CUB4LP40
LOOP POWERED PROCESS METER
⚠️ Reference pricing provided. In case of supply shortages, we will connect you with our trusted procurement partners to ensure your project's continuity.
- Manufacturer: RED LION CONTROLS
- Product type: Digital Panel Meters
- Operating Temperature Max: 60°C
- Operating Temperature Min: 0°C
| Delivery and price | |
|---|---|
| Units per pack | 1 |
| Price | 226.1 € |
| Current stock | 10+ |
| Lead time | 7 days |
**==> picture [532 x 340] intentionally omitted <==**
**----- Start of picture text -----**<br>
@ ® Bulletin No. CUB4LP-L<br>Drawing No. LP0318<br>Released 4/08<br>Tel +1 (717) 767-6511<br>Fax +1 (717) 764-0839<br>www.redlion.net<br>@ DUAL RANGE, 4 to 20 mA OR 10 to 50 mA<br>@ 3%-DIGIT, 0.6" (15.2 mm) HIGH DIGITS<br>(i eSniec eeO -red ifn @ POSITIVE IMAGE TRANSFLECTIVE LCD WITH RED BACKLIGHT<br>i = 428 | @ ORPOSITIVEPOSITIVE IMAGEIMAGE TRANSFLECTIVEREFLECTIVE LCD LCD(CUB4LP) WITH RED BACKLIGHT<br>ise ae caer : OR NEGATIVE IMAGE TRANSMISSIVE WITH RED OR<br>M4 | { = ie- FIR ~~ ped: YELLOW/GREEN BACKLIGHT (CUB4CL)<br>| " @ SPAN AND OFFSET CAPABILITY<br>|| | @ NEGATIVE AND OVERRANGE INDICATION<br>Ribose<br>| 3 @@ SELECTABLENEMA 4X/IP65 DECIMALSEALED POINTFRONT POSITION PANEL BEZEL<br>Pe nd:<br>DESCRIPTION SAFETY SUMMARY<br>**----- End of picture text -----**<br>
The CUB4LP and CUBA4CL are additions to the CUB4 product line. The CUBALP uses a 4 to 20 mA or a 10 to 50 mA input signal as operating power. The input signal is also used to power the backlighting on the CUB4LP40 unit. The CUB4CL uses a 4 to 20 mA or a 10 to 50 mA input signal to power the unit. An extemal power supply is used to power the CUB4CL backlighting to provide a bnghter, more consistent display and a lower compliance voltage.
All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
The units have a 3%2-digit LCD display with 0.6" (15.2 mm) high digits and WARNING - EXPLOSION HAZARD - SUBSTITUTION a DIP switch selectable decimal point. The CUB4LP display is available in OF COMPONENTS MAY IMPAIR SUITABILITY FOR peuisive inane aeMecties (desk ditie, soflecteen backpecunil) cx poeidcve aeegs CLASS |, DIVISION 2/ CLASS II, DIVISION 2 / CLASS III, DIVISION 2 transflective (dark digits, illuminated background) with red backlighting. The CUBACL display is available in positive image transflective (dark digits. SPECIFICATIONS illuminated background) with red or yellow/green backlighting or negative 1. DISPLAY: 3%-digit (-1999 to 1999), 0.6" (15.2 mm) high digits. image transmissive (illuminated digits, dark background) with red or The CUB4LP is available with a positive image reflective LCD or a red yellow/green backlighting. backlit positive image transflective LCD. The intensity of the backlighting The ability to scale the display allows indication in any desired unit of will vary with the input signal. measurement such as temperature, pressure, humidity, fluid flow, etc. The unit The CUB4CL is available with a positive image transflectrve LCD with red is calibrated at the factory with 0.0 displayed @ 4 mA input and 100.0 displayed or yellow/green backlighting or a negative image transmissive with red or @ 20 mA input. yellow/green backlight. The units are contained in a lightweight, high impact plastic case with a clear A minus minus sign is displayed when the when the the indicator is adjusted for a for a a negative offset. viewing window. When properly installed, the sealed front panel meets NEMA Overrange: Overrange is indicated by by a “1” in the most most significant digit and 4X/IP65 specifications for wash-down and dusty environments. the blanking of the the three least significant digits. 2. EXTERNAL BACKLIGHT POWER: (CUB4CL only) Read complete inetnuctons. orior to (NEC)99 - 28 VDC,or SELV @ 28 VDC,or SELV @ VDC,or SELV @or SELV @ SELV @ @ rated.35 mA Above typ.,35 mA Above typ., mA Above typ., Above typ., typ., 5026 VDC,mA26 VDC,mA VDC,mAmA max.derate PowertheSuoderate PowertheSuo PowertheSuotheSuoSuoo **p** eratingplies musttemperature be Class 2toplies musttemperature be Class 2to musttemperature be Class 2totemperature be Class 2to be Class 2to Class 2to 2toto installation and operation of the unit. 50 Cc.
- The CUB4CL is available with a positive image transflectrve LCD with red or yellow/green backlighting or a negative image transmissive with red or yellow/green backlight.
- A minus minus sign is displayed when the when the the indicator is adjusted for a for a a negative offset. Overrange: Overrange is indicated by by a “1” in the most most significant digit and the blanking of the the three least significant digits.
2. EXTERNAL BACKLIGHT POWER: (CUB4CL only) (NEC)99 - 28 VDC,or SELV @ 28 VDC,or SELV @ VDC,or SELV @or SELV @ SELV @ @ rated.35 mA Above typ.,35 mA Above typ., mA Above typ., Above typ., typ., 5026 VDC,mA26 VDC,mA VDC,mAmA max.derate PowertheSuoderate PowertheSuo PowertheSuotheSuoSuoo **p** eratingplies musttemperature be Class 2toplies musttemperature be Class 2to musttemperature be Class 2totemperature be Class 2to be Class 2to Class 2to 2toto 50 Cc.
3. DECIMAL POINTS: Three DIP switch selectable, decimal point positions allow the display to be read in tenths, hundredths or thousandths.
## DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
**==> picture [259 x 48] intentionally omitted <==**
**----- Start of picture text -----**<br>
r .13 (3.3) PANEL CUT—OUT<br>—— 2.68 +:025—_| —<br>1.29 (32.8) (68 *-8) 1.30 +.024“990<br>**----- End of picture text -----**<br>
**==> picture [160 x 79] intentionally omitted <==**
**----- Start of picture text -----**<br>
———_—rea<br>1.54 (39.1)<br>L 2.95 (74.9) ————-<br>**----- End of picture text -----**<br>
**==> picture [127 x 22] intentionally omitted <==**
**----- Start of picture text -----**<br>
15 (3.8) | _ 1.96 (49.8) _|<br>**----- End of picture text -----**<br>
1
## _**SPECIFICATIONS (Cont’d)**_
## 4. **MAXIMUM VOLTAGE DROP** :
3.2 VDC for CUB4LP00
- 4.0 VDC for CUB4LP40
- 3.2 VDC for CUB4CL all models
5. **EQUIVALENT RESISTANCE** :
**CUB4LP00** : 800 Ω max. @ 4 mA; 160 Ω max. @ 20 mA
- 320 Ω max. @ 10 mA; 65 Ω max. @ 50 mA
- **CUB4LP40** : 1000 Ω max. @ 4 mA; 200 Ω max. @ 20 mA
400 Ω max. @ 10 mA; 80 Ω max. @ 50 mA
- **CUB4CL (all models)** : 800 Ω max. @ 4 mA; 160 Ω max. @ 20 mA
- 320 Ω max. @ 10 mA; 65 Ω max. @ 50 mA
6. **MAXIMUM ALLOWABLE INPUT CURRENT** : 100 mA
7. **SCALING RANGE** :
- **Span** : Two potentiometers provide a coarse and fine span adjustment. Span range = 0 to 2000.
- **Offset** : Two potentiometers provide a coarse and fine zero offset adjustment. Offset range = -1999 to 1999.
8. **LINEARITY** : (@ 23 C, Less than 85% RH) ±(0.1% + 1 digit).
9. **READING RATE** : 2.5 per second, nominal.
10. **RESPONSE TIME** : 1.5 seconds to settle for a step change.
11. **NORMAL MODE REJECTION** : 60 dB 50/60 Hz
12. **TEMPERATURE EFFECTS** :
- **Span Temperature Coefficient** : 100 PPM/ _°_ C
- **Offset Temperature Coefficient** : 0.2 digits/ _°_ C
13. **CONSTRUCTION** : High impact plastic case with clear viewing window. (Panel gasket and mounting clips included.) This unit is rated for NEMA
- 4X/IP65 indoor use. Installation Category I, Pollution Degree 2
14. **CERTIFICATIONS AND COMPLIANCES** :
## **SAFETY**
## **ELECTROMAGNETIC COMPATIBILITY**
|**Immunity to EN 50082-2**|||
|---|---|---|
|Electrostatic discharge|EN 61000-4-2|Level 2; 4 Kv contact|
|||Level 3; 8 Kv air|
|Electromagnetic RF fields|EN 61000-4-3|Level 3; 10 V/m1|
|||80 MHz - 1 GHz|
|Fast transients (burst)|EN 61000-4-4|Level 4; 2 Kv I/O|
|RF conducted interference|EN 61000-4-6|Level 3; 10 V/rms2<br>Level 3; 2 Kv power|
|Power frequency magnetic fields|EN 61000-4-8|Level 4; 30 A/m<br>150 KHz - 80 MHz|
|**Emissions to EN 50081-1**|||
|RF interference|EN 55011|Enclosure class B|
|||Power mains class B|
## _**Notes**_
_1. Self-recoverable loss of performance during EMI disturbance at 10 V/m Process Signal may deviate during EMI disturbance._
_For operation without loss of performance_
- _Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent) connected to earth ground._
_2. Self-recoverable loss of performance during EMI disturbance at 10 Vrms. Process signal may deviate during EMI disturbance._
_For operation without loss of performance_
- _Install 1 ferrite core, RLC #FCOR0000 or equivalent, to signal cable at the unit._
- _Refer to the EMC Installation Guidelines of this bulletin for additional information._
15. **ENVIRONMENTAL CONDITIONS** :
- **Operating Temperature** : 0 _°_ to 60 _°_ C
- (Derate backlight voltage to 26 VDC above 50 _°_ C.)
- **Storage Temperature** : -40 _°_ to 80 _°_ C
Type 4X Indoor Enclosure rating (Face only), UL50
- IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for measurement, control and laboratory use, Part 1.
- IP65 Enclosure rating (Face only), IEC 529
- **Operating and Storage Humidity** : 85% max. (non-condensing) from 0 _°_ C to 60 _°_ C.
**Vibration According to IEC 68-2-6:** Operational 5 to 500 Hz, in X, Y, Z direction for 1.5 hours, 5g’s.
**Shock According to IEC 68-2-27:** Operational 30 g, 11 msec in 3 directions. **Altitude** : Up to 2000 meters
16. **WEIGHT** : 3.3 oz. (93.5 g)
## _**INSTALLATION**_
When properly installed, the CUB4LP/CL meets NEMA 4X/IP65 requirements for indoor use. The units are intended to be mounted into an enclosed panel. A sponge rubber gasket, mounting clip, two screws, and nut fasteners are provided to install and seal the unit in the panel cutout.
## _**Installation Environment**_
The unit should be installed in a location that does not exceed the maximum operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided.
- The bezel should be cleaned only with a soft
- cloth and neutral soap product. Do NOT use solvents.
Continuous exposure to direct sunlight may accelerate the aging process of the bezel.
The following procedure assures proper installation:
1. Cut the panel opening to the specified dimensions. Remove burrs and clean the panel opening.
2. Slide nut fastener into slot on mounting clip and then insert mounting screw through nut on both sides of mounting clip. The tip of mounting screw should not project through hole on clip.
3. Slide the panel gasket over the rear of the unit to the back of the bezel. Install CUB4LP/CL unit through panel cutout.
4. Slide mounting clip over rear of unit until the clip is against back of panel. The mounting clip and CUB4LP/CL housing have a latching feature to hold the unit in place until tightened.
- _Note Hold the CUB4LP/CL front bezel in place when sliding the mounting clip into position._
5. Alternately tighten each mounting screw to ensure uniform gasket pressure. Visually inspect the gasket for proper seal. The gasket should be compressed
to approximately 75 to 80% of its original thickness. (Recommended torque is 28 to 36 in-oz.)
6. If the gasket is not adequately compressed and the mounting screws cannot be tightened any further, loosen the mounting screws and insure that the clip is latched as closely as possible to the panel.
7. Repeat Step #6 for tightening the mounting screws.
_**2**_
## _**EMC INSTALLATION GUIDELINES**_
Although this unit is designed with a high degree of immunity to ElectroMagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into the unit may be different for various installations. Cable length, routing and shield termination are very important and can mean the difference between a successful installation or a troublesome installation. Listed below are some EMC guidelines for successful installation in an industrial environment.
1. Use shielded (screened) cables for all Signal and Control inputs. The shield (screen) pigtail connection should be made as short as possible. The connection point for the shield depends somewhat upon the application. Listed below are the recommended methods of connecting the shield, in order of their effectiveness.
- a. Connect the shield only at the panel where the unit is mounted to earth ground (protective earth).
- b. Connect the shield to earth ground at both ends of the cable, usually when the noise source frequency is above 1 MHz.
- c. Connect the shield to common of the unit and leave the other end of the shield unconnected and insulated from earth ground.
2. Never run Signal or Control cables in the same conduit or raceway with AC power lines, conductors feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run in metal conduit that is properly grounded. This is especially useful in applications where cable runs are long and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter.
3. Signal or control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components.
4. In extremely high EMI environments, the use of external EMI suppression devices, such as ferrite suppression cores, is effective. Install them on Signal and Control cables as close to the unit as possible. Loop the cable through the core several times or use multiple cores on each cable for additional protection. Install line filters on the power input cable to the unit to suppress power line interference. Install them near the power entry point of the enclosure. The following EMI suppression devices (or equivalent) are recommended: Ferrite Suppression Cores for signal and control cables:
- Fair-Rite # 0443167251 (RLC #FCOR0000) TDK # ZCAT3035-1330A Steward #28B2029-0A0
- Line Filters for input power cables: Schaffner # FN610-1/07 (RLC #LFIL0000) Schaffner # FN670-1.8/07 Corcom #1VR3
_**Note:** Reference manufacturer’s instructions when installing a line filter._
5. Long cable runs are more susceptible to EMI pickup than short cable runs. Therefore, keep cable runs as short as possible.
## _**WIRING CONNECTIONS**_
**==> picture [315 x 182] intentionally omitted <==**
All conductors should meet voltage and current ratings for each terminal. Also cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that power supplied to the unit (AC or DC) be protected by a fuse or circuit breaker.
The electrical connections are made via screw-clamp terminals located on the back of the unit. When wiring the unit, use the label to identify the wire position with the proper function. Strip the wire, leaving approximately ¼" of bare wire (stranded wires should be tinned with solder). Insert the wire into the screwclamp terminal and tighten the screw until the wire is clamped tightly. Each terminal can accept up to two #14 AWG wires.
## _**CUB4LP/CL SIGNAL INPUT**_
The current range is selected by setting DIP switch S1 to the OFF position for a 4 to 20 mA input or ON for a 10 to 50 mA input. Attach the signal wires to terminals 3 (SIG-) and 4 (SIG+) observing the correct polarity. The (SIG-) signal input circuit is not reverse polarity protected.
## **Backlight Power (CUB4CL only)**
Attach a 9 to 28 VDC supply to terminals 1 (COM) and 2 (V+) to power the backlight. Terminals 3 (SIG-) and 1 (COM) are AC coupled with a capacitor. This limits the isolation between these terminals to 50 VDC maximum.
## _**SPAN ADJUSTMENTS**_
Span is defined as the numerical range that the display traverses, disregarding the decimal point, when the input signal is varied from minimum to maximum (4 to 20 mA or 10 to 50 mA). For example; if a unit is to display 250 @ 4 mA and 1000 @ 20 mA, the span is 750 (the difference between 250 and 1000). Had the minimum display been -250, the span would be 1250 (1000 - (-250) = 1250). The CUB4LP/CL can be set to operate over a wide span range by adjusting the Coarse and Fine Span adjustment pots. The Coarse Span pot is used to get the display to within a couple of counts of the desired reading, and the Fine Span pot is used to adjust for the exact reading.
## _**OFFSET ADJUSTMENTS**_
The minimum currents are not zero based with 4 to 20 mA and 10 to 50 mA signals. To obtain a zero minimum display reading, the display must be offset. The display on the CUB4LP/CL can be offset by adjusting the Coarse and Fine Offset pots.
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
**==> picture [43 x 37] intentionally omitted <==**
_THIS EQUIPMENT IS SUITABLE FOR USE IN: Class I, Division 2, Groups A, B, C, and D Class II, Division 2, Groups F and G Class III, Division 2 or Non Hazardous locations._
_**3**_
## _**DECIMAL POINT POSITION SELECTION**_
The decimal point position is DIP switch selectable for one of three locations. The CUB4LP/CL can be set up to read in 10ths, 100ths, or 1000ths. If all the DIP switches are set to the “OFF” position, no decimal point will appear on the display. The DIP switches are located at the rear of the unit.
## _**APPLICATION EXAMPLE**_
Operation of a refinery process required a local display of the position of a remote pipeline valve. The display would indicate 0 (zero) when the valve was fully closed with an input signal of 4 mA. When the valve was fully open the display would indicate 100 with an input signal of 20 mA.
Both the CUB4LP and the CUB4CL meet the necessary requirements.
**==> picture [140 x 112] intentionally omitted <==**
## _**CALIBRATING THE DISPLAY**_
Calibrating the CUB4LP/CL requires either an accurate adjustable constant current supply or the CUB4LP/CL can be installed and scaled with the process sensor connected to the CUB4LP/CL. To calibrate the unit, proceed as follows.
1. Set DIP switching for the desired current range.
2. Select the desired decimal point position.
3. Apply the minimum input signal to the CUB4LP/CL and adjust the COARSE OFFSET to display the approximate desired minimum value.
- 4.Apply the maximum input signal to the CUB4LP/CL and adjust the COARSE SPAN to display the approximate desired maximum value.
5. Repeat steps 3 and 4 until the minimum and maximum values are within the desired values.
6. Apply the minimum input signal to the CUB4LP/CL and adjust the FINE OFFSET to display the exact desired minimum value.
7. Apply the maximum input signal to the CUB4LP/CL and adjust the FINE SPAN to display the exact desired maximum value.
8. Apply the minimum input signal and verify that the display indicates correctly.
9. Apply the maximum input signal and verify that the display indicates correctly.
10. Repeat Steps 6 through 9 until display reads exact.
## **BLOCK DIAGRAM**
**==> picture [257 x 176] intentionally omitted <==**
_Note The CUB4LP/CL display is factory calibrated to indicate 0.0 to 100.0 with an input of 4 to 20 mA at approximately 25°C._
## _**ORDERING INFORMATION**_
## _**TROUBLESHOOTING**_
For further technical assistance, contact technical support at the appropriate company numbers listed.
|**MODEL NO**|**.**<br>**DESCRIPTION**<br>**PA**|**RT NUMBERS**|
|---|---|---|
|CUB4LP|Reflective LCD Loop Powered Process Indicator<br><br>Red Backlit LCD Loop Powered Process Indicator<br>Positive Image Transflective LCD<br>*|CUB4LP00|
|||CUB4LP40|
|CUB4CL|Red Backlit LCD External Powered Process Indicator<br>Positive Image Transflective LCD<br>Yel/Grn Backlit LCD External Powered Process<br>Indicator Negative Image Transmissive LCD<br><br>Red Backlit LCD External Powered Process Indicator<br>Negative Image Transmissive LCD<br><br>Yel/Grn Backlit LCD External Powered Process<br>Indicator Positive Image Transflective LCD<br><br>|CUB4CL10|
|||CUB4CL20|
|||CUB4CL30|
|||CUB4CL40|
|MLPS|Micro Line/Sensor Power Supply<br>(Non-hazardous use only)<br>|MLPS1000|
|*Backlight intensity will vary depending on signal level.|||
Red Lion Controls 20 Willow Springs Circle York PA 17406 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839
Red Lion Controls BV Printerweg 10 NL - 3821 AD Amersfoort Tel +31 (0) 334 723 225 Fax +31 (0) 334 893 793
Red Lion Controls AP Unit 101, XinAn Plaza Building 13, No.99 Tianzhou Road ShangHai, P.R. China 200223 Tel +86 21 6113-3688 Fax +86 21 6113-3683
Updated at February 9, 2023
About Novapart
Novapart is a B2B electronic component broker specialising in stock shortages and cost reduction. We source hard-to-find parts and identify compliant alternatives across a catalogue of 410,000+ components from 500+ manufacturers.
Learn more →Stock Shortage Specialist
When a component is unavailable, discontinued or has an unacceptable lead time, we tap into our network of vetted European and Asian distributors to source what you need — without compromising on quality or traceability.
Request a quote →Compliant Alternatives
We identify pin-to-pin, electrically equivalent substitutes that meet the same certifications (RoHS, AEC-Q100, REACH) as your original specification — validated against datasheets, not just part numbers. Often at a lower cost.
BOM Analysis service →