Image not available
Illustrative purposes only
ESM-BA 301
Safety Relay, 24 V, 3NO / 1NC, ESM, DIN Rail, 8 A, Screw
⚠️ Reference pricing provided. In case of supply shortages, we will connect you with our trusted procurement partners to ensure your project's continuity.
- Manufacturer: EUCHNER
- Product type: Safety Relays
- IP Rating: IP20
- Coil Voltage: 24V
- Product Range: ESM
- Relay Mounting: DIN Rail
- Contact Current: 8A
- Relay Terminals: Screw
- Contact Configuration: 3NO / 1NC
- Contact Voltage AC Nom: 250V
- Contact Voltage DC Nom: 50V
| Delivery and price | |
|---|---|
| Units per pack | 10 |
| Price | 145.29 € |
| Current stock | 10+ |
| Lead time | 30 days |
## Emergency Stop Safety Relay ESM-BA3..
## User Information
## _Correct Use_
The ESM-BA3.. is a universal emergency stop safety switching device with three safe relay outputs that can quickly and safely stop the moving parts of a machine or system in case of danger.
Applications for the ESM-BA3.. include single or dual-channel emergency stop circuits and guard monitoring on machines and systems.
- _Features_ • _3 safe, redundant relay outputs_
- _1 auxiliary contact (signaling contact)_
- _Connection of:_
- _Emergency stop buttons_
- _Safety switches_
- _Non-contact safety switches_
- _OSSD-Outputs_
- _Single and dual-channel operation possible_
- _Feedback loop for monitoring downstream contactors or expansion modules_
- _Cyclical monitoring of the output contacts_
- _Indication of the switching state via LED_
- _2 start behaviors possible:_
- _Monitored manual start_
- _Automatic start_
- _Short circuit and earth fault monitoring_
- _Up to PL e, SILCL 3, category 4_
## _Function_
The emergency stop safety switching device ESM-BA3.. is designed for safe isolation of safety circuits according to EN 60204-1 and can be used up to safety category 4, PL e according to EN ISO 13849-1.
The internal logical system closes the safety contacts when the start button is pressed.
When the safety switch is opened, the positively driven safety contacts are opened and safely switch the machine off. It is ensured that a single fault does not lead to a loss of the safety function and that every fault is detected by cyclical self-monitoring no later than when the system is switched off and switched on again.
Fig. 1 Block diagram ESM-BA3..
_Installation_
As per EN 60204-1, the device is intended for installation in control cabinets with a minimum degree of protection of IP54. It is mounted on a 35 mm DIN rail according to DIN EN 60715 TH35.
Fig. 2 Installation / removal
- _Safety_ • Installation and commissioning of the device must be _Precautions_ performed **only by authorized personnel** .
- Observe the country-specific regulations when installing the device.
- The electrical connection of the device is only allowed to be made with the device isolated.
- The wiring of the device must comply with the instructions in this user information, otherwise there is a risk that the safety function will be lost.
- It is not allowed to open the device, tamper with the device or bypass the safety devices.
- All relevant safety regulations and standards are to be observed.
- The overall concept of the control system in which the device is incorporated must be validated by the user.
- Failure to observe the safety regulations can result in death, serious injury and serious damage.
- Note down the version of the product (see label “Vx.x.x”) and check it prior to every commissioning of a new device. If the version has changed, the overall concept of the control system in which the device is incorporated must be validated again by the user.
- _Electrical_ • When the 24 V version is used, a safety transformer _Connection_ according to EN 61558-2-6 or a power supply unit with electrical isolation from the mains must be connected.
- External fusing of the safety contacts (6A slow-blow or 8A quick-action or 10 A gG) must be provided.
- A maximum length of the control lines of 1000 meters with a line cross section of 0.75 mm[2] must not be exceeded.
- The line cross section must not exceed 2.5 mm[2] .
- If the device does not function after commissioning, it must be returned to the manufacturer unopened. Opening the device will void the warranty.
|_A1:_<br>_A2 :_<br>_S11:_<br>_S10:_<br>_S21:_<br>_S13:_<br>_S14:_|_Power supply_<br>_Power supply_<br>_DC 24V control voltage_<br>_Control line_<br>_Start control line_<br>_Control line_<br>_Control line_|
|---|---|
|_S12:_<br>_13-14:_<br>_23-24:_<br>_33-34:_|_Control line_<br>_Safety contact 1_<br>_Safety contact 2_<br>_Safety contact 3_|
|_41-42:_|_Auxiliary contact_|
Fig. 3 Connections
V1.1.0
1
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de info@euchner.de
## Emergency Stop Safety Relay ESM-BA3..
## User Information
_Applications_
Depending on the application or the result of the risk assessment according to EN ISO 13849-1, the device must be wired as shown in Fig. 1 to Fig. 11.
## _**Emergency Stop**_
_**Circuit**_
## _**Fig. 1:**_
_Two-channel emergency stop circuit with short circuit and earth fault monitoring. (category 4, up to PL e)_
## _**Fig. 3:**_
_Single-channel emergency stop circuit with earth fault monitoring. (category 1, up to PL c)_
## _**Fig. 2:**_
_Two-channel emergency stop circuit with earth fault monitoring. (category 3, up to PL d)_
## _**Fig. 4:**_
_Two-channel sliding guard monitoring with short circuit and earth fault monitoring. (category 4, up to PL e)_
## _**Fig. 5:**_
## _**Starting Behavior**_
## _**Feedback Loop**_
_Two-channel emergency stop with pnp-outputs/OSSD-outputs_ _**with** short circuit monitoring. (category 4, up to PL e)_
## _**Fig. 6:**_
_Monitored manual start. It is monitored that the start button was opened before the emergency stop button closes. (Prerequisite: operating voltage must not be interrupted.)_
## _**Fig. 8:**_
_Feedback loop for monitored manual start: The feedback loop monitors contactors or the expansion modules ._
## _**Notice:**_
In order to activate earth fault monitoring, S10 must be connected to PE (protective earth) on the AC115/230V devices. With AC/DC 24V, connect PE only to the power supply unit according to EN60204-1.
## _**Fig. 7:**_
_Automatic start. Max perm. delay during closing_ $11 $21 $12 _of the safety switches on S12 and S13: S12 before S13: 300 ms_ _**Warning:** S13 before S12: any Safety contacts switch immediately when the_
## _**Fig. 9:**_
_Feedback loop for automatic start: The feedback loop monitors contactors or the expansion modules ._
## _**Power supply**_
_**and Safety contacts**_
## _**Fig. 10:**_
_Power supply A1 and A2. (Power supply according to techn. data )_
## _**Fig. 11:**_
_Connecting load to safety contacts._
_(Figure shows example. Voltage „+V“ according to techn. data)_
_Commissioning_ _**Note:** The items listed under “Electrical connection” must be observed during commissioning. Procedure_
**1. Wiring emergency stop circuit:**
Wire the emergency stop circuit according to the required Performance Level determined (see Fig. 1 to Fig. 5).
**2. Wiring start circuit:** Wire the start circuit according to Fig. 6 or Fig. 7 to set the starting behavior.
_**Warning:**_
If “Automatic start” is set, bear in mind that the safety contacts will switch immediately after the power supply is connected. If “Monitored manual start” is set, the start button must be opened after wiring.
**3. Wiring feedback loop:**
If your application provides for external contactors or expansion modules, connect them to the device according to Fig.8 or Fig. 9.
**4. Wiring power supply:**
Connect the power supply to terminals A1 and A2 (Fig. 10). _**Warning:**_ Wiring only in de-energized state.
**5. Starting the device:** Switch the operating voltage on.
## _**Warning:**_
If the “Automatic start” starting behavior is set, the safety contacts will close immediately.
If the “Monitored manual start” starting behavior is set, close the start button to close the safety contacts.
LEDs _**K1**_ and _**K2**_ are lit.
**6. Triggering safety function:** Open the emergency stop circuit by actuating the connected safety switch. The safety contacts open immediately.
**7. Reactivation:**
Close the emergency stop circuit. If “Automatic start” is selected, the safety contacts will close immediately. If the “Monitored manual start” starting behavior is set, close the start button to close the safety contacts.
V1.1.0
2
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de info@euchner.de
Emergency Stop Safety Relay ESM-BA3..
## User Information
_Maintenance_ The device must be checked once per month for proper function and for signs of tampering and bypassing of the safety function.
The device is otherwise maintenance free, provided that it was installed properly.
- _What to Do in_ **Device does not switch on:** _Case of a Fault?_ • _Check the wiring by comparing it to the wiring diagrams._ • _Check the safety switch used for correct function and adjustment._
- **Device cannot be switched on again after an emergency stop:** • _Check whether the emergency stop circuit was closed again._
- _Check whether the emergency stop circuit is closed._ • _Was the start button opened before closing of the emer-_
- • _Check whether the start button (with manual start) is gency stop circuit (with manual start)? closed._ • _Is the feedback loop closed?_
- • _Check the operating voltage at A1 and A2._ If the fault still exists, perform the steps listed under • _Is the feedback loop closed?_ “Commissioning Procedure”.
If these steps do not remedy the fault either, return the device to the manufacturer for examination.
**Opening the device is impermissible and will void the warranty.** _Safety_ The device is certified according to EN ISO 13849-1 up to a **Note:** _Characteristics_ Performance Level of PL e. Additional data can be requested from the manufacturer for _According to_ applications that deviate from these conditions. _EN ISO 13849-1_
|**_Safety characteristics according to EN ISO 13849-1 for all variants of ESM-BA3_**|**_Safety characteristics according to EN ISO 13849-1 for all variants of ESM-BA3_**|**_Safety characteristics according to EN ISO 13849-1 for all variants of ESM-BA3_**|**_Safety characteristics according to EN ISO 13849-1 for all variants of ESM-BA3_**|
|---|---|---|---|
|**Load (DC-13; 24V)**|**<= 0,1A**|**<= 1A**|**<= 2A**|
|**T10d**[years]<br>**Category:**<br>**PL**<br>**PFHd [1/h]:**<br>**nop**[cycle / year]|**20**<br>**4**<br>**e**<br>**1,2E-08**<br>**<= 500.000**|**20**<br>**4**<br>**e**<br>**1,2E-08**<br>**<= 350.000**|**20**<br>**4**<br>**e**<br>**1,2E-08**<br>**<= 100.000**|
_Techn. Data_
|Operating voltage|**_ESM-BA301_**<br>**_ESM-BA302_**|**_ESM-BA303_**|
|---|---|---|
||AC/DC24V<br>AC115V|AC230V|
|Rated supply frequency|50-60 Hz||
|Permissible deviation|+ /- 10%||
|Power consumption|**_DC 24V_**<br>**_AC 230V_**||
||approx. 2.3Wapprox.6.9VA||
|Control voltage at S11|DC 24 V||
|Controlcurrent S11...S14|approx.60mA||
|Safety contacts|3NO contacts||
|Auxiliary contacts|1 NC contact||
|Max.switchingvoltage|AC250V||
|Safety contact breaking capacity (13-14, 23-24, 33-34)|AC:<br>250 V, 2000 VA, 8 A for ohmic load,||
||250 V, 3 A for AC-15||
||DC:<br>50 V, 400 W, 8 A for ohmic load;||
||24 V, 3 A for DC-13||
||Max. total current through all 3 contacts||
||15A(13-14,23-24, 33-34)*)||
|Auxiliary contact breaking capacity (41-42)|AC:<br>250 V, 500 VA, 2 A for AC-12||
||DC:<br>50V,100W,2 A for DC-12||
|Minimumcontactload|24 V, 5mA||
|Contact fuses|6 A slow-blow or 8 A quick-action or 10 A gG||
|Line cross section|0.14 - 2.5mm2||
|Max. length of control line|1000 m with 0.75 mm2||
|Contactmaterial|AgSnO2||
|Contact service life|mech. approx. 1 x 107||
|Testvoltage|2.5kV(control voltage/contacts)||
|Ratedimpulsewithstandvoltage,leakage path/airgap|4 kV<br>(DIN VDE0110-1)||
|Rated insulation voltage|250 V||
|Degree ofprotection|IP20||
|Temperature range|-15°C to +40°C*)||
|Degree ofcontamination|2<br>(DIN VDE0110-1)||
|Overvoltage category|3<br>(DIN VDE 0110-1)||
|Weight|approx. 230 g||
|Mounting|DIN railaccording toEN60715TH35||
*) If several ESM-BA3.. devices are closely spaced under load, the max. total current at the ambient temperature of T=20°C: 9A; at T=30°C: 3A; at T=40°C =1A. If these currents are exceeded, a spacing of 5 mm between the devices must be observed.
V1.1.0
3
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de info@euchner.de
Emergency Stop Safety Relay ESM-BA3..
## User Information
**==> picture [323 x 18] intentionally omitted <==**
**----- Start of picture text -----**<br>
Dimension Fixed Plug-In<br>Drawing Terminals — Terminals<br>**----- End of picture text -----**<br>
V1.1.0
4
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de info@euchner.de
Updated at February 9, 2023
About Novapart
Novapart is a B2B electronic component broker specialising in stock shortages and cost reduction. We source hard-to-find parts and identify compliant alternatives across a catalogue of 410,000+ components from 500+ manufacturers.
Learn more →Stock Shortage Specialist
When a component is unavailable, discontinued or has an unacceptable lead time, we tap into our network of vetted European and Asian distributors to source what you need — without compromising on quality or traceability.
Request a quote →Compliant Alternatives
We identify pin-to-pin, electrically equivalent substitutes that meet the same certifications (RoHS, AEC-Q100, REACH) as your original specification — validated against datasheets, not just part numbers. Often at a lower cost.
BOM Analysis service →