Rs~~<br>~~I———_—_——~~|150 to 264 VAC<br>~~nD~~<br>~~es~~<br>~~I———_—_——~~|72 kΩ ±20%<br>~~I———_—_——~~|150 VAC max.(see note 3)<br>~~ee~~<br>~~I———_—_——~~|40 VAC min.(see notes 3 and 5)<br>~~ee~~<br>~~I———_—_——~~|
|G3NA-4❏❏B<br>G3NA-D210B<br>~~I———_—_——~~|5 to 24 VDC<br>~~es~~<br>~~I———_—_——~~|4 to 32 VDC<br>~~es~~<br>~~es~~<br>~~I———_—_——~~|5 mA max.(see note 2)<br>~~es~~<br>~~I———_—_——~~|4 VDC max.<br>~~ee~~<br>~~I———_—_——~~|1 VDC min.<br>~~ee~~<br>~~I———_—_——~~|
||100 to 240 VAC<br>~~I———_—_——~~|75 to 264 VAC<br>~~es~~<br>~~I———_—_——~~|72 kΩ ±20%<br>~~I———_—_——~~|75 VAC max.<br>~~ee~~<br>~~I———_—_——~~|20 VAC min.<br>~~ee~~<br>~~I———_—_——~~|
|G3NA-275B-UTU-2<br>G3NA-290B-UTU-2<br>~~I———_—_——~~<br>~~a~~<br>~~es~~|5 to 24 VDC<br>~~I———_—_——~~|4 to 32 VDC<br>~~I———_—_——~~|15 mA max.(see note 6)<br>~~I———_—_——~~|4 VDC max.<br>~~I———_—_——~~|1 VDC min.<br>~~I———_—_——~~|
|G3NA-475B-UTU-2<br>G3NA-490B-UTU-2<br>~~es~~|100 to 240 VAC|75 to 264 VAC|72 kΩ ±20%|75 VAC max.|20 VAC min.|
- **Note: 1.** The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at 100 to 120 VAC, the input impedance is measured at 120 VAC).
**2.** With constant current input circuit system, the impedance for the G3NA-2❏❏B-UTU is 15mA max.
**3.** Refer to the “Characteristic Data” for further details.
**4.** The G3NA-240B(-UTU) is 72kΩ ±20%
**5.** The G3NA-240B(-UTU) is 20 VAC min.
**6.** The impediance for G3NA-475B-UTU-2 and G3NA-490B-UTU-2 is 7 mA max.
## ■ **Output Ratings**
|**Type**<br>~~eee~~<br>~~ee ee~~|**Applicable load**<br>~~Cee~~<br>~~eee~~|**Applicable load**<br>~~Cee~~<br>~~eee~~|**Applicable load**<br>~~Cee~~<br>~~eee~~|**Applicable load**<br>~~Cee~~<br>~~eee~~|**Applicable load**<br>~~Cee~~<br>~~eee~~|**Applicable load**<br>~~Cee~~<br>~~eee~~|
|---|---|---|---|---|---|---|
||**Rated**<br>**load voltage**<br>~~eee~~<br>~~ee~~|**Load**<br>**voltage range**<br>~~eee~~<br>~~nn~~|**Load current**<br>~~Po~~<br>~~eee~~||**Surge current**<br>~~eee~~|**VDRM, VCEO**<br>**(Ref. Value)**<br>~~eee~~|
||||**With heat sink***<br>~~eee~~<br>~~nn~~|**Without heat sink**<br>~~eee~~|||
|G3NA-205B<br>~~ee ee~~<br>~~os~~|24 to 240 VAC<br>~~ee~~<br>~~os~~|19 to 264 VAC<br>~~nn~~<br>~~os~~|0.1 to 5 A (at 40°C)<br>~~nn~~<br>~~os~~|0.1 to 3 A (at 40°C)<br>~~os~~|60 A (60 Hz, 1 cycle)<br>~~os~~|600V (VDRM)<br>~~os~~|
|G3NA-210B<br>~~ee ee~~<br>~~os~~<br>~~ss~~|24 to 240 VAC<br>~~ee~~<br>~~os~~<br>~~ss~~|19 to 264 VAC<br>~~nn~~<br>~~os~~|0.1 to 10 A (at 40°C)<br>~~nn~~<br>~~os~~|0.1 to 4 A (at 40°C)<br>~~os~~|150 A (60 Hz, 1 cycle)<br>~~os~~<br>~~|~~<br>~~os~~|600V (VDRM)<br>~~os~~<br>~~|~~|
|G3NA-410B<br>~~os~~<br>~~ss~~<br>~~os~~|200 to 480 VAC<br>~~os~~<br>~~ss~~<br>~~os~~|180 to 528 VAC<br>~~os~~<br>~~os~~|0.2 to 10 A (at 40°C)<br>~~os~~<br>~~os~~|0.2 to 4 A (at 40°C)<br>~~os~~<br>~~os~~||1,200V (VDRM)<br>~~os~~<br>~~|~~<br>~~os~~|
|G3NA-220B<br>~~os~~<br>~~ss~~<br>~~os~~<br>~~ss~~|24 to 240 VAC<br>~~os~~<br>~~ss~~<br>~~os~~<br>~~ss~~|19 to 264 VAC<br>~~os~~<br>~~os~~|0.1 to 20 A (at 40°C)<br>~~os~~<br>~~os~~|0.1 to 4 A (at 40°C)<br>~~os~~<br>~~os~~|220 A (60 Hz, 1 cycle)<br>~~os~~<br>~~|~~<br>~~os~~<br>~~|~~<br>~~|~~|600V (VDRM)<br>~~os~~<br>~~|~~<br>~~os~~<br>~~|~~|
|G3NA-420B<br>~~os~~<br>~~ss~~<br>~~a~~|200 to 480 VAC<br>~~os~~<br>~~ss~~<br>~~er~~|180 to 528 VAC<br>~~os~~<br>~~nn~~|0.2 to 20 A (at 40°C)<br>~~os~~|0.2 to 4 A (at 40°C)<br>~~os~~||1,200V (VDRM)<br>~~os~~<br>~~|~~<br>~~|~~|
|G3NA-240B<br>~~os~~<br>~~ss~~<br>~~a~~<br>~~**a**~~|24 to 240 VAC<br>~~os~~<br>~~ss~~<br>~~er~~|19 to 264 VAC<br>~~os~~<br>~~nn~~<br>~~**)**~~|0.1 to 40 A (at 40°C)<br>~~os~~|0.1 to 6 A (at 40°C)<br>~~os~~|440 A (60 Hz, 1 cycle)<br>~~os~~<br>~~|~~<br>~~|~~<br>~~|~~|600V (VDRM)<br>~~os~~<br>~~|~~<br>~~|~~<br>~~||~~|
|G3NA-440B-2<br>~~a~~<br>~~**a**~~|200 to 480 VAC<br>~~er~~|180 to 528 VAC<br>~~nn~~<br>~~**)**~~|0.2 to 40 A (at 40°C)|0.2 to 6 A (at 40°C)||1,200V (VDRM)<br>~~|~~<br>~~||~~|
|G3NA-450B<br>~~**a**~~|200 to 480 VAC|180 to 528 VAC<br>~~**)**~~|0.2 to 50 A (at 40°C)|0.2 to 6 A (at 40°C)|||
|G3NA-D210B<br>~~**a**~~<br>~~Pe~~<br>~~a~~|5 to 200 VDC<br>~~Pe~~<br>~~es~~|4 to 220 VDC<br>~~**)**~~<br>~~Pe~~<br>~~ns~~|0.1 to 10 A (at 40°C)<br>~~Pe~~<br>~~(OD~~|0.1 to 4 A (at 40°C)<br>~~Pe~~<br>~~(OD~~|20 A (10 ms)<br>~~|~~<br>~~Pe~~<br>~~(OO~~|400V (VCEO)<br>~~| |~~<br>~~Pe~~|
|G3NA-275B-UTU-2 <br>~~a~~|24 to 240 VAC<br>~~es~~|19 to 264 VAC<br>~~ns~~|1 to 75 A (at 40°C)<br>~~(OD~~|1 to 7 A (at 40°C)<br>~~(OD~~|800 A (60 Hz, 1 cycle)<br>~~(OO~~|600V (VDRM)|
|G3NA-475B-UTU-2 <br>~~a~~<br>~~Pe~~<br>~~a~~|200 to 480 VAC<br>~~es~~<br>~~Pe~~<br>~~es~~|180 to 528 VAC<br>~~ns~~<br>~~Pe~~<br>~~ns~~|1 to 75 A (at 40°C)<br>~~(OD~~<br>~~Pe~~<br>~~(OD~~|1 to 7 A (at 40°C)<br>~~(OD~~<br>~~Pe~~<br>~~(OD~~|800 A (60 Hz, 1 cycle)<br>~~(OO~~<br>~~Pe~~<br>~~(OO~~|1,200V (VDRM)<br>~~Pe~~|
|G3NA-290B-UTU-2 <br>~~a~~|24 to 240 VAC<br>~~es~~|19 to 264 VAC<br>~~ns~~<br>~~Pn~~|1 to 90 A (at 40°C)<br>~~(OD~~<br>~~rr~~|1 to 7 A (at 40°C)<br>~~(OD~~<br>~~(~~|1,000 A (60 Hz, 1 cycle) <br>~~(OO~~|600V (VDRM)|
|G3NA-490B-UTU-2 <br>~~a~~<br>~~es~~|200 to 480 VAC<br>~~es~~<br>~~es~~|180 to 528 VAC<br>~~ns~~<br>~~es~~<br>~~Pn~~|1 to 90 A (at 40°C)<br>~~(OD~~<br>~~es~~<br>~~rr~~|1 to 7 A (at 40°C)<br>~~(OD~~<br>~~es~~<br>~~(~~|1,000 A (60 Hz, 1 cycle) <br>~~(OO~~<br>~~es~~|1,200V (VDRM)<br>~~es~~|
- *When the appropriate size OMRON heat sink is used.
**Note:** The load current varies depending on the ambient temperature. Refer to _Load Current vs. Ambient Temperature_ charts in the Engineering Data section.
Solid State Relay **G3NA** 471
## ■ **Characteristics**
|■**Characteristics**|■**Characteristics**|||||||||
|---|---|---|---|---|---|---|---|---|---|
|**Type**<br>~~a ~~<br>~~a~~||**G3NA-205B,**<br>**-210B, -220B,**<br>**-225B**<br> ~~ee~~|**G3NA-240B**<br>~~ee~~|**G3NA-410B,**<br>**-420B, -425B,**<br>**-440B-2, -450B-2**<br>~~ee~~|**G3NA-**<br>**D210B**<br>~~ee~~<br>~~ee~~|**G3NA-**<br>**275B-**<br>**UTU-2**<br>~~ee~~|**G3NA-**<br>**290B-**<br>**UTU-2**<br>~~ee~~<br>~~ee~~|**G3NA-**<br>**475B-**<br>**UTU-2**<br>~~ee~~<br>~~ee~~|**G3NA-**<br>**490B-**<br>**UTU-2**<br>~~ee~~<br>~~ee~~|
|Operate time<br>~~er~~|DC input<br>~~er~~<br>~~a~~|1/2 of load power source cycle + 1 ms max.<br>~~er~~|||1 ms max.<br>~~er~~<br>~~ee~~|1/2 of load power source cycle + 1 ms<br>max.<br>~~er~~<br>~~ee~~||||
||AC input<br>~~er~~<br>~~a~~|1 1/2 of load power source cycle + 1 ms max.<br>~~er~~|||30 ms max.<br>~~er~~<br>~~ee~~|3/2 of load power source cycle + 1 ms<br>max.<br>~~er~~<br>~~ee~~||||
|Release time<br>~~PP~~<br>~~a~~|DC input<br>~~a~~<br>~~PP~~|1/2 of load power source cycle + 1 ms max.<br>~~PP~~|||5 ms max.<br>~~ee~~<br>~~PP~~|1/2 of load power source cycle + 1 ms<br>max.<br>~~ee~~<br>~~PP~~||||
||AC input<br>~~PP~~<br>~~a~~<br>|1 1/2 of load power source cycle + 1 ms max.<br>~~PP~~<br>|||30 ms max.<br>~~PP~~<br>|3/2 of load power source cycle + 1 ms<br>max.<br>~~PP~~<br>||||
|Output ON voltage drop<br>~~a~~<br>~~a~~||1.6 V (RMS)<br>max.<br>|1.6 V (RMS)<br>max.<br>|1.8 V (RMS max.) <br>|1.5 V max.<br>|1.6 V (RMS) max.<br>||1.8 V (RMS) max.<br>||
|Leakage current<br>~~a~~<br>~~a~~||5 mA max. at 100 VAC<br>10 mA max. at 200 VAC<br>||10 mA max.<br>at 200 VAC<br>20 mA max.<br>at 400 VAC<br>|5 mA max.<br>at 200 VDC<br>|5 mA max.<br>at 100 VAC<br>10 mA max.<br>at 200 VAC<br>||10 mA max.<br>at 200 VDC<br>20 mA max.<br>at 400 VAC<br>||
|Insulation resistance<br>~~pt~~<br>~~a~~||100 MΩmin at 500 VDC<br>~~pt~~<br>||||||||
|Dielectric strength<br>~~pt~~<br>~~a~~||2,500 VAC, 50/60 Hz for 1 minute<br>~~pt~~<br>||||4,000 VAC, 50/60 Hz for 1 min.<br>~~pt~~<br>||||
|Vibration<br>~~a~~|Malfunction<br>|10 to 55 Hz, 1.5 mm double amplitude<br>||||||||
|Shock<br>~~apO~~<br>~~ee~~|Malfunction<br>~~pO~~<br>~~ee~~|1,000 m/s2(approx. 100G)<br>~~pO~~<br>~~eee~~||||||||
|Ambient temperature<br>~~pO~~<br>~~ee~~|Operating<br>~~pO~~<br>~~ee~~|-30°to 80°C with no icingor condensation<br>~~pO~~<br>~~eee~~||||||||
||Storage<br>~~ee~~|-30°to 100°C with no icingor condensation<br>~~eee~~||||||||
|Ambient operatinghumidity<br>~~ee~~||45% to 85% RH<br>~~eee~~||||||||
|Weight<br>~~pT~~||Approx. 60g<br>~~pT~~|Approx. 70g<br>~~pT~~|Approx. 80g<br>~~pT~~|Approx. 70g <br>~~pT~~|Approx. 120g<br>~~pT~~||||
**Note:** Data shown are of initial value.
Solid State Relay **G3NA**
472
**En ineerin Data g g**
## **Load Current vs. Ambient Temperature**
**==> picture [482 x 514] intentionally omitted <==**
**----- Start of picture text -----**<br>
G3NA-205B G3NA-210B/410B G3NA-220B/420B<br>(LET 20<br>16<br>With standard heat sink 10<br>(Y92B-A100 or Y92B- With standard heat sink With standard heat sink<br>jo N50) or aluminum plate PETE (Y92B-A100 or Y92B- TT] JET (Y92B-A100 or Y92B- py<br>measuring 75 mm x N50) or aluminum plate N100) or aluminum plate<br>75 mm x t3.2 mm 8 measuring 150 mm x measuring 200 mm x<br>(W x H x t) 150 mm x t3.2 mm 200 mm x t3.2 mm<br>Without heat sink 6 (W x H x t) (W x H x t)<br>L W 5 P With iron plate measuring N PON With iron plate measuring E<br>4 100 x 100 x t0.8 (W x H x t) 100 x 100 x t0.8 (W x H x t)<br>Without heat sink<br>l o eee w fo<br>fee) 2 CO S<br>| GE Without heat sink E<br>0<br>Ambient temperature (°C) Ambient temperature (°C) Ambient temperature (°C)<br>G3NA-240B G3NA-440B G3NA-450B-2<br>50 50 60<br>45 45 With Y92B-A250<br>or heat sink with a<br>40 40 radiation efficiency of 1°C/W. 50 With standard heat sink<br>With standard heat (Y92B-P250)<br>sink (Y92B-A150N or 40<br>30 momen Y92B-N150) 30 aTh) With standard heat FoorTOOT<br>sink (Y92B-A150N<br>or Y92B-N150) 30<br>20 TH 20 i TOCA<br>20<br>With iron plate measuring With iron plate measuring<br>12106 PN 100 x 100 x t0.8 (W x H x t)Without heat sink N C 12106 (EN 100 x 100 x t0.8 (W x H x t)Without heat sink Ne 106 PoE Ge Without heat sink INs<br>−04230 fe −20 0 20 sse 40 60 80 100 | −04230 ESSE −20 0 20 40 60 80 100 | −030−20 oo 0 20 40 60 EL 80 100<br>°<br>° ° Ambient temperature ( C)<br>Ambient temperature ( C) Ambient temperature ( C)<br>G3NA-275B-UTU-2 G3NA-290B-UTU-2<br>G3NA-475B-UTU-2 G3NA-490B-UTU-2 G3NA-D210B<br>80 100 20<br>75<br>70 0.6°C/W with 90<br>Heat Sink 0.3°C/W with<br>80 Heat Sink 10<br>60<br>Foe Nee } 70 PORE, IE With standard heat sink<br>(Y92B-A100 or Y92B-N50)<br>50 FARR 60 EAE or aluminum plate measuring Noa<br>150 mm x 150 mm x t3.2 mm<br>40 Using the Y92B-P250NF 50 Using the Y92B-P250NF 6 (W x H x t)<br>30 oy a ie 4035 E | N \— 54 With iron plate measuring 100 x 100 x t0.8 (W x H x t) S-<br>30 Without heat sink<br>20 With iron plate measuring<br>100 x 100 x t0.8 (W x H x t) 20 With iron plate measuring<br>12 100 x 100 x t0.8 (W x H x t) 2<br>10 PEN , 12 FEEEE N Y fo oos<br>2−7030 cS −20Without heat sink0 20 40 60 70 804A100 2−7030 eat −20 Without heat sink 0 20 40 60 70 804A100 | ] −030 [ET −20 0 20 40 60 80 100<br>Ambient temperature (°C) Ambient temperature (°C) Ambient temperature (°C)<br>Load current (A) Load current (A) Load current (A)<br>Load current (A) Load current (A) Load current (A)<br>Load current (A) Load current (A) Load current (A)<br>**----- End of picture text -----**<br>
**Note:** The ambient operating temperature of the Y92B-P250NF is −30 to 70°C. Be sure the operating temperature is within this range.
Solid State Relay **G3NA** 473
## **One Cycle Surge Current**
**==> picture [505 x 525] intentionally omitted <==**
**----- Start of picture text -----**<br>
The values shown by the solid line are for non-repetitive inrush currents.<br>Keep the inrush current below the values shown by the dotted line if it occurs repetitively.<br>G3NA-210B G3NA-220B G3NA-240B<br>G3NA-205B G3NA-410B G3NA-420B G3NA-440B-2/-450B-2<br>60 UTI 150<br>T TLL 200 400<br>To eS 150 oo 300<br>40 PINT 100<br>TT Ey LENE<br>SUNT TT 100 \ Lo 200 \<br>20 LIAN 50 CIN LNT LENE<br>TT E E PETE ENTE 50 PPS 100 NIA<br>010 PTLDCrore) 30 50 100 200 500 1,000 5,000 EP 010 LLLPCOT 30 50 100 200 EEL 500 1,000 7 5,000 010 EE) 30 50 100 200 500 1,000 5,000 010 LL 30 50 PepeTha 100 200 500 1,000 5,000<br>Energized time (ms) Energized time (ms) Energized time (ms) Energized time (ms)<br>G3NA-275B-UTU-2 G3NA-290B-UTU-2<br>G3NA-D210B G3NA-475B-UTU-2 G3NA-490B-UTU-2<br>30 900 1,200<br>28<br>26 SSS 800 ooo ooo<br>24 700 1,000<br>22<br>20 600 800<br>18<br>16 500<br>600<br>14 400<br>12<br>10 300 400<br>8<br>64 PHSee 200100 CASESIl 200 [SUROtt<br>2<br>010 a 20 30 50 70 100 200 300 500 1,000 2,000 010 ee 30 | 50 || 100 300 1,000 010 30 50 100 300 1,000<br>Energized time (ms) Energized time (ms) Energized time (ms)<br>Temperature<br>Characteristics (for<br>Must Operate Voltage<br>and Must Release Heat Sink Area vs.<br>Voltage) Load Current<br>G3NA-2 ❏❏ B AC input G3NA-220B<br>40 ee es es ee ee | 3,000 a<br>2,000 Ambient Ambient<br>temperature 80°C temperature 40°C<br>1,000<br>20 700<br>500 Note: The heat sink area refers to the combined area<br>0 300200 of the sides of the heat sink that radiate heat.<br>Aluminum plate For example, when a current of 18 A is allowed<br>−20 1007050 3.2 mm thick to flow through the SSR at 40shows that the heat sink area is about 450 cm°C, the graph [2] .<br>30 Therefore, if the heat sink is square, one side of<br>−40−30 Py——— −20 TN 0 Ambient temperature (20 40 60 80 °100C) 200 FRRRBEEREEEESseen 2 4 6 8 10 12 14 16 18 20 22 24 the heat sink must be 15 cm ( ) or longer. : 450 (cm [2] )/2<br>Load current (A)<br>Inrush current (A peak) Inrush current (A peak) Inrush current (A peak) Inrush current (A peak)<br>Inrush current (A peak) Inrush current (A peak) Inrush current (A peak)<br>Variation rate (%) Heat sink area (cm2)<br>**----- End of picture text -----**<br>
## **Thermal Resistance Rth (Back of Junction SSR) (Examples)**
|**Model**|**Rth (**°**C/W)**|
|---|---|
|G3NA-205B|3.22|
|G3NA-210B|2.62|
|G3NA-220B|1.99|
|G3NA-240B-2|0.45|
|G3NA-275B-UTU-2<br>G3NA-475B-UTU-2<br>G3NA-290B-UTU-2<br>G3NA-490B-UTU-2|0.45|
|G3NA-D210B|2.62|
## **Thermal Resistance Rth of Heat Sinks (Examples)**
|**(Examples)**||
|---|---|
|**Model**|**Rth (**°**C/W)**|
|Y92B-N50|2.8|
|Y92B-N100|1.63|
|Y92B-N150|1.38|
|Y92B-A100|1.63|
|Y92B-A150N|1.37|
|Y92B-A250|1.00|
|Y92B-P250NF|0.46|
**Note:** When using a commercially available heat sink, use one with a thermal resistance equal to or less that the OMRON Heat Sink.
Solid State Relay **G3NA**
474
## **Dimensions**
## ■ **Relays**
## **Note:** All units are in millimeters unless otherwise indicated.
## **G3NA-205B, G3NA-210B, G3NA-220B, G3NA-410B, G3NA-420B**
**==> picture [486 x 267] intentionally omitted <==**
**----- Start of picture text -----**<br>
11.9 Four, M4 x 8<br>4.5 dia. screws Mounting Holes<br>Terminal Arrangement/<br>a va Internal Connections<br>Two, 4.3-dia. (Top View)<br>or M4 holes<br>ACR pe [| Load Load<br>58 max. 47.5 44 power<br>supply<br>Output<br>> ne t* fens 1 2<br>47.6±0.2<br>−<br>ad cae Operating 15.8 *18.9 | | (4 ) (+)3<br>4.5 indicator 25 max. *28 max. Input<br>25<br>27 max. *30 max.<br>43 max.<br>*Size for G3NA-410B and G3NA-420B.<br>G3NA-240B, G3NA-440B-2 11.9<br>4.5 dia. Two, M5 x 12 screws Mounting Holes Terminal Arrangement/<br>Internal Connections<br>(Top View)<br>Two, 4.3-dia.<br>or M4 holes Load<br>Load<br>58 min.47.5 44 power<br><SS ee, > =( ] , my Lf | i supply<br>Output<br>1 2<br>47.6±0.2<br>Operating −<br>indicator ( ) (+)<br>15.8 *18.9 4 3<br>4.5 25 max. *28 max. Input<br>25 Two,<br>Ee 43 max. M 4 x 8 27 max. *30 max. Le ae<br>*Size for G3NA-240B and G3NA-440B-2<br>**----- End of picture text -----**<br>
## **G3NA-D210B**
**Note:** The load can be connected to either the positive or negative side.
**==> picture [388 x 138] intentionally omitted <==**
**----- Start of picture text -----**<br>
11.9 4.5 dia. Four, M4 x 8 screws Mounting Holes Terminal Arrangement/<br>Internal Connections<br>- (Top View)<br>Two, 4.3-dia.<br>or M4 holes Load<br>Load<br>power<br>58 max. 47.5 44 supply<br>TT 4 {= Output<br>1 2<br>47.6±0.2 − +<br>−<br>( ) (+)<br>Operating 15.8 4 3<br>4.5 indicator 25 max. Input<br>25 27 max.<br>43 max. Note: When connecting the load, either the<br>positive or negative side of the load<br>terminals can be connected.<br>**----- End of picture text -----**<br>
## **G3NA-275B-UTU-2, G3NA-475B-UTU-2, G3NA-290B-UTU-2, G3NA-490B-UTU-2**
**==> picture [379 x 131] intentionally omitted <==**
**----- Start of picture text -----**<br>
4.5 dia.<br>12 Two, M5 x 12<br>screws<br>L Mounting Holes Terminal Arrangement/<br>Internal Connections<br>Two, 4.3-dia. (Top View)<br>or M4 holes<br>Load<br>58 max.47.5 | 44 ae<br>|||<br>Output<br>| Ela 47.6 [±][0.2] , 1 2 Load ®<br>CSS Operating | | power<br>4.5 indicator 16.8 *18.9 supply<br>8.2 Two, M4 x 2 6 max . *28 max. (4−) (+)3<br>fm= 4 3 max.25 8 screws P— 2 8 max . > a *30 max.*Size for G3NA- u @@@B-UTU-2. i={ i Lo _ Input y=<br>**----- End of picture text -----**<br>
Solid State Relay **G3NA** 475
## ■ **Options (Order Separately)**
## **One-touch Mounting Plate**
The One-touch Mounting Plate is used to mount the GN3A to a DIN Track.
To mount the Relay to DIN Track, first mount it to the One-touch Mounting Plate and then attach it to the DIN Track as shown in the diagram.
## **R99-12 FOR G3NA (for the G3NA and G3NE)**
**==> picture [124 x 95] intentionally omitted <==**
**----- Start of picture text -----**<br>
Two, M4 mounting<br>holes for the G3NA<br>Ey<br>Two, M4 mounting 30<br>holes for the G3NE 44<br>**----- End of picture text -----**<br>
To remove the Relay from the DIN Track, pull down on the tab with a screwdriver in the direction of the arrow.
- When a Relay is mounted to DIN Track, use it within the rating for a Relay without a heat sink.
- Use the following DIN Tracks: PFP-100N or PFP-100N2.
## **Mounting Bracket**
## **R99-11 (for the G3NA-240B, G3NA-440B)**
Use Mounting Bracket R99-11 so that the G3NA-240B/-440B can be mounted with the same pitch as that of the G3N-240B.
**==> picture [120 x 69] intentionally omitted <==**
**----- Start of picture text -----**<br>
16<br>8<br>5<br>12.5<br>21<br>—<br>4 ‘ 4.6<br>**----- End of picture text -----**<br>
**==> picture [9 x 6] intentionally omitted <==**
**----- Start of picture text -----**<br>
56<br>**----- End of picture text -----**<br>
## **Heat Sinks**
## **Y92B-N50 Heat Sink (for the G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-410B, G3NE-210T(L))**
For surface mounting, a 30% derating of the load current is required (from the _Load Current vs. Ambient Temperature_ graphs). The orientation indicated by the external dimensions is not the correct mounting orientation. When opening mounting holes, refer to the mounting hole dimensions.
**==> picture [353 x 127] intentionally omitted <==**
**----- Start of picture text -----**<br>
Mounting Holes<br>4.6 dia. Two, M3 holes Two, 3.2-dia. holes Two, 4.4-dia. or M4 holes<br>Two, M4 holes<br>35 30.5±0.3 44 max. 30 47 max.<br>47.6 5.6 5 6 4.5 90±0.4<br>il mii i<br>77 max.<br>51 max.<br>90±0.3<br>100 max.<br>35±0.2<br>Weight: approx. 200 g<br>**----- End of picture text -----**<br>
Solid State Relay **G3NA**
476
## **Y92B-N100 Heat Sink (for the G3NA-220B, G3NA-420B, G3NE-220T(L))**
For surface mounting, a 30% derating of the load current is required (from the _Load Current vs. Ambient Temperature_ graphs). The orientation indicated by the external dimensions is not the correct mounting orientation. When opening mounting holes, refer to the mounting hole dimensions.
**==> picture [376 x 301] intentionally omitted <==**
**----- Start of picture text -----**<br>
Mounting Holes<br>Two, M3 holes Two, M4 Two, 3.2-dia. holes<br>4.6 dia. holes Two, 4.4-dia.<br>or M4 holes<br>35 30.5±0.3 71 max. 30 75 max.<br>es ST 90±0.4<br>47.6 5.6 28 5 13 4.5<br>77 max. 100 max.<br>90±0.3<br>100 max.<br>35±0.2<br>Weight: approx. 400 g<br>Load Current vs. Ambient Temperature graphs).<br>47.6 Two, 3.2-dia. holes Mounting Holes<br>Three, Two, 4.4-dia.<br>4.6 dia. M4 holes or M4 holes<br>35 100 max. 30 104 max.<br>He 56±0.3 5.6 28 5 4.5<br>13<br>77 max. 100 max.<br>90±0.3<br>Weight: approx. 560 g<br>100 max.<br>**----- End of picture text -----**<br>
## **Y92B-N150 Heat Sink (for the G3NA-240B, G3NA-440B-2)**
For surface mounting, a 30% derating of the load current is required (from the _Load Current vs. Ambient Temperature_ graphs). The orientation indicated by the external dimensions is not the correct mounting orientation. When opening mounting holes, refer to the mounting hole dimensions.
## **Y92B-P250NF Heat Sink (for the G3NA-275B-UTU-2, G3NA-475B-UTU-2, G3NA-290B-UTU-2, G3NA-490B-UTU-2)**
The orientation indicated by the external dimensions is not the correct mounting orientation. When opening mounting holes, refer to the mounting hole dimensions.
Observe the precautions given in Mounting Method under _Precautions for Correct Use_ .
**==> picture [393 x 141] intentionally omitted <==**
**----- Start of picture text -----**<br>
Mounting Holes<br>Fan power supply, 200 VAC 50/60 Hz<br>1 72 max. 133.4 64 [±][0.3]<br>_—_ 160 max. 1 20 max. = ft<br>120 105<br>———~ ale i<br>M4 130 [±][0.3]<br>80 max. 64 110max.<br>Two, 4.6-dia. holes<br>47.6 Two, M4 holes ThermostatNC contact, 90°C Weight: approx. 2.5 kg Two, 4.5-dia. or M4 holes<br>**----- End of picture text -----**<br>
Solid State Relay **G3NA** 477
**==> picture [488 x 451] intentionally omitted <==**
**----- Start of picture text -----**<br>
Y92B-P250 t<br>ll<br>Two, M4 Depth 10 Four, M4 Mounting Holes<br>Four, 4.5 dia. or M4<br>il<br>fo 47.6 n 190.5 max.<br>ey TO<br>Four, R2.5<br>130.5 max.<br>-<br>70 max.<br>vn<br>Y92B-A100 Heat Sink<br>(for the G3NA-205B,<br>G3NA-210B,<br>G3NA-220B, Y92B-A150N Heat Sink<br>G3NA-410B, (for the G3NA-240B, Y92B-A250 Heat Sink<br>G3NA-420B, G3NA-440B-2) (for the G3NA-440B-2)<br>G3NA-D210B) Three, M4 holes Three, M4 holes<br>Two, M4 holes<br>102 max.<br>80.5 max.<br>R2.2 47.6 R2.2 47.6 1.5<br>9.6<br>47.6 50±0.1 PS 50±0.1 E 1.52<br>50±0.1 56±0.5 56±0.5 45.5 max.30<br>ES 100 max. [TS] 150 max. Bae 250 max.<br>Weight: approx. 210 g Weight: approx. 310 g Weight: approx. 510 g<br>0.1 0.1± 0.1±<br>± 90 90<br>90<br>**----- End of picture text -----**<br>
**Mounting Holes Y92B-A100 Y92B-A150 Y92B-A250** Four, 4.3-dia. or M4 holes
For surface mounting, a 30% derating of the load current is required (from the _Load Current vs. Ambient Temperature_ graphs). The orientation indicated by the external dimensions is not the correct mounting orientation. When opening mounting holes, refer to the mounting hole dimensions.
Solid State Relay **G3NA**
478
## ■ **Approvals**
**UL Recognized (File No. E64562) / CSA Certified (File No. LR35535) - - Ambient Temp. = 40** ° **C**
|~~po~~|||~~eee~~|~~eee~~|
|---|---|---|---|---|
|**SSR type**<br>~~a ee~~<br>~~po~~<br>~~pe~~|**Input voltage**<br>~~ee~~<br>~~——~~|**Load type**<br>~~ee~~<br>~~——~~|**Contact ratings**<br>~~ee~~<br>~~eee~~||
||||**Without heat sink**<br>~~ee~~|**With heat sink (see note 1)**<br>~~ee~~<br>~~eee~~|
|G3NA-205B<br>~~po~~<br>~~pe~~<br>~~pe~~|5 to 24 VDC<br>100 to 120 VAC<br>200 to 240 VAC<br>~~——~~<br>~~——~~<br>~~——~~<br>~~——~~<br>~~——~~<br>~~——~~|General use/Tungsten<br>~~——~~|3 A, 240 VAC|5 A, 240 VAC<br>~~eee~~|
|||Motor<br>~~——~~<br>~~——~~|2.5 FLA, 15 LRA, 240 VAC|2.5 FLA, 15 LRA, 240 VAC<br>~~eee~~|
|G3NA-210B<br>~~po~~<br>~~pe~~<br>~~pe~~<br>~~pe~~||General use/Tungsten<br>~~——~~<br>~~——~~|4 A, 240 VAC|10 A, 240 VAC<br>~~eee~~|
|||Motor<br>~~——~~<br>~~——~~<br>~~——~~|2.5 FLA, 15 LRA, 240 VAC|5 FLA, 30 LRA, 240 VAC|
|G3NA-220B<br>~~pe~~<br>~~pe~~<br>~~pe~~<br>~~pe~~||General use/Tungsten<br>~~——~~<br>~~——~~<br>~~——~~|4 A, 240 VAC|20 A, 240 VAC|
|||Motor<br>~~——~~<br>~~——~~<br>~~——~~|2.5 FLA, 15 LRA, 240 VAC|10 FLA, 60 LRA, 240 VAC|
|G3NA-225B<br>~~pe~~<br>~~pe~~<br>~~pe~~<br>~~pe~~||General use/Tungsten<br>~~——~~<br>~~——~~<br>~~——~~|4 A, 240 VAC|25 A, 240 VAC|
|||Motor<br>~~——~~<br>~~——~~<br>~~——~~|2.5 FLA, 15 LRA, 240 VAC|12 FLA, 72 LRA, 240 VAC|
|G3NA-240B<br>~~pe~~<br>~~pe~~<br>~~pe~~<br>~~pe~~||General use/Tungsten<br>~~——~~<br>~~——~~<br>~~——~~|6 A, 240 VAC|40 A, 240 VAC|
|||Motor<br>~~——~~<br>~~——~~<br>~~——~~|5 FLA, 30 LRA, 240 VAC|20 FLA, 120 LRA, 240 VAC|
|G3NA-410B<br>~~pe~~<br>~~pe~~<br>~~pe~~<br>~~pe~~|5 to 24 VDC<br>100 to 240 VAC<br>~~——~~<br>~~——~~<br>~~——~~<br>~~——~~<br>~~——~~<br>~~——~~<br>~~——~~|General use/Tungsten<br>~~——~~<br>~~——~~<br>~~——~~|4 A, 480 VAC|10 A, 480 VAC|
|||Motor<br>~~——~~<br>~~——~~<br>~~——~~|2.5 FLA, 15 LRA, 480 VAC|5 FLA, 30 LRA, 480 VAC|
|G3NA-420B<br>~~pe~~<br>~~pe~~<br>~~pe~~<br>~~pe~~||General use/Tungsten<br>~~——~~<br>~~——~~<br>~~——~~|4 A, 480 VAC|20 A, 480 VAC|
|||Motor<br>~~——~~<br>~~——~~<br>~~——~~|2.5 FLA, 15 LRA, 480 VAC|10 FLA, 60 LRA, 480 VAC|
|G3NA-425B<br>~~pe~~<br>~~pe~~<br>~~pe~~<br>~~pe~~||General use/Tungsten<br>~~——~~<br>~~——~~<br>~~——~~|4 A, 480 VAC|25 A, 480 VAC|
|||Motor<br>~~——~~<br>~~——~~<br>~~——~~|2.5 FLA, 15 LRA, 480 VAC|12 FLA, 72 LRA, 480 VAC|
|G3NA-440B<br>~~pe~~<br>~~pe~~<br>~~pe~~<br>~~po~~||General use/Tungsten<br>~~——~~<br>~~——~~<br>~~——~~|6 A, 480 VAC|40 A, 480 VAC|
|||Motor<br>~~——~~<br>~~——~~<br>~~——~~|5 FLA, 30 LRA, 480 VAC|20 FLA, 120 LRA, 480 VAC|
|G3NA-450B<br>~~pe~~<br>~~pe~~<br>~~po~~||General use/Tungsten<br>~~——~~<br>~~——~~<br>~~——~~|6 A, 480 VAC|50 A, 480 VAC|
|||Motor<br>~~——~~<br>~~——~~|5 FLA, 30 LRA, 480 VAC|24 FLA, 144 LRA, 480 VAC|
|G3NA-D210B<br>~~pe~~<br>~~po~~||General use<br>~~——~~<br>~~——~~<br>~~a~~|4 A, 200 VDC|10 A, 200 VDC|
## **Note: 1.** When used with the proper OMRON heat sink part number or an appropriately dimensioned equivalent.
**2.** The rated values approved by each of the safety standards (e.g., UL, CSA, and TÜV) may be different from the performance characteristics individually defined in this catalog.
**3.** In the interest of product improvement, specifications are subject to change.
Solid State Relay **G3NA** 479
## **Safet Precautions y**
! **Caution** Touching the charged section may occasionally cause minor electric shock. Do not touch the G3NA terminal section (the charged section) when the power supply is ON. Be sure to attach the cover before use. ~~SS~~
**3.** Wire the G3NA and tighten screws correctly, observing the following precautions
- Heat generated by a terminal error may occasionally result in fire damage. Do not operate if the screws on the output terminal are loose.
- Abnormal heat generated by wires may occasionally result in fire damage. Use wires suitable for the load current.
! **Caution** The G3NA and heat sink will be hot and may occasionally cause minor burns. Do not touch the G3NA or the heat sink either while the power supply is ON, or immediately ~~A~~ after the power is turned OFF. ~~;~~ ! **Caution**
- Abnormal heat generated by terminals may occasionally result in fire damage. Do not operate if the screws on the output terminal are loose.
## **Tightening Torque**
~~;~~ The internal snubber circuit is charged and may occasionally cause minor electric shock. Do not touch the G3NA’s main circuit terminals immediately after the power is turned OFF. ~~—~~
**==> picture [261 x 70] intentionally omitted <==**
**----- Start of picture text -----**<br>
|||
|---|---|
|Screw size|Tightening torque|
|M4|1.2 N•m|
|M5|2.0 N•m|
|———————|
|•|Abnormal heat generated by terminals may occasionally result|
|in fire damage. When tightening terminal screws, be sure that|
|no non-conductive foreign matter is caught in screw.|
**----- End of picture text -----**<br>
! **Caution** Be sure to conduct wiring with the power supply turned OFF, and always attach the terminal cover after completing wiring. Touching the terminals when they are charged ~~A~~ may occasionally result in minor electric shock.
- For GN3A Relays of 40 A or higher, use crimp terminals of an appropriate size for the wire diameter for M5 terminals.
- Do not use any wires with damaged sheaths. These may cause electric shock or leakage.
## ! **Caution**
~~_~~
Do not apply a short-circuit to the load side of the G3NA. The G3NA may rupture. To protect against short-circuit accidents, install a protective device, such as a quickburning fuse, on the power supply line.
- Do not place wiring in the same conduit or duct as high-voltage lines. Induction may cause malfunction or damage.
- Use wires of an appropriate length, otherwise malfunction and damage may result due to induction.
## ■ **Precautions for Safe Use**
- Mount the DIN Track securely. Otherwise, the DIN Track may fall.
Although OMRON continuously strives to improve the quality and reliability of our relays, the G3NA contains semiconductors, which are generally prone to occasional malfunction and failure.
- Be sure that the G3NA clicks into place when mounting it to DIN Track. The G3NA may fall if it is not mounted correctly.
- Do not mount the G3NA when your hands are oily or dirty, e.g., with metal powder. These may cause G3NA failure.
Maintaining safety is particularly difficult if a relay is used outside of its ratings. Always use the G3NA within the rated values. When using the G3NA, always design the system to ensure safety and prevent human accidents, fires, and social damage even in the event of G3NA failure, including system redundancy, measures to prevent fires from spreading, and designs to prevent malfunction.
- Tighten the G3NA screws securely. Tightening torque: 0.78 to 0.98 N•m
- Tighten the heat sink screws securely. Tightening torque: 0.98 to 1.47 N•m
**4.** Preventing Overheating
**1.** G3NA malfunction or fire damage may occasionally occur. Do not apply excessive voltage or current to the G3NA terminals.
When using the High-capacity Heat Sink (Y92B-P250NF), always use a thermostat or other method to protect from overheating in the event that the fan stops.
**2.** Heat Dissipation
- Do not obstruct the airflow to the G3NA or heat sink. Doing so may cause the output element to short, or cause fire damage.
**5.** Do Not Touch Fan Blades
When the fan is operating, do not touch the fan blades with any part of your body or allow foreign matter to come into contact with the blades. Always attach the enclosed finger guard when using the G3NA.
- Be sure to prevent the ambient temperature from rising due to the heat radiation of the G3NA. If the G3NA is mounted inside a panel, install a fan so that the interior of the panel is fully ventilated.
**6.** Operating Conditions
- Mount the G3NA in the specified orientation. If the G3NA is mounted in any other orientation, abnormal heat generation may cause output elements to short or may cause burning.
- Only use the G3NA with loads that are within the rated values. Using the G3NA with loads outside the rated values may result in malfunction, damage, or burning.
- Do not use the G3NA if the heat sink fins are bent, e.g., as the result of dropping the G3NA. Heat dissipation characteristics will be reduced, possibly causing G3NA failure.
- Use a power supply within the rated frequency range. Using a power supply outside the rated frequency range may result in malfunction, damage, or burning.
- Apply a thin layer of Momentive Performance Material’s YG6260 or Shin-Etsu Chemical’s G747, or a similar product to the heat sink before mounting.
**7.** Do not transport the G3NA under the following conditions. Failure or malfunction may occur.
- Conditions under which the G3NA will be exposed to water
- If a material with high thermal resistance, such as wood, is used, heat generated by the G3NA may occasionally cause fire or burning. When installing the G3NA directly into a control panel so that the panel can be used as a heat sink, use a panel material with low thermal resistance, such as aluminum or steel.
- High temperatures or high humidity
- Without proper packing
## ~~!WARNING~~
Minor Humon hazard by electric shock may occasionally occur. Heatsink must be connected to ground in the end product.
- Use the specified heat sink or one with equivalent or better characteristics.
Solid State Relay **G3NA**
480
## **Operating and Storage Locations**
Do not use or store the G3NA in the following locations. Doing so may result in damage, malfunction, or deterioration of performance characteristics.
- Do not use or store in locations subject to direct sunlight.
- Do not use in locations subject to ambient temperatures outside the range –20 to 60°C.
- Do not use in locations subject to relative humidity outside the range 45% to 85% or locations subject to condensation as the result of severe changes in temperature.
- Do not store in locations subject to ambient temperatures outside the range –30 to 70°C.
- Do not use or store in locations subject to corrosive or flammable gases.
- Do not use or store in locations subject to dust (especially iron dust) or salts.
- Do not use or store in locations subject to shock or vibration.
- Do not use or store in locations subject to exposure to water, oil, or chemicals.
- Do not use or store in locations subject to high temperatures or high humidity.
- Do not use or store in locations subject to salt damage.
- Do not use or store in locations subject to rain or water drops.
## ■ **Precautions for Correct Use**
Please observe the following precautions to prevent failure to operate, malfunction, or undesirable effect on product performance.
## **Before Actual Operation**
## ~~ess~~
**1.** The G3NA in operation may cause an unexpected accident. Therefore it is necessary to test the G3NA under the variety of conditions that are possible. As for the characteristics of the G3NA, it is necessary to consider differences in characteristics between individual SSRs.
**2.** Unless otherwise specified, the ratings in this catalog are tested values in a temperature range between 15°C and 30°C, a relative humidity range between 25% and 85%, and an atmospheric pressure range between 88 and 106 kPa (standard test conditions according to JIS C5442). It will be necessary to provide the above conditions as well as the load conditions if the user wants to confirm the ratings of specific G3NAs.
## **Mounting Method**
## **SSR Mounting Pitch (Panel Mounting)**
**==> picture [180 x 138] intentionally omitted <==**
**----- Start of picture text -----**<br>
Duct<br>a<br>60 mm min.<br>SsR [0] fo)|<br>Vertical direction<br>30 mm min.<br>rs rr a<br>80 mm min.<br>| —<br>**----- End of picture text -----**<br>
## **Relationship between SSRs and Duct Height**
**==> picture [268 x 174] intentionally omitted <==**
**----- Start of picture text -----**<br>
Incorrect Example Countermeasure 1 Countermeasure 2<br>50 mm max.<br>Duct (A height of no<br>more than half Duct<br>Ye— 100 mm, Y t., Y y,<br>the SSR's height<br>= is recommended.)<br>p—tcomm—i SSR | : ai 7 Airflow SSR<br>J H<br>Vertical Base<br>direction<br>Y<br>|'Y,|;t 4<br>Duct Duct Duct<br>7i— / y<br>=<br>Do not surround the SSR Use short ducts. If the ducts cannot be<br>with ducts, otherwise the shortened, place the SSR on<br>heat radiation of the SSR a metal base so that it is not<br>will be adversely affected. surrounded by the ducts.<br>Mounting surface Mounting surface Mounting surface<br>**----- End of picture text -----**<br>
## **Ventilation Outside the Control Panel**
**==> picture [233 x 115] intentionally omitted <==**
**----- Start of picture text -----**<br>
Be aware of airflow<br>Duct<br>(| Ventilation ©<br>outlet<br>_ (axial fan)<br>I(2) SSR<br>Z EIOB|- -SSR i<br>| | io l<br>Air inlet<br>**----- End of picture text -----**<br>
If the air inlet or air outlet has a filter, clean the filter regularly to prevent it from clogging to ensure an efficient flow of air.
Do not locate any objects around the air inlet or air outlet, otherwise the objects may obstruct the proper ventilation of the control panel. A heat exchanger, if used, should be located in front of the SSRs to ensure the efficiency of the heat exchanger.
- Please reduce the ambient temperature of SSRs. The rated load current of an SSR is measured at an ambient temperature of 40°C.
- An SSR uses a semiconductor in the output element. This causes the temperature inside the control panel to increase due to heating resulting from the passage of electrical current through the load. To restrict heating, attach a fan to the ventilation outlet or air inlet of the control panel to ventilate the panel. This will reduce the ambient temperature of the SSRs and thus increase reliability. (Generally, each 10 °C reduction in temperature will double the expected life.)
|**Load current (A)**<br>~~ee~~|**5 A**|**10 A**|**20 A**|**40 A**|**75 A**|**90 A**|
|---|---|---|---|---|---|---|
|Required number<br>of fans per SSR<br>~~ee~~|0.08|0.16<br>0.31|0.31|0.62|1.2|1.44|
Example: For 10 SSRs with load currents of 10 A, 0.16 x 10 = 1.6
Thus, 2 fans would be required.
Size of fans: 92 mm[2] , Air volume: 0.7 m[3] /min,
Ambient temperature of control panel: 30 °C
If there are other instruments that generate heat in the control panel other than SSRs, additional ventilation will be required.
Solid State Relay **G3NA**
481
## **- High capacity Heat Sink - (Y92B P250NF)**
## **DIN-track Mounting**
- Assembled DIN Tracks are heavy. Mount the DIN Tracks securely. Be sure that the Heat Sink is securely locked to the DIN Track.
- Attach End Plates (PFP-M, order separately) to both ends of the Units on the DIN Track to hold them in place.
- To mount a Heat Sink to a DIN Track, press down at the point indicated by arrow 1 in the diagram and then press in the Heat Sink at the point indicated by arrow 2.
## **- Ratings and Characteristics of High - capacity Heat Sink (Y92B P250NF) Fan Ratings**
|**Fan Ratings**||
|---|---|
|**Rated voltage**|200 V|
|**Operating voltage**|85% to 110% of rated voltage|
|**Frequency**|50/60 Hz|
|**Rated current**<br>**(See note.)**|0.061 A at 50 Hz<br>0.052 A at 60 Hz|
|**Rated speed**<br>**(See note.)**|2,600 r/min at 50 Hz<br>3,050 r/min at 60 Hz|
**Note:** Average values.
## **Thermostat Ratings**
|**Operating temperature**|Approx. 90°C|
|---|---|
|**Contact ratings**|3 A at 240 VAC or 24 VDC, resistive load|
**==> picture [24 x 6] intentionally omitted <==**
**----- Start of picture text -----**<br>
Vertical<br>**----- End of picture text -----**<br>
## **Fan/Thermostat Characteristics**
## **Applicable DIN Track**
Mounting is possible on TE35-15Fe (IEC 60715) DIN tracks. DIN tracks from the following manufacturers can be used.
|**Manufacturer**|**Thickness: 1.5 mm**|**Thickness: 2.3 mm**|
|---|---|---|
|Schneider|AM1-DE2000<br>---|---|
|WAGO|210-114 or 210-197<br>210-118|210-118|
|PHOENIX|N35/15|N35/15/15-2.3|
## **Direct Mounting**
- Prepare mounting holes as shown in the diagram. Tightening torque: 0.98 to 1.47 N•m
64[±][0.3]
**==> picture [19 x 5] intentionally omitted <==**
**----- Start of picture text -----**<br>
130 [±][0.3]<br>**----- End of picture text -----**<br>
|**Fan/Thermostat Characteristics**|**Fan/Thermostat Characteristics**|
|---|---|
|**Motor type**|Single-phase shading coil induction motor<br>(2-pole, open type)|
|**Terminal type**|Terminals|
|**Insulation class**|IEC class B (130°C)<br>UL class A (105°C)<br>CSA class A (105°C)|
|**Insulation**<br>**resistance**|100 MΩmin. (at 500 VDC) between all power<br>supply connections and uncharged metal parts.|
|**Insulation withstand**<br>**voltage**|2,000 VAC (1 minute) between all power sup-<br>ply connections and uncharged metal parts.|
|**Amb. operating temp.**|−30 to 70°C (no icing)|
|**Amb. storage temp.**|−40 to 85°C (no icing)|
|**Ambient humidity**|25 to 85%|
|**Protection**|Impedance protection|
|**Materials**|Frame: Die-cast aluminum<br>Blades: Glass polycarbonate|
|**Bearings**<br>**Weiht**|Ball bearings<br>Approx. 300|
|**Weight**|Approx. 300g|
|**Compliant standards**|PSE, EN/IEC 60335 (CE marking compli-<br>ant)|
|**Certified standards**|UL/CSA (pending)|
- Use a commercial power supply (50/60 Hz) for the Fan.
- Be sure to turn OFF the power supply and wait for the blades to stop before inspecting the Fan.
Four, 4.5 dia. or M4 holes
- When mounting a Heat Sink directly, first remove the Fan Unit, then mount the Heat Sink by itself before attaching the Fan Unit again. (Remove the two screws shown in the following diagram.)
**==> picture [87 x 7] intentionally omitted <==**
**----- Start of picture text -----**<br>
Remove screws Fan Unit<br>**----- End of picture text -----**<br>
- High-precision ball bearings are used in the fan and these may be damaged if the Fan is dropped or otherwise subjected to shock. The life and characteristics of the Fan will be reduced if the bearings are damaged. Do not subject the Fan to shock.
- The life of the Fan depends on the ambient temperature, As a guideline, the Fan life is 40,000 hours for continuous usage at 40°C.
- Be sure there are no objects near the air vents that would restrict air flow and no loose objects, such as electrical lines.
- The Fan is an OMRON R87F-A4A-93HP (200 VAC) Fan. Use the same model of Fan for replacement.
- The tightening torque of the mounting screw when replacing the Fan is 0.44 N•m.
- Terminals equivalent to Faston #110 are used for the Fan power supply terminals.
Heat Sink
- First, temporarily mount the Heat Sink with the bottom two screws and then attach the top two screws with the mounting bracket sandwiched between the Heat Sink and mounting surface. Finally, tighten all four screws.
- Refer to the following table for the OMRON Fan power supply plug cables (order separately).
|**Cable**<br>**length**|**UL certified**|**Complies with Electrical Appliance**<br>**and Material Safety Law (Japan)**|
|---|---|---|
|1 m|R87F-PC|R87F-PCJT|
|2 m|R87F-PC-20|R87F-PCJT-20|
- Connect the ground screw hole on the fan to PE.
Solid State Relay **G3NA**
482
## **Preventing Overheating with a -capacity Heat Sink (Y92B-P250NF) -P250NF) High-capacity Heat Sink (Y92B-P250NF) capacity Heat Sink (Y92B-P250NF) P250NF)**
- **Preventing Overheating with a 2.** DC-switching models **High-capacity Heat Sink (Y92B-P250NF)** Less than 3 m **•** When the High-capacity Heat Sink is used, high-capacity switching Lo ~~a~~ d at 75 A or 90 A requires forced cooling with a fan. Connect the Fan Input G3NA-UTU Output
- ~~U~~ to a power supply according to its ratings specifications. ~~S~~ **•** If the Fan stops due to a power supply error, due to foreign matter **•** The input cable must be less than 3 m. in the power supply connection, or due to aging, the Heat Sink will heat to high temperatures, possibly resulting in failure of the SSR or **Loss Time** adverse affects on other devices. Implement an overheating prevention measure, such as turning OFF the load current, if the Heat Sink overheats.
The loss time will increase when the G3NA is used at a low applied
voltage or current. Be sure that this does not cause any problems.
- A thermostat is provided to detect overheating. The thermostat uses a NC contact, i.e., the circuit will be opened for overheating. This thermostat can be used to stop the operation of the SSR. Implement an overheating prevention measure by using this signal to output an alarm or perform another response applicable to the system. Also, confirm that there is no problem with the overall system.
Loss time ~~fo~~
- Do not connect the thermostat directly to the load power supply. Connect it to a contactor or other shutoff device connected above the SSR.
- Terminals equivalent to Faston #187 are used for the thermostat terminals.
## **Using DC Loads**
- Do not place heat-dissipating silicon grease on the thermostat.
For a DC or L load, a diode should be connected in parallel the load
to absorb the counter electromotive force of the load.
- Do not solder the thermostat terminals.
**•** The following diagram shows a protective circuit example.
**==> picture [463 x 91] intentionally omitted <==**
**----- Start of picture text -----**<br>
Circuit breaker<br>Circuit breaker (contact side) Load<br>(coil side) Thermostat Y92B-P250NF Load Input SSR supplyLoad power<br>Coil (NC contact)<br>power<br>supply G3NA Load side<br>Fuses<br>Input side<br>ohT Circuitbreaker h Connect a quick-break fuse in series with the load as a short-circuit 2 protection measure. Use one of the fuses in the following table or one<br>**----- End of picture text -----**<br>
Connect a quick-break fuse in series with the load as a short-circuit protection measure. Use one of the fuses in the following table or one with equivalent or better characteristics.
## **- Ventilating a High capacity Heat Sink - (Y92B P250NF)**
## **Recommended Fuses**
|**Ventilating a High-capacity Heat Sink**<br>**(Y92B-P250NF)**|**Recommended Fuses**|||
|---|---|---|---|
|**•** Refer to_Ventilation Outside the Control Panel_.|**G3NA rated**<br>**Fuse model Manufacturer**|**Fuse model Manufacturer**|**Applicable SSR**|
|**Operating Conditions**|**load current**<br>5 A<br>60LFF5|Hinode Electric|G3NA-205B|
|**•** Do not apply currents exceeding the rated current otherwise, the<br>temperature of the G3NA may rise excessively.|8 A<br>60LFF8|Co., LTD.|G3NA-210B|
|**•** As protection against accidents due to short-circuiting, be sure to|10 A<br>60LFF10|||
|install protective devices, such as fuses and no-fuse breakers, on|15 A<br>60LFF15||G3NA-220B|
|the power supply side.|20 A<br>60LFF20|||
|**•** Do not apply overvoltages to the input circuit or output circuit. Fail-|50SHA20|||
|ure or burning may result.|25 A<br>60PFF25||G3NA-240B|
|**•** Do not drop the G3NA or otherwise subject it to abnormal shock.|50SHA25|||
|Malfunction or failure may result.|30 A<br>60PFF30|||
|**•** Keep the cooling system running continuously during the ON/OFF|50SHA30|||
|operation of the SSR. This is to allow residual heat to dissipate<br>while the SSR is OFF. (load current 75A, 90A models)<br>**EMC Directive Compliance (For-UTU type)**|40 A<br>50SHA40<br>45 A<br>50SHA45<br>50 A<br>50SHA50||G3NA-275B-UTU-2|
|EMC directives can be complied with under the following conditions.|75 A<br>50SHA75|||
|**1.** AC-switching models|80 A<br>50SHA80||G3NA-290B-UTU-2|
|**•** A capacitor must be connected to the input power supply.|100 A<br>50SHB100|||
|**•** A capacitor, varistor and toroidal core must be connected to the<br>load power supply.<br>**•** The input cable must be less than 3 m.<br>G3NA<br>Output<br>Input<br>Recommended Capacitor : 0.05μF, 500 VAC (Load)<br>Troidal core<br>~~Load~~<br>3 m max.<br>~~ay~~ ~~eR~~|**Reverse Connection**<br>The output terminal side of the G3NA-D210B is connected to a built-<br>in diode to protect the SSR from damage that may result from<br>reverse connection. The SSR, however, cannot withstand one minute<br>or more if the wires are connected in reverse. Therefore, pay the<br>utmost attention not to make polarity mistakes on the load side.<br>Oo|||
|0.1μF, 250 VAC (Input)||||
|Recommended Varistor : 470 V, 1750 A||||
Recommended Troidal core : NEC/TOKIN:ESD-R-25B or equivalent
Solid State Relay **G3NA**
483
## ■ **Precautions on Operating and Storage Environments**
## **1. Operating Ambient Temperature**
The rated value for the ambient operating temperature of the G3NA is for when there is no heat build-up. For this reason, under conditions where heat dissipation is not good due to poor ventilation, and where heat may build up easily, the actual temperature of the G3NA may exceed the rated value resulting in malfunction or burning.
When using the G3NA, design the system to allow heat dissipation sufficient to stay below the _Load Current vs. Ambient Temperature_ characteristic curve. Note also that the ambient temperature of the G3NA may increase as a result of environmental conditions (e.g., climate or air-conditioning) and operating conditions (e.g., mounting in an airtight panel).
## **2. Transportation**
When transporting the G3NA, observe the following points. Not doing so may result in damage, malfunction, or deterioration of performance characteristics.
## **3. Vibration and Shock**
Do not subject the G3NA to excessive vibration or shock. Otherwise the G3NA may malfunction and internal components may be deformed or damaged, resulting in failure of the G3NA to operate. To prevent the G3NA from abnormal vibration, do not install the G3NA in locations or by means that will subject it to vibration from other devices, such as motors.
## **4. Solvents**
Do not allow the G3NA or the resin portion of the Fan’s thermostat to come in contact with solvents, such as thinners or gasoline. Doing so will dissolve the markings on the G3NA.
## **5. Oil**
Do not allow the G3NA terminal cover to come in contact with oil. Doing so will cause the cover to crack and become cloudy.
- Do not drop the G3NA or subject it to severe vibration or shock.
- Do not transport the G3NA if it is wet.
- Do not transport the G3NA under high temperatures or humidity.
- Do not transport the G3NA without packing it properly.
## ■ **Operation**
## **1. Leakage Current**
A leakage current flows through a snubber circuit in the G3NA even when there is no power input. Therefore, always turn OFF the power to the input or load and check that it is safe before replacing or wiring the G3NA.
Switch element Snubber circuit Leakage current Nae
## **2. Screw Tightening Torque**
Tighten the G3NA terminal screws properly. If the screws are not tight, the G3NA will be damaged by heat generated when the power is ON. Perform wiring using the specified tightening torque.
## **3. Handling Relays**
## **4. Do Not Drop** ~~a~~
Do not mount the G3NA when your hands are oily or dirty, e.g., with metal powder. These may cause G3NA failure.
Be careful not to drop a Relay or Heat Sink onto any part of your body while working. Injury may result. This is particularly true for the High-capacity Heat Sink (Y92B-P250NF), which weighs 2.5 kg.
Solid State Relay **G3NA**
484
**==> picture [39 x 10] intentionally omitted <==**
**----- Start of picture text -----**<br>
MEMO<br>**----- End of picture text -----**<br>
Solid State Relay **G3NA**
**All sales are subject to Omron Electronic Components LLC standard terms and conditions of sale, which can be found at http://www.components.omron.com/components/web/webfiles.nsf/sales_terms.html** ~~pt~~ **ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.** To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. ~~pT~~ OMRON. **OMRON ELECTRONIC OMRON ON-LINE COMPONENTS LLC** Global - http://www.omron.com 55 E. Commerce Drive, Suite B USA - http://www.components.omron.com Schaumburg, IL 60173 **847-882-2288**
**OMRON ON-LINE** Global - http://www.omron.com USA - http://www.components.omron.com
Printed in USA
Cat. No. X301-E-1b 09/11 Specifications subject to change without notice
Solid State Relay **G3NA**
Updated at June 10, 2026
With a legacy spanning over 80 years, Omron Industrial Automation is a globally recognized leader in the manufacture of advanced industrial control and automation components. Renowned for their reliability and engineering excellence, Omron delivers comprehensive solutions that enhance efficiency, machine safety, and precision across a wide range of manufacturing environments. Our extensive portfolio of Omron products is heavily focused on their industry-leading sensing and switching technologies. We offer a vast selection of sensors, excelling specifically in high-performance proximity sensors, light sensors, and temperature sensors. Complementing this range are robust switching solutions, featuring a deep inventory of power relays, solid-state relays, safety relays, and essential relay accessories designed for demanding operational requirements. Beyond sensing and switching, Omron is highly regarded for its precision automation and process control equipment. Our selection features highly accurate temperature controllers, versatile process controllers, and sophisticated panel displays and instrumentation. To support these fundamental systems, we also supply dependable Omron power supplies, notably AC/DC converters, alongside vital connectivity components like DIN rail terminal blocks to ensure secure, efficient, and complete industrial setups.
About Novapart
Novapart is a B2B electronic component broker specialising in stock shortages and cost reduction. We source hard-to-find parts and identify compliant alternatives across a catalogue of 410,000+ components from 500+ manufacturers.
Learn more →Stock Shortage Specialist
When a component is unavailable, discontinued or has an unacceptable lead time, we tap into our network of vetted European and Asian distributors to source what you need — without compromising on quality or traceability.
Request a quote →Compliant Alternatives
We identify pin-to-pin, electrically equivalent substitutes that meet the same certifications (RoHS, AEC-Q100, REACH) as your original specification — validated against datasheets, not just part numbers. Often at a lower cost.
BOM Analysis service →